CESIMod. RSP 5
CESI
INSPECTION REPORT CONFIDENTIAL APPROVED 84020696
Client
Subject
Place and
date
of inspection
Order
Notes
N. of pages
Issue date
Prepared
Approved
cEsiSpA,
SHENDA ELECTRIC GROUP CO.,LTD
No.17, Huatong Road, Jiangshan Economical Development Zone,
Zhejiang Province, China
Witness to type, special and routine tests on Power Transformer
Type SFZ-100000/220, Serial Number 120514-1
STRI-CTQC Laboratory, No. 18 Building, Hushitai South Avenue
Shenbei New District Shenyang Liaoning Province, P.R. of China
From October 10" to October xx, 2012
Agreement (CES! Quotation 84020084)
4 [Link] 79
September 3" 2014
TCE/CER/PRO Giorgio CRIPPA
TCE/CER Fiorenzo BREGANI
Page vaCESI
Mod. LETT. 12
Vesa
Protocolo 84020960 TCE-CER/PRO GC/kz
AE141SP001, B4020442
Data 5/09/2014
Object: dispatch documentation
Dear Sirs
Shenda Electric Group Co,, Ltd.
No.17, Huatong Road, Jiangshan Economical
Development Zone,
Zhejiang Province, China
Attn Mr. Zheng Jun
Tel: +86 570 4222602
Here enclosed we are sending you the following documents
* 1 original “Inspection Report” number 84020696 with annex Test report No.
CTQC/B-12.218 number B2033383 dated 23/10/2012.
Best regards
CESI spa
‘Testing & Certification Division
Business Area Certification
fofCESI rk
Fie
an
INSPECTION REPORT CONFIDENTIAL APPROVED Ba0z0005 =F GH
Table of contents
1 GENERAL
2. REFERENCE DOCUMENTS
2.1. Normative documents.
2.2 Test reports issued by Test laboratory
3. CONCLUSIONS .
Robb &
ANNEX 1: TEST REPORT CTQC/B-12.218 WITH CESI STAMP AND SIGNATURE (79 PAGES) ...4
Page 214CESI =
INSPECTION REPORT CONFIDENTIAL APPROVED —eaazoess «=~ EGH
}
1 GENERAL
CESI was entrusted by SHENDA ELECTRIC CO., LTD. to issue Inspection Report related to
type tests, special tests and routine tests performed on following Oil immersed Power
Transformer:
Manufacturer: SHENDA ELECTRIC GROUP CO.,LTD.
Type: SFZ-100000/220
Serial number: 120514-1
Year of manufacturing: 2012
Above tests, carried out at STRI-CTQC Laboratories, were performed according to IEC
standard and (for the ones not specified in IEC), according to GB standards.
Detailed applicable Standard edition are listed in paragraph 2.1.
Tests have been witnessed by CESI inspector, Mr Umberto Di Marco, who stamped and
signed every page of CTQC Test report of witnessed tests,
Pages of above report which have not been signed, refer to test not witnessed
(See paragraph 2.2. for details).
2. REFERENCE DOCUMENTS
2.1 Normative documents
[1] IEC 60076-1 (2011);
[2] IEC 60076-2 (2011);
[3] IEC 6076-3 (2000);
[4] IEC 6076-5 (2006);
[5] GB 1094-1 (1996);
[6] GB 1094-2 (1996);
[7] GB 1094-3 (2003);
[8] GB 1095-5 (2008);
[9] GB 76451 (2008).
2.2. Test reports issued by Test laboratory
[1] _ Test Report Nr CTQC/B-12.218, dated 23.10.2012, (See Annex 1), identified with CES!
reference B2033383
Note: CESI Inspector was not present to following tests and therefore relevant pages do not have
CESI inspector signature:
- Routine tests before Short Circuit;
~ FRA, winding frequency response (pag,. 38, 39)
- RIV Radio Interference voltage (Pag. 43)
- Transient voltage transfer (Page 49 and Annexe 2;))
Page 3/4CESI ke
INSPECTION REPORT CONFIDENTIAL APPROVED Baomoese” ««-EGH
F
3. CONCLUSIONS
On the basis of the test results , it can be concluded that the Oil-immersed Power
Transformer type SFZ11-100000/220, Serial number 120514-1, manufactured by
SHENDA ELECTRIC GROUP CO., LTD., passed successfully all performed tests listed
in Test report specified in par 2.2, in compliance with the reference specifications
listed in par 2.1.
ANNEX 1: TEST REPORT CTQC/B-12.218 WITH CES! STAMP AND SIGNATURE (79 PAGES)
Page aaCTQC
Nez CTOG/B-12. 218
CX-F-O1 Test Report
Total G0 Page 1
CONTENTS
Page
| Certification of report
[Link] report cover
[Link],
4Signing and issuing...
S-Test results.
