Sei sulla pagina 1di 48

Hitachi VRF Systems

SET FREE Σ
HEAT PUMP type NS SERIES
01
Hitachi VRF Systems
SET FREE Σ
HEAT PUMP type NS SERIES

Index 03 What can Hitachi VRF offer ? 22 Specifications / Dimensions


05 Line-up Overview Service Space
07 Features and Benefits Overview 36 Options
09 Design Flexibility 45 GlobalFootprint
13 Adaptability
16 High Efficiency

02
What can Hitachi VRF offer ?

What can Hitachi VRF offer ?

Greater Greater Easier


Comfort
Performance Design Flexibility Installation

An average of up to 39% energy Meet any local requirements Overall cost/time reduction Delivering precisely the
savings for some applications and constraints with a thanks to the lightweight correct amount of heating or
compared to conventional HVAC number of improvements and modular VRF systems. cooling to each zone leads
systems. of Outdoor unit (e.g. Larger to the comfortability, and
capacity range or Smaller also quiet operation and
footprints). defrosting are upgraded.

- Higher efficiency ratio - Larger capacity with smaller footprint - Overall lighter cabinet - Smart compressor control:
in APF, EER and COP - Better piping limit (16% lighter on average) keep indoor temperature more
- Lower CO2 emissions - Available for the lift transportation constant
- Extended external static pressure
- Lower power consumption - New package design to be craned - Lower noise operation
more easily - New defrosting technology

03
System Better
Maintenance Ease Aesthetics
Integration life-cycle costs

Delivering the ability of Easier maintenance thanks VRF can operate for 20- Let alone total line-up of
Integrating all management to Both the elimination of 30 years with whole easier Ceiling Concealed type of
systems, from individual any water treatment like maintenance, that leads to IDU, Ceiling Cassette type of
IDU to whole building, which pumps etc., and Design “Better Lifecycle Costs”! IDU are also designed not to
leads to both time saving change in unit. be the noise in space.
and cost saving.

- H-LINK solution - All PCB visible and easily accessible - More Efficiency Operation thanks to - Higher ESP ODU: the better visual
- Advanced individual and centralized - Easy access to compressors and valves DX system aesthetics compared to outdoor
control system - Maintenance Ease installment
- Smart refrigerant pump-down
- Easy BMS connection - Higher Control capacity thanks - Wide range of ceiling concealed type
to Advanced Individual/Centralized of IDU (Ducted type) will suit to your
control system interior requirement
- Ceiling cassette type IDU are also
designed to be clean and simple
without any disturbance to indoor
space.

04
Line-up Overview

Line-up Overview

NS SERIES

Base Unit

1675mm
1675mm

1675mm

765mm 765mm 765mm


950mm 1210mm 1600mm

8HP : RAS-8FSNS 190kg 14HP : RAS-14FSNS 268kg 20HP : RAS-20FSNS 350kg


10HP : RAS-10FSNS 190kg 16HP : RAS-16FSNS 310kg 22HP : RAS-22FSNS 364kg
12HP : RAS-12FSNS 210kg 18HP : RAS-18FSNS 311kg 24HP : RAS-24FSNS 365kg

Combiantion of Base Units


1675mm

1675mm

1675mm

765mm 2440mm 765mm 2830mm 765mm


2180mm
26HP : RAS-26FSNS 478kg 32HP : RAS-32 FSNS 579kg 38HP : RAS-38FSNS 633kg
28HP : RAS-28FSNS 520kg 34HP : RAS-34 FSNS 621kg 40HP : RAS-40FSNS 675kg
30HP : RAS-30FSNS 521kg 36HP : RAS-36 FSNS 622kg 42HP : RAS-42FSNS 676kg
1675mm

1675mm

3220mm 765mm 3670mm 765mm


44HP : RAS-44FSNS 728kg 50HP : RAS-50FSNS 890kg
46HP : RAS-46FSNS 729kg 52HP : RAS-52FSNS 932kg
48HP : RAS-48FSNS 730kg 54HP : RAS-54FSNS 933kg

