Sei sulla pagina 1di 2

COOLING LOAD ESTIMATOR - Ruang Dalaman Dewan

Temperature DB (oC) WB (oC) Hum Ratio


Outdoor temp to 33 28.3 0.02264 Room area 974 m2 è Imtiaz - Blok Dewan Serbaguna
Room temp ti 23 17 0.00969 Room Height 6.0 m
Daily Range DR 11

SENSIBLE COOLING LOAD


Conduction (A) Solar (B) Total Cooling (A) + (B)
Area (m2) U (W/m2.oC) CLTD Load-C (W) SC SGHF CLF Load-S (W) Load (W) Load (Btu/hr)
Windows
North 8.5 è 0.00 347 0 0.00 0.00
NE 8.5 è 0.00 637 0 0.00 0.00
East 8.5 è 0.00 618 0 0.00 0.00
SE 44.4 6.3 8.5 è 2,377.62 0.88 230 0.25 2246.64 4,624.26 15,778.62
South 8.5 è 0.00 120 0 0.00 0.00
SW 8.5 è 0.00 230 0 0.00 0.00
West 8.5 è 0.00 618 0 0.00 0.00
NW 44.4 6.3 8.5 è 2,377.62 0.88 637 0.52 12942.20928 15,319.83 52,273.40

Conduction Total Cooling


Area (m2) U (W/m2.oC) CLTD Load-C (W) Load (W) Load (Btu/hr)
Walls (Less glass)
North 12.6 è 0.00 0.00 0.00
NE 15.6 è 0.00 0.00 0.00
East 19.6 è 0.00 0.00 0.00
SE 177.6 1.49 20.6 è 5,451.25 5,451.25 18,600.44
South 22.6 è 0.00 0.00 0.00
SW 24.6 è 0.00 0.00 0.00
West 22.6 è 0.00 0.00 0.00
NW 177.6 1.49 15.6 è 4,128.13 4,128.13 14,085.77

Conduction Total Cooling


Area (m2) U (W/m2.oC) CLTD Load-C (W) Load (W) Load (Btu/hr)
Roof
w/o ceiling 33.5 è 0.00 0.00 0.00
wth ceiling 974 0.761 29.5 è 21,865.81 21,865.81 74,609.22

Conduction Total Cooling


Area (m2) 2 o
U (W/m . C) Δt Load-C (W) Load (W) Load (Btu/hr)
Partition
Partition 324 1.695 10 è 5,491.80 5,491.80 18,738.79
Floors 974 2.353 10 è 22,918.22 22,918.22 78,200.18

Total Cooling
Numbers SHG CLF Load (W) Load (W) Load (Btu/hr)
Internal sources
People 800 75 1 è 60,000.00 60,000.00 204,728.40

Total Cooling
Area (m2) Density (W/m )
2 CLF Factor Load (W) Load (W) Load (Btu/hr)
Internal sources
Light 974 18 1 1.2 21,038.40 21,038.40 71,785.97
Power 50 1 1 0.00 0.00 0.00

Total Cooling
No of people Rate (Lps/p) Vent (L/s) Δt Load (W) Load (W) Load (Btu/hr)
Ventilation
People vent 800 1.2 960 10 11,808.00 11,808.00 40,290.55
Infilteration (base on ACH = 0.3) 487 10 5,984.90 5,984.90 20,421.31

GRAND TOTAL SENSIBLE COOLING LOAD 178,630.61 609,512.65

LATENT COOLING LOAD Total Cooling


Numbers SHG CLF Load (W) Load (W) Load (Btu/hr)
Internal sources
People 800 55 1 è 44,000.00 44,000.00 150,134.16

Total Cooling
No of people Rate (Lps/p) Vent (L/s) Δw Load (W) Load (W) Load (Btu/hr)
Ventilation
People vent 800 1.2 960 0.01295 37,420.32 37,420.32 127,683.37
Infilteration (base on ACH = 0.3) 487 0.01295 18,966.53 18,966.53 64,716.47

GRAND TOTAL LATENT COOLING LOAD 100,386.85 342,534.00

SPACE COOLING LOAD (Btu/hr) 952,046.65


Engineering check (Btuh/sq.ft) 90.84
Sensible Heat Ratio (SHR) 0.64
Supply air (Cfm) 20,260.72
Engineering check (Cfm/ton) 255.37
Supply Air Flow = Sensible Heat Gain Notes:
1210 (Room Db - Supply Db) Supply air temperature = T air leaving coil

= 178,630.61 Nos of row 4


1210 (23 - 7.6) BPF (By Pass Factor) 0.10

= 9.57 m3/s Troom 23 Deg C


= 20,261 Cfm Tapparatus dew point,room 5.89 Deg C
Tair leaving coil 7.6 Deg C
% Outside air = Ventilation
Supply air

= 3,063
20,261
= 15.12
say 15%

Mixture air = Outside air x % OA


Room air x (100-%OA)

= 33 x 0.15 = 4.95
23 x 0.85 = 19.55
Mixture 24.5
o
say 24.5 C

Potrebbero piacerti anche