INDEX
1. WARNINGS page.13
2. LAYOUT AND CONNECTIONS page.13
3. TECHNICAL SPECIFICATIONS page.14
3.1. Description of components page.14
3.2. Description of terminal-boards page.14
3.3. Anti-crushing function page.14
3.4. Over pushing stroke page.14
4. PROGRAMMING OF THE LOGIC page.14
ENGLISH
5. PROGRAMMING THE SPEED page.14
6. START-UP page.15
6.1. Leds check page.15
6.2. Programming the Dips-switch page.15
6.3. Time - setup learning page.15
7.INSTALLATION OF BUS ACCESSORIES page.16
7.1. Addressing the BUS photocells page.16
7.2. Memory storage of BUS accessotries page.17
7.3. Memorising the BUS encoder page.18
8. MEMORY STORING THE RADIO CODE page.18
8.1. Memory storage of - JLC (Amigo-Kilo) radio controls page.18
8.2. Memory storage of 433 RC (Bravo - Echo) radio controls page.18
8.3. Radio controls deletion procedure page.19
9. BATTERY KIT (OPZIONAL) page.19
10. AUTOMATED SYSTEM TEST page.19
11. FUNCTION LOGICS page.20
EU DECLARATION OF CONFORMITY
The Manufacturer
Company name: FAAC S.p.A. Soc. Unipersonale
Address: Via Calari, 10 - 40069 Zola Predosa BOLOGNA - ITALY
hereby declares under its own exclusive liability that the following product::
Description: Control board
Model: BRAIN 15
complies with the following applicable EU legislations:
2014/30/EU , 2011/65/EU
Furthermore, the following harmonised standards have been applied:
EN61000-6-2:2005 , EN61000-6-3:2007 + A1:2011
Bologna, 01-06-2017 CEO
1. WARNINGS
Before attempting any work on the control unit (connections, maintenance), always turn off power.
Install, upstream of the system, a differential thermal breaker with adequate tripping threshold,
Always separate power cables from control and safety cables (push-button, receiver, photocells, etc.).
To avoid any electrical disturbance, use separate sheaths or a screened cable (with the screen earthed).
Fig. 1
ENGLISH
Fuses F2 = T2A-250V BUS Safety devices with BUS technology
or RED
T4A-120V terminal
Function logics A, E, AP, EP,A1,B,C J2
SERVICE Service Light control output (connect a
Work time (time-out) 1 minute (maximum) GREY LIGHT relay coil at 24Vdc-100mA max)
Varies according to learning terminal
Pause time
(max. 10 min.) J3
Open A, Open B, Stop, BUS
Terminal board inputs ORANGE LAMP Flashing lamp 24Vdc - 15W
(I/O)
Power supply, battery radio terminal
Connector inputs J4
module 3 pins
Electric lock 12Vac or 24 Vdc (to be
Motors, flashing lamp, power LOCK
BLUE installed on leaf 1)
supply to accessories, electric
Terminal board outputs terminal
lock, service light contact (90
sec fixed) J7 MOT1 Motor 1 (leaf 1)
Logic (A, E, AP, EP,A1,B,C), J8 MOT2 Motor 2 (leaf 2)
Programmable functions
Speed (High - Low)
Pause time, The service light control is active as specified in advanced
Learning functions function 9 Table 4:
leaf closing delay
- for the entire opening and closing movement of the gate
and for a further 90 seconds (standard operation)
The power supply and the fuse are related to the - when the gate is closed (closed status function)
purchased version.
Leaf 1 means the leaf which opens first during the opening
Different output values can be obtained on the board operation.
supply terminals depending on the mains voltage va-
lue. Before start-up always check if the output voltage 3.3. Anti-crushing function
on the transformer secondary winding is between 20 The electronic anti-crushing function is obtained by controlling the
Vac and 26 Vac. Voltage must be measured load free. current consumption or the encoder of the motors connected to
the BRAIN 15 equipment.
3.1. Description of components If the gate detects an obstacle during the opening or closing move-
J1 POWER SUPPLY connector ment, the anti-crushing function activates and reverses the sense
of direction of the operator, thus increasing the safety degree of
J2 SERVICE LIGHT command terminal-board
the automated system.
J3 FLASHING LAMP terminal-board
J4 ELECTRIC LOCK terminal-board 3.4. Over pushing stroke
J5 COMMANDS terminal-board If you enable this function, at every OPEN pulse the leaf on which the
J7 MOTOR 1 terminal-board electric lock is installed starts its closing movement for a few seconds.
This facilitate release of the electric lock.