Nomenclature
Unit Type
RAS: Outdoor Unit

System Capacity (HP)

RAS - 8 FS N S
Standard Type

Refrigerant Type
N: R410A
SET FREE System
FS: Heat Pump System (2 Pipes System)

05
Summary Table

Item Unit
Current Model
(FSXN1)
NS Series Features and
Capacity HP 8-54 8-54
Benefits Overview

Nominal Cooling Capacity KW 22.4 - 150.0 22.4-150.0 Design Flexibility 9


- COMPACT
Nominal Heating Capacity KW 25.0 - 165.0 25.0-165.0 - EASY TRANSPORTATION
- IMPROVED EXTERNAL STATIC PRESSURE
Maximum Connectable Indoor Unit Quantity 64 64 - PIPING CONNECTION WORKABILITY
- OPERATION TEMPERATURE RANGE
- IDU COMBINATIONS RANGE
Combination Capacity Ratio Between ODU and IDU % 50-130 50-130

Total Piping Length m (ft) 1000 (3281) 1000 (3281)


Adaptability 13
Maximum Piping Length Between ODU and IDU m (ft) 165 (541) 165 (541) - LOW NOISE OPERATION
- SILENT MODE
Maximum Equivalent Piping Length Between ODU and IDU m (ft) 190 (623) 190 (623) - IMPROVED STRENGTH
- DEFROSTING
- TO PREVENT FAILURE AND EMERGENCY
Maximum Piping Length Between 1st Branch and IDU m (ft) 90 (295) 90 (295)
OPERATION IN CASE OF FAILURE

Maximum Height Difference Between ODU and IDU *


- MAINTENANCE EASE
m (ft) 90 (295) 110 (361)
(when ODU is higher than IDU)

Maximum Height Difference Between ODU and IDU


(when IDU is higher than ODU)
m (ft) 40 (131) 40 (131) High Efficiency 16
- EFFICIENCY RATIO
Maximum Height Difference Between IDU and IDU m (ft) 30 (98) 30 (98) - 4 ADVANCED TECHNOLOGY
FAN
°C DB -5 to 43 -5 to 48 HEAT EXCHANGER
Cooling Operation Range **
(°F) (23 to 109) (23 to 118)
COMPRESSOR
°C WB -20 to 15 -20 to 15 COMPRESSOR CONTROL
Heating Operation Range **
(°F) (–4 to 59) (-4 to 59) - FOR BOTH YOU AND THE EARTH

* Please consult your distributor or dealer if the height different is over 50m.
** For more details, please consult your distributors or dealer, or, refer to technical manuals.

Benefit to

Educational Health Hotels Office Multi-tenant Historic Factory


Facilities Care Building residential Building Structures

06
Features and Benefits Overview

Features and Benefits Overview

FEATURES ADVANTAGES BENEFITS


Heat pump VRF systems • Precisely heats or cools multiple zones • Provides extreme system design flexibility

ODU Compact footprint • Requires less indoor space than conventional systems • Expands options for positioning outdoor units

• Provides flexibility to customize systems to each project’s • Simplifies design process


Modular components ODU
needs • Allows easy updates as space is reconfigured or expanded

Piping flexibility: with pipe runs up to 1000 • Suitable for short or long runs; accommodates nearly all
• Allows design freedom
meter projects

• Leads to both less piping length and lower installation cost


• Provides more options for outdoor units to be installed
Higher ESP: up to 80 Pa • Better efficiency
inside building by using ducts
• Better visual aesthetics compared to outdoor installment

Temperature Range • Operates from -20℃ to 48℃ • Allows design freedom


ARCHITECT
&
Silent Mode • Lower sound power/sound pressure level by Three steps • Meet the local limitations to sound level
SYSTEM
DESIGNER
• Ultimate in design flexibility • Reduces system costs
Non-ducted systems
• Reduces clearance between building floors • Ideal for historic renovations

• Accommodates retrofits by making use of existing duct


infrastructure
Ducted systems • Reduces overall construction costs
• Suits unique buildings that include ducted and non-ducted
areas

Connectable IDU/ODU capacity ratio Up • Up to 130% for Combination Capacity • Reduces system costs

VRF Selection Software • Intuitive functionality that simplifies and speeds designs • Allows confident selection and right-sizing of systems

H-LINK: Hitachi original communication


• No connection boundary among RAC, PAC and VRF • Allows design freedom
system to control multiple ODUs and IDUs
• Flexible wiring routes • Reduces system costs
from one control point.