6, Test object parameter
7. Sample condition description.
8. Standards.....ccsscceesss
9, Test items and conclusions......s.:s
[Link] 1: Rating plate and outline photo (Total page 1)
M1 Annex 2: Test ciruits (Total pages 10)
12,Annex 3: ‘Transformer drawings (Total pages 2) Cc Ee SI
ol Date
[Link] 4: ‘The table of check instruments (Total pages 4)
Protoc
82033383 23 October 2012
Signature:
ces
——————
Tnapection service
ak oN
Postal code: 110122 Tel: (024) 89874449
Address: Mushitai Sounth Aveniie No, 18, Shenbei New District, Shenyang
(024) 89872527
nttps //[Link] Fax: (O24)89707949 Tel: (
Boails ctgetvip.CX-F-01 CTQC
China National Transformer Quality Supervision And Testing Center
Shenyang Transformer Institute Co.,Ltd. Transformer Laboratory
Test — Report
Nes_CTQ0/B-12. 218 Total 60 Page 2
Test object
Test object arses SFZ -100000/220
iia Brand /
Entrusted Kind of
Ns Ee Trust testing
Manufacta- Sampling
wre aa Sept.19, 2012
‘Address Serial No 1205141
18C60076-12011,, GB1094.1-1996
16C60076-22011, GB10942-1996
1860076-3:2000,,GB1094.3-2003
Standards Testitems | See page 3-6
18C60076-5:2006, GB10945-2008
oBT6451-2008,
Techical contact,
The test results of routine tests, short-duration AC withstand voltage test,
temperature-rise test, measurement of sound levels, measurement of zero
sequence impedance on three phase transformers, measurement of the harmonies
of the no-load current, short-circuit withstand test, lightning impulse test,
long-duration no-load test, radio interference voltage measure
Results | of analysis of winding frequency response spectrum, determipatl a
voltage transfer characteristics of SFZ-100000/220 are ji gcordance
standards and technical contract. The sample passed t
Signing and issuing di
Period of validity 5 years
Note CES]
inepection service
‘Test witnessed by: Umberto Di Marco(CESI Inspector). weil Lr
On
Approved AR Checked by: Sunainentt=—~Goephief me Kiucai
Wh tf
Statement + {Testing report is invalid withoutCost special seal
2, Testing report is invalid without compiler, checker and approver’s signature.
[Link] inform CTOC in time after received the testing report if you have some disagr
to the testing report,
4 Test ing or witnessing only apply to sample,
5. Copying test ing certificate or testing report is forbidden without written permission From
CTaG(expect for copying al! the testing report)
Address: Hushitai Sounth Avenue No. 18, Shenbei New District, Shenyang Postal code: 110122 Tel: (O24) 89874449
E-aails etgetvip. sina, ecw huip: //[Link] Pax: (024)89707949 Tel: (024) 898725CTQC
Ne: CTOG/B-12. 218
Test Report
Total 60 Poze 3
Test results
Specified values Measured _velues
Ne | Test items 3 Sone
(instal on) Before S.C. After SCT. sions
‘Measurenent of .
dissipation factor
(tan 8 ofthe | Providing system capacitances :
capacitances
(Routine test) _
Determination of
capacitances
wwindings-io-earth
2 | and between | Providing capacitances See 4.1 See4.15.5.3 /
windings,
(Routine test,
special test) -
Measurement of
de. insulation aie
restr teen | vine inslaon
> | cach wining 10 | Providing absorption ratio aay Se04.15.5.5 /
vaindings | Rays)
(Routine test)
Check ofthe ratio a ary
and polity of | providing ratio measured value saa i
4. | buinearen | Previing ratio meased Not applicable Notappliable ,
Gansta x pola No built-in current | No built-in current
(Baiting tex) transformers transformers
Measurement of
voltage ratio and | The tolerances of voltage ratio +
5 check of | 40.5% 0.01% ~0.07% | 0.04% ~0.07% Passed
connection group | Connection group: Dyn Dynl Dyn
(Routine test) a
ere °F | saximum unbalancedness
6 | winding | Phase: <2% H.V@phase): 0.61% | [Link]): 0.70% | Passed
|| cronneteay | Lines <1%6 fives 0.08% | Levine): 0.139%
Measurement
7 | ofnmo-toad toss | 19%: 03 ol on asa
andcurent | Py (kW): 69.2 61.10 4 6249
(Routine test) ae
Measurement
ee 90% 110% | 909% 110%
8 pee acute ior | %: Providing measured value | 0.06 0.53 | 0.06 0.50 t
. 6 of | pykW): Providing measured value | 45.78 96.358 | 46.64. * 97.10
rated volage
Routine test) a L : +
TTest on on-load | According to Clause 10.8 of : 7
o | “apenanen |teceooreroitcstoss.- [Campy win [Cometh “s: | sag
(Kouinete) [1996 gape
Addees:
E-mails etqe@rip, sina, com
verified
Fax: (02189707949 Tel: (024) 89872527Test Report
CTQC
No: CTOG/B-12, 218
Total 60 Page 4
Specified values
Measured values
Conclu
Me Test
Standards : sions
Technical eonract) —_ | _B&fESC-T. | fer Sc-t. J
Switching
10 | impulse test Passed
(Routine test) pe aeeA
Separate-source 7s
11 | ACowithstand | HV. neutral: 200KV; 60s 200KVs 60s | 200KV; 60s | Ay