J8 MOTOR 2 terminal-board
J9 Rapid connection for RADIO MODULE 3 pins
J10 BUS terminal-board 4. PROGRAMMING OF THE LOGIC
J11 BATTERY connector Repeatedly press the SW3 LOGIC push-button to select one of the
SW1 SET UP push-button 7 programming logics available.
SW2 SPEED push-button The selected logic is signaled by the LD7 LED:
The number of blinkings corresponds to the number of the se-
SW3 LOGIC push-button
lected logic.
DS1 Programming Dip-switch See paragraph 6.3.3.
F1 Accessories protective fuse
F2 Fuses protecting transformers and motors 5. PROGRAMMING THE SPEED
LED Signalling LEDs The function speed can be adjusted at any time by pressing
push-button SW2.
The selected logic is then displayed on LED LD8:
Led on = HIGH speed
Led off = LOW speed
Page 16 BRAIN 15
6.1. Leds check Before any manoeuvre is executed, a SETUP cycle must
first be run.
The following table shows that status of the LEDs in relation to the
status of the inputs (the closed at rest automated system condition If the motor type is changed with the DS3 and DS4 dip-
is shown in bold). switches after the SETUP, a new SETUP is requested.
Check the status of the signalling LEDs as per table below:
Tab. 1 - Operation of inputs status LEDs When the board is powered up and a SETUP cycle has never been
executed, LEDs LD4 and LD5 begin to flash slowly to signal that
LED ON (closed contact) OFF (open contact) a SETUP cycle must be executed.
STOP Command disabled Command enabled There are two possible types of SETUP: AUTOMATIC and MANUAL
OPEN A Command enabled Command disabled 6.3.1. AUTOMATIC SETUP
OPEN B Command enabled Command disabled 1. Set the operators for manual operation and take them to
ENGLISH
13. Send an OPEN command to determine the start of the Tab. 4 - Programming features
decelerated part and wait until the closing mechanical stop
point is reached.
N° pressure
N° flashes
Function
14. When leaf 1 reaches the closing mechanical stop point, the
LD7 off
Menu
SW2
LD8
LD7
setup phase is completed. If it has been performed correctly,
on
LEDs LD4 and LD5 turn off. If this is not the case, LEDs LD4
and LD5 flash and the setup procedure must be repeated.
ENGLISH
closure is set by default. To change it, execute a second Preliminary
4 4 4 SI NO
level programming (see paragraph 6.3.4.). blinking
Leaf opening
5 5 5 SI NO
Pause time and leaf delay values can be modified, both delay
at closure and at opening, by simply programming the counting
second level parameters, without repeating the setup Leaf closing
6 6 6 of delayed —
procedure. delay
leaf
counting
6.3.3 PROGRAMMING OF THE LOGIC 7 Pause time 7 7 —
time break
Repeatedly press the SW3 push-button to select one of the 7 Stop point se-
programming logics available. The selected logic is signaled by arch space
the LD7 LED. The number of blinkings corresponds to the number (function active LOW HIGH
of the selected logic: 8 8 8
only if Long leaf Short leaf
Tab. 3 - Selection logic PROcoder avai-
N° N° lable)
Logic pressure blinkings closed sta- standard
SW3 LD7 9 Service Light 9 9
tus function function
“A”
1 1 With menus 6 and 7, keep the LOGIC push-button pres-
Automatic
“E” sed until reaching the time to be set. The time can be
2 2 set between 0 and 4.25 minutes.
Semi-automatic
“AP” Windproof function: The windproof function allows the gate to
3 3 operate even in gusts of wind. The obstacle search time is set at
"Stepped" automatic
“EP” 5 sec. and commands motion reversal.
4 4 Reverse stroke: With the gate closed, the reverse stroke function
"Stepped" semi-automatic
entails that before opening, the motors push in closing for approxi-
“A1”
5 5 mately 3 seconds to facilitate release of the electric lock.
Automatic 1
Soft-touch: The soft touch function allows the leaves, after having
“b” touched the stop in closing, to move back to then lean delicately.
6 6
Semi-automatic “b” This function can be useful to respect the impact curve required
“C” by standards in force.