FEATURES ADVANTAGES BENEFITS


• Ease of transportation leads to time/cost saving in
Compact footprint • Requires less indoor space than conventional systems
installation

• 16 % lighter cabinet on average compared to Current • Ease of transportation leads to time/cost saving in
Lighter cabinet
Model (FSX N1) installation

New Package of ODU • Easy to understand for craning • Reduces installation time and cost

• Outdoor unit piping can be connected from front, back or


underneath.
Installation simplicity • Reduces installation time and cost
• Small and light indoor units are easy to handle without
heavy equipment

Comprehensive training • Modules tailored to specific job functions • Enables professional, high-quality, timely installation
MECHANICAL
CONTRACTOR • Ensures correct components are delivered to job sites on • Enhances installation efficiency
& Consistent, reliable product delivery
time • Allows efficient labor scheduling
INSTALLER
• The upper panel (on the side of an electric box)
independently detached from the lower panel (on the
compressor chamber side)
• All PCB visible and easily accessible including 7-segment
• Speeds up time spent on maintenance, repair, and
Easy maintenance access display
troubleshooting
• More Space in lower section, easy access to compressors
and each valve
• Refrigerant evacuation: Enforced operation to open ODU
EVO/EVB, IDU EVI, and Hi/Low pressure Bi-pass SVB

Improved Strength • Rigidity ratio increased by 36.7% • Extends service life

• All product information is available on TS-Web


Technical Support Web • Reduce time to check up the necessary resources
http://www.jci-hitachi.com/support/technical

07
FEATURES ADVANTAGES BENEFITS
• In multiple-unit applications at partial load, outdoor • Optimizes efficiency
Rotational operation units operate alternately so that operating hours are • Extends service life
shared equally. • Increases reliability

• Allows one outdoor unit to be taken off-line for • Avoids system downtime
Backup operation function
maintenance while remaining units keep operating. • Protects occupant comfort

Efficiency optimized for part-


System • APF cooling among industry’s highest for VRF systems • Saves energy
load operation

• Heat pump systems deliver simultaneous heating and • Efficient heating/cooling


Optimum individualized comfort
cooling • Maximizes occupant comfort

• Extremely quiet (24.5-28 dB for indoor units)


Noise reduction preference • Let users choose from three settings for a “not to
• Ideal where outdoor units are positioned on side of
mode exceed” sound level
building or in locations where there are noise restrictions

• Among industry’s most efficient VRF systems:


DC inverter-driven scroll • Engineered to deliver the optimum efficiency at normal • Highest EER
compressor load conditions • Highest APF
• Highest COP in low and high heating modes
Compressor
Newly introduced compressor
• New cover can shield up the compressor sound • Lower sound pressure level
shield cover

Compressor modulation in 0.1 • Smoothly delivers only the exact amount of refrigerant • Allows fine control for optimum comfort
Hz increments needed for the load • Saves energy

• Users can select from a wide variety of power settings • Limits electric demand charges
Demand control from 100% to 60% and program “not to exceed” a given • Limits equipment wear and tear
power level • Reduces noise

BUILDING Smooth Drive: new compressor • Saves energy


• Controls compressor more efficiently
OWNER control operation system • Constant room temperature

• Allows programming to turn units on/off in rotation at • Saves energy


Load shedding
10- to 20-minute intervals • Limits demand charges
Outdoor Units
• Improved compressor cover
Low noise operation • More quiet operation
• Improved Fan + Fan-inlet structure

New Heat Exchanger (which • Greater heat exchange rate


• Heat exchange are increased by more than 10 % (12HP)
looks like Σ) • More efficient operation