voltage test | LV. : BSKV: 60s B5KV: 60s B5KV; 60s =
(Routine test) a
Phase to earth west
=1. Umi Cv) 27 247.34
jon (s): 120 (tyf) 30 30
Long-duration [Link]/y3 (kV) 218 218.24
AC withstand | Duration(min): 30 30 30
2 Passed
voltage test | pD<500pC <40 <20
Routinetest) [11Um/Y3 (kV) 160 160,05
Duration(min): 5 5 5
PDS100pC | X20 <10
_ Frequency (itz): >50 200
Measurement of | t: 75°C —
short-cireuit | 2%: 13.0 £7.5% | 13.10 13.10
13. | impedance and | Py (kW): 296.0 +15% | 274.74 272.57 Passed
Toad toss | Pra (KW): 365.2 +10% | 335.84 334.66
(Routine test)
Breakdown voltage (kV): 240 | 62.7 ea
tn (90): <0.01 0.00049 0.00053,
‘Teston trans: | We iesoty
ia formerall” | Weerdssoived incit Cm), | sno Passed
Routine S| providing gas chromatography | Providing gos | Provi
| chromatography _ | chro
Tiree times each phase 3
Duration (s): 0.25: 10% 0.25
“Test waveshapes have no
Short-citeuit | “tortion No distortion
15 | wihetadlteg, | Deviation of reactance before
(Gpecia tes | ME aller SC.T.<2% 0.14%
- ‘Tre untanking inspection shows
‘no apparent defects No apparent defects
Successfully check items after
SCT. Passed
lghening Full wave Chopped wave
impulse test | [Link]):950. 1050 43% | 948,6~958.0 1055~1060
'6 | CRoutine test, [O ¢KV)s 400 __-43% | 396.0~401.2 Bassed
typetest) | LY.(kV): 200 220 43% | 199.0~2014 218.8~221.7 }
Adddvesss thshitai Sounth venue No, 18, Shenbei New District, Shenyang Postal code: 110122 Tel: (024) 89871449
E-mails etgetvip. sins. can tips //[Link] Fax: (024)89707949 Tel: (02489872527CTOQC
Noy OTOG/B-12, 218
Test Report
Total 60 Page §
Specified values
Mo ‘Test items Stndes Measured values read
a (Teehnical contract) =|
Measurement of
analysis of winding
17, | frequency response | Providing measured ascillogeams See 4.13 !
spectrum
(Special test) _ -
A phase-to-earth test with single phase supply
U; (kV): 395) 305.
Duration (s); 120 Cfyf? 30
U1 5Umy3 Cv) 218
Duration(min): 5 5
PDS500pC <10
L1Umif3 (kv 160)
Duration(min):. S 4
PD 1009C <10
Short-turation Ac Fm -
ig | withstond voage | Preqeney (H2)e >S0 200 eal
oer ey [A Phase-t0-phase test with three-phase supply
Uy (kV): 395 395
Duration (5): 120 Cfyf) 30
Us=1.3Um (kV) ~/3276
Duration(min):. 5 5
PD<3009C {sto
11Um (kV 212
Duration(min): 5 5
PD<100pC - <10
Frequency (Hz): >50 200
~~) Measuremen _- pr
19 | of'sound levels | Sound tevef Tam ABCA): / 65 Passed
(Special test) _ | Sound power level Layn dB(A): <94 | 86 A -
Measurement of the a. *
ay | harmonics of the | Providing no-load current Iy-tagmo load current )
no-load current | harmonic values of each phase harmonies
= (Special test) _| |
‘ _. | Applied voltage (kV): 277.2 2772 ara
Radio interference | Radi interference level V): <2500 | A: 467
2 voltage test ‘ Passed
(Special test)
Tnepection service ‘
sori m N\
GQ. oh fares
voeccnnsonfiai /
Address: Mushitai Sounth Avenue No, 18, Shenbot New District, Shenyang Postal codes 110122 Tel: (o24)89674449
Eomafls exqee au https /[Link] Fass (024) 89707949 Tel: (024)89872527CTOQC
No: CTOG/B-12. 218
Test Report
Total 60 Page 6
Specified values conclu
Ne Test items inate Measured values en
Standards _ (Technical contract) stone
Tong-duration | Applied vollage(kV). 1.1Ur 407
2 no-load test | Duration(h)s 12 12 Passed
(Special test) _| No Cot inl No CoH in oil
Measurement of 20
sequence impedance On |p. :tins zara seq
2 three phase geome S137 !
‘wansformers (Special ""P
tes) =
‘Applied pressure (kPa): 30 30
24 fndicess Duration Ch): 24 24 Passed
unin No leakage oil and damage No leakage oil and damage
“Temperature-rise iit (K):
Temperatureise | Top oils 60 55.7
= test(Typetest) | Winding: 65 HAV. :60.1 Paved
: LV 619
Determination of
transient voltage
26 | svancterchareetertics | Providing measured value See 4.26 !
(Special test)
en
Inspection service
verified by
E are
Aiddvesss lushitai Sounth ivenue No, 18, Shenbei New District, Shenyang
Ewald
etgestvip. [Link]
utp: //mew. etn. en
Postal codes 110122
Tol: (02a) 89874449
(oad) 89707919 Tel: (024)89872527CTOC
Naz CTOC/B-12, 218
Test Report
Total 60 Page 7
1. Test object parameters
Rated power (kVA): 100000
Um (kW): 252
Rated voltage (kV): 220/37
Rated current (A): 262.43/1560.4
Rated frequency (Hz): 50
Number of phases: 3
Tap range (kV): (22088 1,25% ) 37
Connection symbol: Dyn
Cooling method: ONAF
‘Temperature class of insulation: A
Insulation level: hv. line terminal SVLVAC — 750/950/395KV
hy, neutral LAC 400/200kV
Ly. Hine terminal LAC 200/85kV
[Link] condition description
Sample exterior construction and major dimensions( length, width, height) are in compliance with drawing.
