CHECK CONFIGURED ANALOG SCALLING AND ANALOG ALARM/TRIP LEVELS ARE CORRECT (AS PER SPEC BY ENGINEERING)
CHECK FOR CONFIGURED ALARMS/SIGNALS FOR HMI
RECORD
DIGITAL INPUTS-
CHECK EACH OF THE DIGITAL INPUT BY TOGGLING THE SWITCHES ON THE SIMULATION PANEL
CHECK THE CORRECT RACK/SLOT/CHANNEL LED ILLUMINATES ON INPUT MODULESAND CORRESPONDING HMI DISPLA
CHANGING THE DEVICE COLOR AS PER THE SPECIFICATION IN THE HMI
CHECK CONFIGURE HMI ALARM IS CORRECT (AS PER ENGINEERING )
RECORD
DIGITAL OUTPUTS-
USE ENGINEERING STATION FORCE ON (ENERGISE ) EACH OUTPUT
CONFORM THAT CORRECT RACK/SLOT/CHNNEL/ADRESS LED ILLUMINATES ON OUT PUT MODULE
CONFORM THAT CORRECT LAMP/SYMBOL ON SIMULATION PANEL TURNS ON
CHECK CONFIGURE HMI ALARMS IS CORRECT (AS PER ENGINEERING)
RECORD
ANALOG OUTPUTS-
USE ENGINEERING STSTION FORCE ON (ENERGISE) EACH OUTPUT
CONFORM TAHAT CORRECT RACK/SLOT/CHANNEL/ADRESS ASSIGNED ON OUT PUT MODULE
CONFORM THAT CORRECT LAMP/SYMBOL ON SIMULATION PANEL TURNS ON
CHECK CONFIGURING HMI ALARMS IS CORRECT (AS PER ENGINEERING)
RECORD
ALL THE DIGITAL INPUTS INTO ITS NORMAL POSITION "OPEN" OR "CLOSE" AS PER NORMAL PROCESS OPERATING CONDITION
ALL ANALOGUE INPUTS INTO ITS NORMAL POSITION "LESS THEN HIGH SETPOINT" OR "MORE THEN LOW SETPOINT"AS
NORMAL PROCESS OPERATING CONDITION
LOGIC TEST
EACH LOGIC SEQUENCE WILL BE TESTED EXACTLY AS PER THE CONTROL LOGUIC DIAGRAM FROM ENGINEERING AND OROC
OPERATING CONDITIONS , WITH EACH STEP PERFORMING IN SEQUENCE AS PER ENGINEERING.
ANY CORRECTION REQUIRED WILL BE DONE THEN OR AT THE END OF THE TEST BASED ON CURRENT REQUIREMENT
REDUNDANCY CHECK
CPU REDUNDANCY CHECK
CHECK CHANGEOVER OF CPU
POWER SUPPLY REDUNDANCY CHECK
ETHERNET SWITCH REDUNDANCY CHECK
RIO BUS REDUNDANCY CHECK
CHECKED BY-
VARIFIED BY-
APPROVED BY-
OK FAULTY REMARK