• Longer fan blades increase airflow quantity by 25%, • Operates more efficiently
New long blade propeller fan
resulting in higher static pressure • Extends motor life

As high as 200Pa static pressure • Offers adjustable speeds to match the static pressure
• Flexibility to accommodate long or short ductwork runs
in ducted systems requirement

Indoor Units Widest range of line-up • meets any of your indoor requirement • keeps aesthetic

Optional motion and radiant • Sets back temperature when space is unoccupied,
• Saves energy
sensors increasing efficiency even further

• Controls multiple indoor and outdoor units from one


• Maximizes indoor comfort
control point
"H-LINK" Protocol • Saves energy
• Adds versatility to connect various central control
• Improves system management
options

Controls • Adjusts in 0.5/1 degree C increments • Auto-adjusts for daylight saving time
Temperature control
• Adjustable fan speeds • Provides options to satisfy multiple projects/buildings

• Enables control of VRF systems by way of a building • Optimizes comfort


H-LINK BACnet adapter for
management system (e.g. Metasys®) for almost • Saves energy
integration into BMS
unlimited control in a building of campus enterprise. • Unified interface for all HVAC systems

08
Design Flexibility

Design Flexibility

COMPACT

Combination Comparison of Outdoor Unit


HP 8 to 16 18 to 24 26 to 32 34 to 48 50 to 54

Current Model
(RAS-FSXN1)

Single Module Two Units Two Units Three Units Four Units

New
New Model
(RAS-FSNS)

Single Module Single Module Two Units Two Units Three Units

Expand single module capacity

More Compact Case (Compare to Current Model)

Space
11% Weight
New Model
Current
model
16%New Model
Current
model
reduction lighter
on average on average
1,210mm(47 5/8inch) 1,600mm(63inch)
1,920mm(75 3/5inch) 2,180mm(85 4/5inch)

18HP New Model


New Model
Current
Current
model
model
37% New Model
New New Model
Model
24HP
Current
Current
Current
model
model model
New Model
Current
model
27%
reduction New Model reduction
Current
model
1,210mm(47 5/8inch) 1,600mm(63inch)
1,210mm(47 5/8inch)
1,920mm(75 3/5inch)
1,920mm(75 3/5inch)
30%
1,210mm(47 5/8inch)
1,600mm(63inch)
2,180mm(85 4/5inch)
1,920mm(75
2,180mm(85 3/5inch)
4/5inch)
1,600mm(63inch)
2,180mm(85 4/5inch)
2,830mm(111 2/5inch)
32%
lighter 3,410mm(134 1/4inch)
lighter
Space:1.47m2 0.93m2 Space:1.67m2 1.22m2
Weight:445kg 311kg Weight:540kg 365kg

42HP Current 54HP Current


New Model Current Current New Model
New Model model New Model model
model model

2,830mm(111 2/5inch) 3,670mm(144 2/5inch)


2,830mm(111 2/5inch) 2,830mm(111 2/5inch)
3,410mm(134 1/4inch) 4,380mm(172 11/25inch)
3,410mm(134 1/4inch) 3,410mm(134 1/4inch)

Space:2.61m2 2.16m2 Space:3.35m2 2.81m2


Weight:850kg 676kg
17% 20% Weight:1080kg 933kg
16% 17%
reduction lighter reduction lighter

Current
New Model Current Current
New Model model
New Model
model model

3,670mm(144 2/5inch)
3,670mm(144 2/5inch) 3,670mm(144 2/5inch)
09 4,380mm(172 11/25inch)
4,380mm(172 11/25inch) 4,380mm(172 11/25inch)
EASY TRANSPORTATION

Smaller Lighter

Can be
transported in an Lift Crane

elevator by pallet 800


jack (up to 18HP)

New
New package
design to be
craned
more easily

1210

765

1350

IMPROVED EXTERNAL STATIC PRESSURE

High static pressure for outdoor units: can handle up to 80Pa

Current Model New Model


Wall Wall Wall Wall
60PA 80PA

Duct (Field
Duct (Field Supplied)
Supplied) Duct (Field Supplied)
Duct (Field Supplied)

offers more options for


the indoor installation
of the outdoor unit
• Less piping length
• Lower installation cost
• Visual aesthetics