Measured values: length is 7340mm, width is 6040mm, height is 280mm.
| Outline dimensions | ___Rating plate Body assembl} Core assembh
1SD.001.1619 8SD.011.1619 SSD.401.1619 SSD.301.1619
HV. lead LV. lead HV. winding L.V. winding,
6SD.801.1619 SSD.901.1619 68D.601.1619 6SD.701.1619
Rating, plate and outline drawings are in testing report annex, other drawings should be conserved by
‘enterprise after affirming by testing center,
‘The form, performance data , specifications of sample rating plate are in compliance with drawings.
igh voltage and low voltage side of the sample is clear and right.
jon and damage.
‘The marking of the phase sequence ot
The surface of the sample has no coll
3. Standards
GB1094.1-1996, 1£060076—1:2011 {Power transformers Part 1: General
GB1094.2-1996, 1EC60076—2:2011 «Power transformers Part 2: Temperature rise},
GB1094.3.2003, 1EC60076—3:2000 (Power transformers Part 3: Insulation les, diced
tests and external
clearances in air ¢
GB1094.5-2008, 1EC60076—5:2006 (Power transformers Part 5: Ability to withstand short circuit)
GB/TO4SI-2008 (Specifi
Technical contract,
requirements for oi-immersed power transforiners)
CESI
ae
Tnapection service
Vanified by 2s
Chi npares
Address: Washi tai Sounth Avenue No, 18, Shenbei New District, Shenyang Postal code: 110122 Tel: (024) 89874449
E-mails ctge@vip. sina, cow https //[Link] Fax: (02189707949 Tel: (024)89872527CTOQC
Nor CTQG/B-12..218
Total 60 Page 8
Test Report
[Link] items and conclusions
4.1 Measurement of dissipation factor (tan’) of the insulation system capacitances
(Routine test) Test date: Sept.26,2012
Humidity: 40%: Oil temperatures 23.7°C
Measurement position Cx (pF) tan
HVALY. &E 10270 0.0030
LVALY. &E 16270 0.0034
HvLN—e | 15510 0.0034
HY. ssi : 0.0025
4.2 Determination of capacitances windings-to-earth and between windings
(Routine test, Special test) ‘Test date: Sept.26,2012
See 4.1
4.3 Measurement of d.c. insulation resistance between each winding to earth and between windings
‘Test date: Sept.26,2012
Humidity: 40%: Oil temperature: 23.7°C
Insulation resistance (M@ )
‘Measurement position Rawls Rao
Roo Roo Ris |
HVA-LY. &E 35900 18300 15600 4 1.96
LV—HM. RE 65100 24000 16600 14s 2m
HY. LV | 32500 15900 11700 136 fo
HN. —LY. ’ 25900 16800 154 !
Core + | 10000 Js.
Clamp—E i 8000 I
CES!
es
Inepection sarvica
Verified by
ee
Adresse thishitai Sounth Avenue No. 18, Shenbet New District, Shenyang Postal eodes 110122 Tel: (024)89874449
E-mails etge@vip. sims. cou https //omen-ctneen Fax: (02089707949 Tel: (024)89872527CTQC
Test
Report
Nez CTQC/B-12, 218
Total 60 Page 9
4.4 Check of the ratio and polarity of built-in current transformers (Routine test)
Because the sample doesn't fix current transformer, it doesn t put up this test item.
4.6 Measurement of voltage ratio and check of connection group (Routine test)
Test date: Sept.26,2012
HY. LY. _ Measured deviation (%) ‘Cannes:
= . tio = tion
patton | cA¥5" | postton_| “aS” App | pete | cate | group
1 | 242.000 6541 0.02 003 | O04
2 | 239.250 6.466 0.02 0.04
3 | 236.500 6392 002 | 00 0.04
4 | 233.750 6318 0.02 0.03 | 004
5 | 231.000 6243 0.02 0.03 | 0.05
6 | 228.250 6.169 0.02 003 | 00s
7 | 225.500 6.095 0.04 00s | 0.06
8 | 222.750 6.020 005 | 007
F 910,11 | 220000) 37 5.946 oos | 007 | Dynt
2 | 217250 5.872 005 | 0.07
P13 | 214.500 5.197 006 | 0.07
14 | 21750 5.723 006 | 0.07
—_15 | 209,000 5.649 0.06 | 0.08
16 | 206.250 5574 0.06 | 0.08
17 | 203.500 5.500 0.06 | 0.08
18 | 200.750 3.426 0.06 | 0.09
19 | 198.000 5351 0.06 | 0.09
Result: Passed.
