Sei sulla pagina 1di 1

8 7 6 5 4 3 2 1

INVERTER Sungrow-200kW 3C X 1.5 SQ MM Cu Cable


TYPE:OUTDOOR 1500Vdc & 800Vac Aux. Supply Cable
Aux Supply SCADA SYSTEM

=1 =2 =3 =4 =5 =6 =7 SCADA CABLE SCHEDULE


19C/ 2CX1.5 SQ MM Cu Cable
~ ~ ~ ~ ~ ~ ~ TERMINAL BLOCK
TB- 1 & 2
TB-3 & 4
COMM. TYPE
RS-485
RS-485
TB-5 & 6 RS-485
F
TB-7 & 8 RS-485 RS 485 Cable
MODULE TB-9 & 10 RS-485
TB-11 & 12 RS-485
TEMPERATURE TB-13 & 14 RS-485
SENSOR TB-15 & 16 RS-485
Power Cable
TB-17 & 18 AI (4-20 mA)

250A, 3P MCCB

250A, 3P MCCB

250A, 3P MCCB

250A, 3P MCCB

250A, 3P MCCB

250A, 3P MCCB

250A, 3P MCCB
ACDB TB-19 & 20 AI (4-20 mA)
TB-21 & 22 AI (4-20 mA)
SMP3 SMART TB-23 & 24 AI (4-20 mA)
TB-25 DI
PYRANOMETER TB-26 DI
4 to 20 MA TB-27
TB-28
DI
DI
TB-29 DI
TB-30 DI
TB-31 DI
RYB TB-32 DI
TB-33 DI
METERING CT MCB TB-34 DI
MFM
1600 /5A TB-35 DI
TB-36 DI
TB-37 DI E
1600A, 800V TB-38 DI
ACB, 50 kA TB-39 DI
TB-40 DI
TB-41 DI
MCB 3-Ø, 40kA TB-42 DI
SPD,type 2 TB-43 DI
TB-44 DI
TB-45 DI
TB-46 DI
TB-47 DI
TB-48 DI
TB-49 DI
TB-50 DI
TRANSFORMER TB-51 DI
1600 kVA, 0.800kV/6.6kV, TB-52
TB-53
DI
DI
TB-54 DI
TB-55 DI
TB-56 DI
TB-57 DI
TB-58 DI
HT PANEL & TERMINAL DETAILS TB-59 DI
TB-60 DI D
X-4 TB-61 DI
133 U5C
TB-62 DI
BKR IN TEST SIGNAL TO SCADA U6C
134 TB-63 DI
135 U7C
BKR IN SERVICE SIGNAL TO SCADA U8C TB-64 DI
136
K5 TB-65 DI
BKR IN SERVICE POSITION SIGNAL 137
TO RELAY 138
K5A TB-66 DI
TB-67 DI
TB-68 DI
X-8 TB-69 DI
U1B TB-70 DI
LOCAL SIGNAL 1
U2B TB-71 DI
TO SCADA 2
U3B TB-72 DI
REMOTE SIGNAL 3
U4B TB-73 DI
TO SCADA 4
U5B TB-74 DI
SPRING CHARGE 5
U6B TB-75 DI
SIGNAL TO SCADA 6
U7B TB-76 DI
EMERGENCY TRIP 7
U8B TB-77 DI
OPERATED SIGNAL TO SCADA 8
U9B TB-78 DI
BUCHHOLZ TRIP 9
U10B TB-79 DI
SIGNAL TO SCADA 10
U11B TB-80 DI
BUCHHOLZ ALARM 11
U12B TB-81 DO
SIGNAL TO SCADA 12
U13B TB-82 DO
OIL TEMP. HIGH TRIP 13 C
U14B TB-83 DO
SIGNAL TO SCADA 14
U15B TB-84 DO
OIL TEMP. HIGH ALARM 15
U16B TB-85 DO
SIGNAL TO SCADA 16
U17B TB-86 DO
WDG. TEMP. HIGH TRIP 17
U18B TB-87 DO
SIGNAL TO SCADA 18
U19B TB-88 DO
WDG. TEMP. HIGH ALARM 19
U20B TB-89 DO
SIGNAL TO SCADA 20
U21B TB-90 DO
PRV TRIP 21
U22B TB-91 DO
SIGNAL TO SCADA 22
TB-92 DO
TB-93 DO
X-9 TB-94 DO
U1A TB-95 DO
CLOSING SIGNAL 1
U2A TB-96 DO
FROM SCADA 2
U3A TB-97 DO
TRIPPING SIGNAL 3
U4A TB-98 DO
FROM SCADA 4
TB-99 DO
TB-100 DO
X-1
J1
110V DC SUPPLY 201
J2
(FROM POWERPACK) 202
H1
230V AC SUPPLY 203
H2
Aux Supply
(CONTROL TRANSFORMER) 204 B
H3A
230V AC SUPPLY 205
H4A
(FOR POWERPACK) 206
207
208
SPARE TERMINALS
209
210

X-12
K5
DOWNSTREAM 1
BREAKER OFF STATUS K5E
2
K5
3
CLOSE INTERLOCK K5F
4
LBB PICKUP SIGNAL K5
5 00 30.06.2022 FIRST ISSUE SURESH DNV NILESH
FROM TSL K5G
6
PROTECTION TRIP K5
7 REV. DATE DESCRIPTION DRAWN CHKD. APPR.
OPERATED FROM TSL K5G
8
K5
VCB OFF & IN TEST
POSITION SIGNAL FROM TSL
9
K5
TO CUSTOMER PANEL @6.6kV
10
K5
OWNER TYPICAL SCADA SCHEME SLD FOR
VCB NOT ON & IN 11
SERVICE POSITION FROM TSL K5G
12
K5 TATA STEELS
CLOSE CET INSERTED 13
SIGNAL FROM TSL K5G
14
CET NOT INSERTED 15
K5 KALINGANAGAR, ODISHA A
SIGNAL FROM TSL K5G
16
K5
17 CONTRACTOR
TRIP INTERLOCK
18
K5H TATA POWER SOLAR SYSTEMS LTD.
PLOT-78, ELECTRONIC CITY PHASE-1
BENGALURU-560100

TPS DWG NO:TPS-B21-066-EL-107A TSL DWG NO: EDW-24-02-17-08-008-001

SCALE:- NTS SHEET. NO: 1 OF 1 REV. NO. 00 SHEET SIZE : A0


8 7 6 5 4 3 2 1 A0 (841X1189mm)