Wall Wall Outdoor


Outdoor Unit Unit Wall Wall Outdoor Unit Unit
Outdoor

10
Design Flexibility

PIPING CONNECTION WORKABILITY

Improvement of restrictions on piping construction


Total piping length 1000m

Longest length actual (Equivalent) 165m (190m)

Longest length after first branch 90m

Higher ODU Standard 50m Optional 110m(*)


Level difference between ODU and IDU

Up to 110m*
Lower ODU 40m

Level difference between IDUs 30m

30m
* Please consult your distributor or dealer if the height difference is over 50m.

• Suitable for a high-


rise building or complex
facilities. 90m
• Leads to cost/time saving
for designers, with more
efficient design.
190m

Piping Direction
The pipes can be installed in three directions (front, rear or bottom side) from the bottom base.

For Piping from Front cover For Piping from Bottom base to Left, Right and Rear side

Cover gaps Control Wiring


with packings. Transition Wiring
(field-supplied)
Liquid Pipe
Power Source
Wiring
Gas Pipe
Piping Cover Control Wiring

Transition
Wiring
Power Source
Wiring
Cover gaps with
packings
(field-supplied)
Liquid Pipe Gas Pipe

For more
service space
in front.

image: front image: bottom

11
OPERATION TEMPERATURE RANGE

Expansion of scope of outdoor operating temperature


Improved!
Cooling Capacity Range °C DB (°F) -5 to 48 (23 to 118)

Heating Capacity Range °C WB (°F) -20 to 15 (-4 to 59)

-5°C
-5°C
-5°C
-5°C0 0 52°C
48°C
52°C
48°C -20°C
-20°C
-20°C
-20°C 00 15°C
15°C
15°C
15°C

Cooling
Coolingmode
mode Heating
Heatingmode
mode

NOTES:
1. Cooling operation at maximum 48oC DB (for standard type) and 52oC DB (for high efficiency type) should be available only if the outdoor air inlet temperature increase temporarily according to the installation condition.
2. If install the units to the place where exceed ambient temperature 48oC continuously, the combination ratio must be lower 130% and not to operate all of the indoor unit simultaneously.
3. The cooling capacity is deteriorated at high ambient temperature. Select the larger capacity outdoor unit than compatible building heat load.
4. The appropriate amount (100%) of refrigerant must be charged. Excessive charging of refrigerant is forbidden.
5. It must be avoided to install the units where affected by direct sunlight reflection and short circuit. There may be the possibility to activate protection control and alarm system if install the units to inappropriate place.
Also the life time of the products and parts must be considerably shortened.
6. Periodic maintenance (1/certain month) must be applied to the heat exchanger fin to avoid adhesion of dirt and clogging of sand to the outdoor unit heat exchanger.
7. Refer to the technical catalog for the detail.

IDU COMBINATIONS RANGE


Up to
Expansion of number of connectable indoor units
130%

38HP 64 units at maximum

Outdoor Unit Capacity (HP) 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38-54

Range of
combination capacity Standard Type (FSNS) : 50 to 130% (In case the combination ratio exceed 130%)

Maximum Connectable
13 16 19 23 26 26 33 36 40 43 47 50 53 56 59 64
IDU Quantity

Recommended Connectable
8 10 10 16 16 16 18 20 26 26 32 32 32 32 32 38
IDU Quantity

NOTES:
1. The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity
2. For the system under which all the indoor units are supposed to operate simultaneously, the total indoor unit capacity should be less than outdoor unit capacity. Otherwise, it may cause a decrease of operating performance and
operating limit in overload operation.
3. For the system under which all the indoor units are not supposed to operate simultaneously, the total indoor unit capacity is available up to 130% against the outdoor unit capacity.
4. When operating the outdoor unit in cold areas with temperatures of -10oC, or under the high heating load conditions, the total indoor unit capacity should be less than 100% against the outdoor unit capacity and the total piping
length should be less than 300m.
5. The air flow volume for indoor units of 0.8 and 1.0HP is set higher than that for indoor units of 1.5HP or more. Make sure to select appropriate indoor units when installing indoor units where cold draft may occur during heating
operation. If installing indoor units in such places, refer to the recommended number of connectable indoor units.
6. If combination capacity of indoor units exceed 100% of outdoor unit capacity, there might be the possibility of insufficient capacity of 130% (standard) and 150% (high efficiency) combination ratio. Refer to the technical.