CESI
verified by
pection service
Address: Hushitai Sounth Avenue No,
E-nails etqodvip. sim, com
Shenbei New Distric
hutpe //ews. etn. en
|. Shenyay
Postal code: 110122
Faxs (024) 89707919
Tel : (024) 99874419
Tel: (024)age72527CTQC
Ne: CTOG/B-12. 218
Test Report
Total 60 Page 10
4.6 Measurement of winding resistance(Routine test) ‘Test date: Sept.26,2012
Oil temperature:
7c
Measured values ( ) Unbatancedness
Winding Tap position a aaa ae oe
a a~b bee oma
1 0.6142 0.6175 0.6167 od
0.6072 0.6067 053
a oss | 0.3966 0.50
0.5868 0.5864 051
0.5767 0.764 0.52
| 0.5666 0.5663 0.57
05566 | 0.5564 058
0.5463 0.5461 061
HY. 5347 o.s340 047
0.5465 0.5461 0.59
0.5564 0.5562 0.52
0.5667 0.5663 os _|
05768 | 10.5764 052
05871 | _ 0.5866 053
_| 0390 0.5966 050
0.6075 0.6070 053
Se J 0.6176 0.6169 055
Lv. ! 0.02330 0.02329 | __ 0.02330
Result: Passed,
Inspection
verified by
A
4.7 Measurement of no-load loss and current (Routine test) spall Ne 26,2012
e
‘Test circuit is givenin Annex?2-a .
voltage (kV) Nos load
linge Applied voliage (KV) load current Nostoaoss. (kW)
tnuiple | Reading of mean value [ Reading ofems. | ¢q, | qq | Measured
voltmeter voltmeter value
90% Uy 33.300 33.280 1.01 0.06 45.16 45.78
100% U, 37.000 37.043 1.15 oul 61.7
110% U, 40.700 J 4naaz 8.32 0.53 98.35
Result: Passed.
Address: Hashitai Sounth Wenne No. 18, Shenbei New District, She Postal code: 110122 Tel: (02489814449
https //[Link] Fax: (024) 89707949 Tel: (024)898725:27
Femail: ctgetelCTQC
No: C10C/B-12. 218
Test Report Total 60 Page 11
4.8 Measurement of no-load loss and current at 90% and 110% of rated voltage (Routine test)
See 4.1
4.9 Test on on-loa tap-changers (Routine test) Test date: Sept.26, 2012
Operation test:
a. 8 complete operating cycles with the transformer not energized(a eycle of operation goes from
one end of the tapping range to the other and back agin).
}. complete operate cycle with the transformer is not enengized, with 85% ofthe rated
operation voltage.
€. Leomplate operating cycle
Frequency at no-load.
4d, With one winding short-circuited and made rated eurrent in the tapped winding, 10 eyctes
of tap-change operations across the range of two steps on each side from where a coarse or
reversing changeover selector operates, or otherwise from the middle tapping( the tapchangger
will pass 20 times through the changeover position).
Result: Passed.
the transformer is energized at rated voltage and rated
CESI
eae
‘Nepection service
verified by
S
4
cibei New District, Shenyang Postal codes 110122 Tel (oz4)89874449
hetps //[Link] Faxes (0208070799 Tel: (O2d)89872527
jourath Avenue No. 18,
Address: shiv
vip. siCTQC
oT + CTOC/B-12. 218
Test Report “ i
Total 60 Page 12
ing impulse test (Routine test) Test date: Sept.26,2012
4.10 Switel
Humidity: 43.3%; Ambient temperature: 20.6°C; Atmospheric press: 99.9KPa.
‘Test items and voltage
‘Tested terminals Rated withstand voltage (kV) Tap position
A,B,C 750 1
‘Test sequence:
One reduced negative polarity switching impulse;
Three rated negative polarity switching, impulse
Test record
‘Th:Front time; TD:A total duration from the virtual origin to the first zero passage:
‘Va:Time above 90%Up: —_Up:Peak voltage.
Result: Passed,
CESI
a
inepection Service
verified by
i
A
hi Avcnue No. 18, Sheabei New District, Shenyang Postal codes 110122 Tel : (024) 80874449
https //[Link] Fax: €024)89707949 Tel: (024)898725¢7
Address thishi tai Sou
E-mails etgedvip. sitCTQC
Test Report
Ne: CTOC/B-12. 218
Total 60 Page 13
Address; Hush tai Sountt Avenue No, 18, Shenbei Nex District, Sheny
1
‘Tested terminal: A Test polarity: Negative
‘Prat Tora i840)
Inepection service
Verified by
8
cctgedl ip, sina e3m hetps //amw. etn, en
og
Postal code:
Faxs (024989707949
noi
[Link] records CH2, Neutral current records
f
Tel: (02089374449)
Tel: (024)89872527
JCTQC
+ CTOC/B-12. 218
Total 60 Page 14
Test Report
Tested terminal: B Test polarity: Negative [Link] records CH2. Neutral current records,
i ae a a
Inepection service
verified by
Address: Hashitai Sounth Avenue No. 18, Shenbei New District, Shenyang Postal code: 110122 Tel: (O24) 8871449
B-aail: etgo@vip. sina, con https //wew,[Link] — Raxs (024)89707949 Tels (024) 89872527CTQC
Nez CTOG/B-12, 218
Total 60 Page 15
Tested terminal: C Test polarity: Negative CHIVoltage records CH2. Neutral current records
PS Pras Gt 1 zzIBLT) |
‘Inspection service
vanifiag by
ounth Avenue No, 18, Shenbei New District, Shenyany, Postal code: 110122 Tel: (024)89874449
‘08 hutps //[Link] axe (024)89707919 Tel: (024)89872527
Ie etgetvip.Nez CTOC/B-12. 218
Total 60 Page 15
Test Report
4.11 Separate-source AG withstand voltage test (Routine test) Test date: Sept.27,2012
‘Test circuit is given in Annex2-b
Humidity: 45%: Oil temperature: 24,0°C; Atmospheric pressure: 99.0kPa
Position Applied voltage (kV) Duration (5) Result
HY. neutral
VRE 200 60
- Passed
LVHLY. &E 85 60
4.12 Long-duration MC withstand voltage test (ACLD) (Routine test) Test date: Sept.28,2012
‘Test circuit is given in Annex2-c
Phase to earth test, tap position 10, _fiequeney 200Hz,
Induced voltage " Partial discharge levels (pC)
Phase-to-earth | Duration
Multiple fo A B c
11Umy3 160 5 min <2 <20 <2
Up [Link]/ a 2
Bb 218 5 min <20 <20 <20
~USLTUny 7 -
o 247 30s / / !