7 7
Dead man Pre-flashing: Activated approximately 3 sec. before each opening
and closing movement
Leaf opening delay: Delays opening of leaf 2 respect to leaf 1,
6.3.4. SECOND LEVEL PROGRAMMING thus preventing interference between the leaves.
To enter the second level menu, keep the SW2 SPEED push- Leaf closing delay: Delays closing of leaf 1 respect to leaf 2.
button pressed for more the 2.5 seconds. The two SETUP LEDs Standby time: In A, AP, A1 logics, this is the time set for the leaf
are permanently lit. In this mode, the SPEED push-button is used to reclose after opening.
to scroll the menus. The different menus are identified by the Stop point search space: This parameter adjusts the mechanical
number of blinkings. stop search angle within which the board stops the movement
The parameter value is set with the LOGIC push-button. The menu without reversing if an obstacle is encountered or the mechanical
is scrolled sequentially. Keep the SPEED push-button pressed for stop itself can be adjusted. It is only active if PROcoder is installed.
2.5 seconds to exit the second level menu. Service Light: This parameter defines the service light control
(See section 3.2).
Make sure that there are no two or more photocells pairs B-C OPENING
with the same address.
ENGLISH
D CLOSING
Fig. 2
/ OPEN PULSE
Table 5 shows the programming operations of the dip-switch inside
the transmitter and of the BUS Photocells receiver.
6. Give an OPEN impulse, leaves will move and the BUS 8. MEMORY STORING THE RADIO CODE
learning procedure is over.
The control board has an integrated 2-channel decoding system.
The board has memory stored the BUS accessories. Follow the
This system makes it possible to memory-store both total opening
instructions in the table below to check if the BUS connection is
(OPEN A) and partial opening OPEN B) of the automated system
correct.
- this is made possible by an additional receiver module (fig.3 ref.
Tab. 6 - Description of BUS LED
) and radio controls on the same frequency.
Normal operation (LED ON even in the • Only one radio code can be used at a time.
Steady light
absence of photocells)
• To change over from one code to another, you must
At least one input engaged: photocell
Slow flashing lamp delete the existing one (see paragraph on deletion),
engaged or not aligned, Open A or Open
(flash every 0.5 sec) and repeat the memory-storage procedure.
B or Stop input engaged
Light OFF
BUS line short circuited
ENGLISH
(flash every 2.5 sec)
If you have detected a BUS connection
error, repeat the acquisition procedure.
Fast flashing lamp If the error is repeated, make sure that
(flash every 0.2 sec) there is not more than one accessory
with the same address in the system
(also see the accessories instructions)
storage executed.
• Quickly press twice the push-button of the memory stored
radio control.
The automated system performs one opening operation.
Make sure that the automated system is free of any
obstacle created by persons or things.
Other radio controls can be remotely stored only with the 433 RC
Fig. 5
(Bravo - Echo) radio controls, i.e. without using the LOGIC-SPEED-
SETUP push-buttons, but using a previously stored radio control. 3. To correctly fasten and connect the kit to the control unit,
1. Get a radio control already stored on one of the 2 channels consult the instructions enclosed with the battery kit.
(OPEN A or OPEN B ).
2. Press and hold down push-buttons P1 and P2 simultaneously 10. AUTOMATED SYSTEM TEST
until both the LEDs flash slowly for 5 sec.
3. Within 5 sec. press the push-button of the radio control When you have finished programming, check if the system is
that had been memory stored to enable learning on the operating correctly. In particular, check if the safety devices are
selected channel. operating correctly.
4. The LED on the board relating to the channel being learned
flashes for 5 sec., within which time the code of another radio
control must be transmitted.
5. The LED lights up on steady beam for 2 seconds, indicating
memory storage executed, and then resumes flashing for
5 sec., during which other radio controls can be memory
stored, and then goes OFF.
8.3. Radio controls deletion procedure
To delete ALL the input radio control codes, press push-button
LOGIC (SW3) or SPEED (SW2) and, while holding it down, also
press push-button SETUP (SW1) for 10 sec.
1. The LED relating to the pressed push-button flashes for the
first 5 sec, and then flashes more quickly for the next 5 sec.
2. Both LEDs light up on steady beam for 2 sec and then go
OFF (deletion completed).
3. Release both push-buttons.
This operation is NOT reversible. All codes of radio con-
trols stored as OPEN A and OPEN B will be deleted.
