Sei sulla pagina 1di 2

COOLING LOAD ESTIMATOR - Ruang Solat Utama

Temperature DB (oC) WB (oC) Hum Ratio


Outdoor temp to 33 28.3 0.02264 Room area 570 m2 è Imtiaz - Blok Surau
Room temp ti 23 17 0.00969 Room Height 4.0 m
Daily Range DR 11

SENSIBLE COOLING LOAD


Conduction (A) Solar (B) Total Cooling (A) + (B)
Area (m2) U (W/m2.oC) CLTD Load-C (W) SC SGHF CLF Load-S (W) Load (W) Load (Btu/hr)
Windows
North 28.8 6.3 8.5 è 1,542.24 0.88 347 0.82 7211.38176 8,753.62 29,868.58
NE 8.5 è 0.00 637 0 0.00 0.00
East 8.5 è 0.00 618 0 0.00 0.00
SE 8.5 è 0.00 230 0 0.00 0.00
South 16.8 6.3 8.5 è 899.64 0.88 120 0.5 887.04 1,786.68 6,096.40
SW 8.5 è 0.00 230 0 0.00 0.00
West 16.8 6.3 8.5 è 899.64 0.88 618 0.72 6578.28864 7,477.93 25,515.74
NW 8.5 è 0.00 637 0 0.00 0.00

Conduction Total Cooling


Area (m2) U (W/m2.oC) CLTD Load-C (W) Load (W) Load (Btu/hr)
Walls (Less glass)
North 67.2 1.49 12.6 è 1,261.61 1,261.61 4,304.80
NE 15.6 è 0.00 0.00 0.00
East 19.6 è 0.00 0.00 0.00
SE 20.6 è 0.00 0.00 0.00
South 39.2 1.49 22.6 è 1,320.02 1,320.02 4,504.10
SW 24.6 è 0.00 0.00 0.00
West 39.2 1.49 22.6 è 1,320.02 1,320.02 4,504.10
NW 15.6 è 0.00 0.00 0.00

Conduction Total Cooling


Area (m2) U (W/m2.oC) CLTD Load-C (W) Load (W) Load (Btu/hr)
Roof
w/o ceiling 33.5 è 0.00 0.00 0.00
wth ceiling 570 0.761 29.5 è 12,796.22 12,796.22 43,662.48

Conduction Total Cooling


Area (m2) 2 o
U (W/m . C) Δt Load-C (W) Load (W) Load (Btu/hr)
Partition
Partition 100 1.695 10 è 1,695.00 1,695.00 5,783.58
Floors 570 2.353 10 è 13,412.10 13,412.10 45,763.96

Total Cooling
Numbers SHG CLF Load (W) Load (W) Load (Btu/hr)
Internal sources
People 500 75 1 è 37,500.00 37,500.00 127,955.25

Total Cooling
Area (m2) Density (W/m )
2 CLF Factor Load (W) Load (W) Load (Btu/hr)
Internal sources
Light 570 18 1 1.2 12,312.00 12,312.00 42,010.27
Power 50 1 1 0.00 0.00 0.00

Total Cooling
No of people Rate (Lps/p) Vent (L/s) Δt Load (W) Load (W) Load (Btu/hr)
Ventilation
People vent 500 1.3 650 10 7,995.00 7,995.00 27,280.06
Infilteration (base on ACH = 0.3) 190 10 2,334.97 2,334.97 7,967.25

GRAND TOTAL SENSIBLE COOLING LOAD 109,965.17 375,216.56

LATENT COOLING LOAD Total Cooling


Numbers SHG CLF Load (W) Load (W) Load (Btu/hr)
Internal sources
People 500 55 1 è 27,500.00 27,500.00 93,833.85

Total Cooling
No of people Rate (Lps/p) Vent (L/s) Δw Load (W) Load (W) Load (Btu/hr)
Ventilation
People vent 500 1.3 650 0.01295 25,336.68 25,336.68 86,452.28
Infilteration (base on ACH = 0.3) 190 0.01295 7,399.67 7,399.67 25,248.73

GRAND TOTAL LATENT COOLING LOAD 60,236.35 205,534.86

SPACE COOLING LOAD (Btu/hr) 580,751.42


Engineering check (Btuh/sq.ft) 94.69
Sensible Heat Ratio (SHR) 0.65
Supply air (Cfm) 13,155.94
Engineering check (Cfm/ton) 271.84
Supply Air Flow = Sensible Heat Gain Notes:
1210 (Room Db - Supply Db) Supply air temperature = T air leaving coil

= 109,965.17 Nos of row 4


1210 (23 - 8.4) BPF (By Pass Factor) 0.10

= 6.21 m3/s Troom 23 Deg C


= 13,156 Cfm Tapparatus dew point,room 6.78 Deg C
Tair leaving coil 8.4 Deg C
% Outside air = Ventilation
Supply air

= 1,778
13,156
= 13.52
say 14%

Mixture air = Outside air x % OA


Room air x (100-%OA)

= 33 x 0.14 = 4.62
23 x 0.86 = 19.78
Mixture 24.4
o
say 24.4 C