Sain <20 <2 <20
<20 <40 <20
Up [Link]/ 15 min <20 <40 <20
Bp 218
20 min <20 <40 <20
25 min <2 <40 <20
<20 <40 <20
Luma 160 Simin <20 <20 <20
Note: Um=252kV <
Background noise level is <20pC before and affer test,
Sart voltage: 218kV Extinction vollogg> OV.
Result: Passed a
Verified by?
|
Address: Hushitai South ivenue No. 18, Shenbei New District, Shenyang Postal codes 110122 Tel: (024)89874449
0 https //aws,etnen Fax: (024)89707919 Tel: (O24)R9872527
E-mails exgetCTQC
Nez CTOG/B-12 218
Total 60 Page 17
Test Report
4.13 Measurement of short-circuit impedance and load loss(Routine test) Test date: Sept.28,2012
‘Test circuit is given in Annex2-d
TL, shor
Aaplied current impedance Load oss cKw) | Tea oss
= 1 Measured |__CEach phase) 4
Winding | TP | voltage | o Measured | Comeated | Conected
postion: i vy | 6? | CO [value | value value
wi} & EBT BC rc
Ht [ier tr
a 1 [12233 | s127 | 16.963 | 0.06 ass | 338.63
| 10 146.62 | 55.87 | 16098 | 63.40 274.74 335.84
oe AONE: | 4
115537 | 53.28 | 13.s8 | siso so789 | 388.99
Result: Passed.
4.14 Test_on transformer oil (Routine test) Test date: Sept.26, 2012
tan (90°C) Breakdown voltage (kV) Water
0.00019 27 8.68
Gas chromatography( before routine tests ) ‘Test dates Sepl.26, 2012
wLL
Hy co co, | cy CH Cally Cath | Mydrocarcons
0.00 9.82 6331 | 007 0.00 0.00 0.00 0.07
Gas chromatography (after S.C:T test) Test date: Oct. 11, 2012
we
th co | cy Call Gly Goth | Hydrocarions
0.00 104s | 7709 | 036 0.00 0.00 0.00 036
Gas chromatography (aller insulation test, before long-duration no-load tesl,) Test dates Oct.15, 2012
w LL
ra co, | chy Call Gly Gott] Hydrocardons
0.00 12.01 79.54 | 037 0.00 0.00 | d00 037
Gas chromatography (afler long,
Result: Passed. |
Ividress: tshitai Sounth Avene Ho. 18,Shenbet Nox District, Shenvang Postal code: 110122 Tel: (024) 89871449
E-mail: etge@vip. sina. cox http: //aww,ctncn Fass (024)89707919 Tel: (02489872527CTQC
Nor CTQG/B-12, 218
Total 60 Page 18
Test Report
4.15 Short-circuit withstand test (Special test) Test date: Oct. 10,
4.15.1 Calculated short-circuit current (Reference temperature 75°C)
HV. current value (AD LV. current value (kA)
Ty irl The rm.
” | tetmipakar | Themsvaueot | Tetstzekof [Ticrms wlio) Mul
position | the asymmetrical | the symmetrical 7 SIRE te ities cKy2 >
Shortcreuit current short-circuit curent | shore nda current | short-cut earent
1 24.47 2.550
on 25334 2.550
19 5398 207 25.02 981 2.550
4.15.2 Measurement of short-circuit current
‘Test citeuit is given in Annex 2-e
Perform single-phase test, supply is provided between one line terminal and the other two line terminals connected
together, 9 times, Test waveshapes have no distortion. Test oscillograms are shown in Page SO~S8.