ENGLISH
OPEN IN PAUSE time of released stops operation no effect time (CLOSE time (CLOSE
time
leaf disabled) disabled)
stops and opens
reopens leaves reopens leaves reverses at
CLOSING stops operation no effect at release (saves
immediately immediately opening
CLOSE)
no effect (OPEN/ no effect (OPEN no effect (CLOSE no effect (OPEN/
BLOCKED closes leaves closes leaves
CLOSE disabled) disabled) disabled) CLOSE disabled)
Tab. 8
LOGIC “E” PULSES
AUTOMATED SY-
OPEN A OPEN B STOP FSW OP FSW CL FSW CL/OP
STEM STATUS
opens released no effect (OPEN no effect (OPEN no effect (OPEN
CLOSED opens the leaves no effect
leaf disabled) disabled) disabled)
stops and opens
immediately rever- at release (OPEN
OPENING stops operation stops operation stops operation no effect
ses at closure stops - saves
CLOSE)
rerecloses leaves rerecloses leaves no effect (OPEN/ no effect (CLOSE no effect (OPEN/
OPEN no effect
immediately immediately CLOSE disabled) disabled) CLOSE disabled)
stops and opens
reopens leaves reopens leaves reverses at at release (OPEN
CLOSING stops operation no effect
immediately immediately opening stops - saves
CLOSE)
no effect (OPEN
no effect (OPEN/ no effect (OPEN no effect (CLOSE
BLOCKED closes leaves closes leaves stops - saves
CLOSE disabled) disabled) disabled)
CLOSE)
Tab. 9
LOGIC “AP” PULSES
AUTOMATED SY-
OPEN A OPEN B STOP FSW OP FSW CL FSW CL/OP
STEM STATUS
opens released
opens and closes no effect (OPEN no effect (OPEN no effect (OPEN
CLOSED leaf and closes no effect
after pause time disabled) disabled) disabled)
after pause time
stops and opens
reverses at closu- at release (OPEN
OPENING stops operation stops operation stops operation no effect
re (saves OPEN) stops - saves
CLOSE)
recharges pause recharges pause
OPEN IN PAUSE stops operation stops operation stops operation no effect time (CLOSE time (CLOSE
disabled) disabled)
stops and opens
reopens leaves reopens leaves reverses at at release (OPEN
CLOSING stops operation no effect
immediately immediately opening stops - saves
CLOSE)
no effect (OPEN/ no effect (OPEN no effect (CLOSE no effect (OPEN/
BLOCKED closes leaves closes leaves
CLOSE disabled) disabled) disabled) CLOSE disabled)
Page 22 BRAIN 15
Tab. 10
LOGIC “EP” PULSES
AUTOMATED SY-
OPEN A OPEN B STOP FSW OP FSW CL FSW CL/OP
STEM STATUS
opens released no effect (OPEN no effect (OPEN no effect (OPEN
CLOSED opens the leaves no effect
leaf disabled) disabled) disabled)
stops and opens
immediately rever- at release (OPEN
OPENING stops operation stops operation stops operation no effect
ses at closure stops - saves
CLOSE)
recloses leaves recloses leaves no effect (OPEN/ no effect (CLOSE no effect (OPEN/
OPEN no effect
immediately immediately CLOSE disabled) disabled) CLOSE disabled)
stops and opens
ENGLISH
Tab. 11
LOGIC “A1” PULSES
AUTOMATED SY-
OPEN A OPEN B STOP FSW OP FSW CL FSW CL/OP
STEM STATUS
opens released
opens and closes no effect (OPEN no effect (OPEN no effect (OPEN
CLOSED leaf and closes no effect
after pause time disabled) disabled) disabled)
after pause time
continues to open stops and opens
OPENING no effect no effect stops operation reverses and recloses at release (saves
after 5 s CLOSE)
locks and closes recharges pause
restores pause restores pause
OPEN IN PAUSE stops operation no effect on disengagement time (CLOSE
time time
after 5 s disabled)
stops and opens
reopens leaves reopens leaves reverses at
CLOSING stops operation no effect at release (saves
immediately immediately opening
CLOSE)
no effect (OPEN/ no effect (OPEN no effect (CLOSE no effect (OPEN/
BLOCKED closes leaves closes leaves
CLOSE disabled) disabled) disabled) CLOSE disabled)
Tab. 12
LOGIC “B” PULSES
AUTOMATED SY-
OPEN A OPEN B STOP FSW OP FSW CL FSW CL/OP
STEM STATUS
no effect (OPEN no effect (OPEN no effect (OPEN
CLOSED opens the leaves no effect no effect
disabled) disabled) disabled)
OPENING no effect locks operation stops operation locks operation no effect locks operation
no effect (OPEN/ no effect (CLOSE no effect (OPEN/
OPEN no effect closes leaves no effect
CLOSE disabled) disabled) CLOSE disabled)
CLOSING opens the leaves no effect stops operation no effect locks operation locks operation
no effect (OPEN/ no effect (OPEN no effect (CLOSE no effect (OPEN/
BLOCKED opens the leaves closes leaves
CLOSE disabled) disabled) disabled) CLOSE disabled)
BRAIN 15 Page 23
If the cycle began with OPEN-B (released leaf), both leaves are activated at opening
ENGLISH