HY. current value
Ty “The first peak of the ‘The rims, value of the .
e symmetrical symmetrical fra | Dura- Serial
posi- | Phase short-circuit current(A) | cA) | ton No
i: Measured 6)
value %)
re) _|
- 104.0 1598 943 0 | 025 | Br2ais-sor
ape | 4526 104.8 1608 oa 6 | 02s | Biz2is-so2 |
4534 105.0 1621 95 0 [025 | Bizais-sos
LLY. current value
The first peak of the asymmetrical “The rams. value of the symmetrical
15 phase i curren(KA) ___1.5 phase short-circuit current(kA)
a 0 c ca _ Zr ec
24 L 24.03 892 us 891
24.01 __|_ 23.96 889 | 1 89 |
23.86 t 23.81 882 1 8.82
Note: Ia is the earthing current of oil tank: CEST
Wepection service
verified \
Gn ZL i \
District, Shenyang Postal cade: 110122 Tel: (024)g9874449
(oa) 89707919 Tel: (024) 89872527
Address: Mush tai Sounth Avenue Xo, 18, Shenbe
E-mails etgcdvip. sina. cow etn //[Link] FaCTQC
Ne GTOC/B-12. 218
Test Re
port Total 60 Page 19
__ HY. current value
Th “The frst peak of the ‘The ran.s value ofthe itict,
: asymmetrical symmetrical i Serial
posi | Phase short-circuit ourrent(A) | fag | H" Ne
Use Measured Measured ®
value (%) value cm) AX
| ow re) _| |
499 101s 1821 oa 0 | 02s | Br221s-sos |
pac | 4992 oa 1823 cas | 0 | 025 | przais-sos
4992 ola 1829 94.8 o | 025 | praais-so6
- _ LN. current value :
“The first peak of the asymmetrical “The rm. value of the symmetrical
w 1.5 phase short-circuit current(kA), 15 phase short-circuit current(kA)
| a b « a b ©
25.44 25.54 ! | 941 9.40 s |
234d asso | oAl 94h /
2534 25.29 ! 942 9.40 t
| HY. current value
Tap The fist peak oF the The ram. value of the
asymmetrical symmetrical Serial
posi- | Phase shortcireuit current (A) | short-circuit current (A) | yg | tion Me
- Measured Measured (s)
value (%) value (%) ca)
_ (Ay «|
538 998 1980 93.5 0 | 025 | Biazis.so7
cap | 5397 wooo | 1984 | 937 0 _.| 025 | Bizais-sos
5382 99.7 igs0 | 93.5 0 [0.25 | Bi2218-s09
LLY, current value
‘The first peak of the asymmetvical ‘The nn, value of the symmetrical
9 ____L.5 phase short-circuit current(kA) 1.5 phase short-circuit current(kA) :
a b ce
aso | 1 9.19 919
25.11 ! 9.20
25.08 9.18
vari
Address+ Hushitai Sounth avenue No, 18, Sherbet Now Distriet, Shenya {10922 Tel = (OzABOBTAAN
E-mail: etgetip. sina. cor tips //ww. 6 Tel: (024) 99872527croc
Nes CTOG/B-12. 218
Test Report Total 60 Page 20
4.15, 3Measurement of short-circuit reactance each shot
‘Tap Measured reactance value (® ) Deviation of reactance €%)
posi- a = =
Sais A B A B ©
Before 80.20 80.96 79.89 1 t !
U 80.24 80.96 79.95 <0. <0 <0
' 2 80.17 80.96 79.92 <0 <0 <0
i 80.02 80.93 7991 02 <0. nae Rest |
‘Atmospheric a a - No leakage oll and
pressure damage passed
4,25 Temperature
se test (Type test) Test date: Oct.18, 2012
The testis conducted by means of short-cireuit method, test duration is 14h, stability duration is 4h. Tap 19.
Measure top oil temperature-rise: Specified total loss is 388.1 5kW, injected total loss of 388.15kW during test
Measute winding temperature-rise: Specified current is 291.59A, injected test current of 291.594 during test.
Conclusions of temperature-rise
‘Top oil temperaturesise (K) 557
HWY. 60.1
Winding temperature-tise CK) >
Lv. a9
Result: Passed.
CES!
a
Inspection service
Address; Mushitai Sounth venue No, 18, Shenbel New District, Shen
Fant
ang Pos
codes 10122 Tel: (O24) 89874449
ge6vip. sina, eon herpes //awectnen Fars (O24) 89707949 Tel : ((24)89707051CTOQC
Test Report Mis CTOC/B-12. 218
Total 60 Page 45
Inspection service
Ss,
Lene ote ated Guk naces
Tas aaa ao
Initial average icuid temp, 575 C Estimated winding time constant
Final average tiquid temp, S20 Estimated average liquid temp,
Licuid temperature slope | _ 0.18 Kimi} Estimated winding to Bquid temp.
Ai iis ‘op va po nt ha dom
le 8.0078 [= ee
te overs i aaa
Ri wy “a Ow Bul
Pare! a) Pare ee | mwa | omar | 2 conewea | 8%, | 2” | owen?) ott] Sa
107] A | measured and r Abul) calculated
vaidatea | 5)
ia
| 7 7551
1 7 7 Tat
4 | 7309 | -1415 |-103.40 | 5342.14 | oG974 | 7259
i | Wao | -1204 | -8688 | Si67.53 | 06108 [7132
7 | 7085 | 0990 | -7048 | 5025.58 | 05485 | 7008
r+ | 0. 4991.50 | 0.4864 | 69.96
i fanaa ona [038
i ‘tee 038 | 7
i ‘eazat| oss | 68
a 4530.40 |
i eit
+ ‘ats
;
i
eae
cor [7
ee | t
oer | i
waa | i
oa | 4
| e398 | 7 | 4093.96 |
6383 | 1 ag74.39 [00712 | 59.77
e360 | 1 ‘4054.87 | 0.0631 | 59.47
was | 1 404074 | 00560 | 59.18
6346 | i 4026.64 | 0016 | 588)
om | i 4012.56 | 0.0040 | 56.63
6328 | 7 | 00390 | 58.37
e321 | it 3095.10 | 00346 | 58.12
6344 | 3906.38 | o.0307 | 7.8
S7 | e307 | + x [sarz.e7 | 007re }
- “Omen 75)» 2138 6,
HAV. Wang ama 186 AO y= (O,g- Om can) 718 -87.9)%( Sor gg ) 99.8 O04
Address: Mushitai Sounth Avenue No, 18, Shenbei New District, Shewvang — Postal cade: 110122 Tel: 024)8987449
(02089707919 Tel (oeadagrOTaSI
E-mails etgedivip, sina, com tips //emetnen FaCTQC
Ni; GTQC/B~12.218
Test Report
Total 60 Page 46
GEST
Inspection service
verified by
Legend: Data to be inserted Go. hayes
‘Tine interval [i min
Aol average Hud temp, [575 © | Estimated winding tine constant
Final average-fiquid temp, Beet Estimated average liquid temp.
Liquid temperature slope [0.18 _Kimit] Estimated winding to gud tomo.
‘Amar variables ‘Average winding temp, atthe instant of shut down
tor «75210 a sa sb %
te= o.r202 (Ris Sime] —27| nt [aveser[Ta0at
{ Tea
|reme] 9 foonge| Oma | catia {2 | | yyy?) gcera| SA
fms] 2] AW |g SByeg | OM | Owcorn |i | COmeeted | prog | | min?| 0 a5
* | moa | ‘aig | toss | 28m calculated
a oe |}
im [A i 7759 |
[2 | 2a08 0 177
3 | 2774 1 sa42.i4| 06974 | 7413 |
“4 | 2760 i 506528 | 0.6351 | 7205
5 | 2748 1 5197.60 | 0.5670 | 71.31
6 | 2737 1 5048.40 | 0.5061 | 70.09
< 493263 | 0.4518 | 6898
1 e020 | 0.4034 | 67.08
1 705.11 | 03601 |
1 | 6800 | 0.507 | 4057 | 460362 | OAD14 | Ge22
act g | 4587.87 | 02670 | 6845
[4 arte | 02562 | 6474
1 242773] 02267 | 6409
1 57.13 | azoaz | 62.49
iE as2.7 | 0.1623 | 6293
1 wa0na2 | 0.1627 | 6241
1 #24587 | 0.1452 | 6103
7 421i45| o1207 | 6149 |
ai77az| 01167 | 6107
4143.63 | 041033 | Go67
ar2az2 | oa22 | 6030
i060 | 00823 | 5198
a0ri31| 00735 | 5861
065 27| 0.0656 | 5830
032.00} 0.0506 | 5899
2ei | atz7e7| 00523 | 5870
w 00467 | 5842
2.50 [4o0a74 | 00417 | 8016
953 | 398466 | 00372 | 5790
24a [3a7ae7| oosa | 5764
291.59 6,
+398 = 61.9
201.60 “
LV, Winding temp.~ise (1: AB yy Y'+00,4= ( 79.6 -57.5 ) x (
L
Address: Mushitai Sounth Avemw No. 18, Shenbei New District, Shenyang Postal ede: 110122 Tel
E-mails ctqoteip. sina
(ozaysox7eu19
http: //[Link] Faxs (024) 89707949 Tel: (024) 89707951
Potrebbero piacerti anche
20169E00
Nessuna valutazione finora
20169E00
17 pagine
Cei 3
Nessuna valutazione finora
Cei 3
68 pagine
Cei 7-11 PDF
Nessuna valutazione finora
Cei 7-11 PDF
18 pagine
Cei 20-19-13
Nessuna valutazione finora
Cei 20-19-13
16 pagine
Cei 20-20-11
Nessuna valutazione finora
Cei 20-20-11
10 pagine
Cei 20-29
Nessuna valutazione finora
Cei 20-29
16 pagine
Cei 20-51
Nessuna valutazione finora
Cei 20-51
20 pagine
Cei 20-46
Nessuna valutazione finora
Cei 20-46
12 pagine
Cei 20-37 6
Nessuna valutazione finora
Cei 20-37 6
12 pagine
Cei 20-19-8
Nessuna valutazione finora
Cei 20-19-8
14 pagine
Cei 20-24
Nessuna valutazione finora
Cei 20-24
28 pagine
Cei 20-20-13
Nessuna valutazione finora
Cei 20-20-13
20 pagine
Ris Manuale
Nessuna valutazione finora
Ris Manuale
36 pagine
Cei 20-44
Nessuna valutazione finora
Cei 20-44
20 pagine
Cei 20-17
Nessuna valutazione finora
Cei 20-17
28 pagine
NT 333
Nessuna valutazione finora
NT 333
2 pagine
Cei 7-6
Nessuna valutazione finora
Cei 7-6
16 pagine
Condo 4
Nessuna valutazione finora
Condo 4
45 pagine