12
Adaptability

Adaptability

LOW NOISE OPERATION

Thanks to below 2 Design Changes


Sound Power Level dB(A)
HP 8 10 12 14 16 20 22 24 -1.5 on Average !
The performance capability has
Current Model 81.5 82.5 84 85.4 85.5 86 87 87
increased, but the running Sound
New Model 80 82 82 85 85 86 84 86 Power Lebel (dB(A)) has decreased.

Compressor: Air blower:


The model is louder than conventional models due to the utilization The air blower has a new structure where it is placed above the
of a compact high-speed compressor, but it can reduce the level heat exchanger, meaning that the noise on the reverse side can be
of the sound pressure by up to 2dB(A) due to the utilization of new suppressed.
pressure covers.
New New
Cover Model

New Model

New Cover

SILENT MODE IMPROVED STRENGTH


The user can set a (three-step) nighttime low-noise schedule using Rigidity ratio (measured value) in the front and back direction :
the control unit remote controller. The user can set a schedule for increased by 36.7%
operation that takes the ambient environment into account.

Setting example
Day Night Day
Sound
Power
Level

Rigidity
improved !
86dB(A) 72.5dB(A) 86dB(A)
Nominal Step2 Nominal

86dB(A) Nominal 72.5dB(A) Step2 Improved!


dB(A)

18HP 42HP

Noise Reduction
Sound Power Level Sound Power Level
mode
Nominal 86 89
image
Step1 82.5 86
Step 2 77.5 81
Step3 72.5 76

*The range of performance and operation is limited, since the rotation frequency of
the compressor and ODU fan are forcibly decreased.

13
DEFROSTING
Prevention Improved!
for defrosting prevention, the model controls
frost and ice formation during heating operation by
running mid-temperature coolant (5°C-20°C) before
decreasing the pressure through a heat exchanger to frosting
control frost and ice formation on the lower part of the
cold
outdoor heat exchanger.
warm
defrosting

image hot

Better Sensing New


Model
Even while defrosting, Hitachi’s original sensing function
Sensing ability
has improved the system for detecting the frost amount.
increased

More efficient defrosting


image
In addition, the defrosting interval has been increased by
more than 200%, from 120 minutes to 250 minutes.
Undertakes defrosting more efficiently, rather than
unnecessary defrosting every two hours.

Current Model (image) New Model (image)

Unstable Temperature More constant Temperature


More efficient
and
Room
Temperature

Room
Temperature

comfortable
Heating Defrosting
on

Heating duration
more than 200%
longer

Time Time

on off on off on off on off on off on on off on off on


No cold air flow to Indoor
thanks to automatic IDU step

14
Adaptability

TO PREVENT FAILURE AND EMERGENCY OPERATION IN CASE OF FAILURE

To prevent failure Back up function


Standardize the running time of the individual outdoor units Full introduction of backup operation function. If one outdoor unit
and distribute the load by rotating the order of operation of the should fail, the model can continue to operate using the remaining
compressors of the outdoor units. outdoor units, thereby preventing total system failure.

off on on
Combined ODU

Rotation
on on off on off on

MAINTENANCE EASE
Totally
New!
Total Structure Change
Newly adopted window for
7-segment display:
New Structure: Adopting access door to the
In upper section, all PCB visible electrical box in the upper panel,
and easily accessible which leads to easy access to
7-segment display, PSW & DSW
and so on.

New Structure:
More Space in lower section, easy
access to compressors or valves
open

New DSW setting for


Refrigerant pump-down:
New Panel: Refrigerant evacuation: Enforced
The upper panel (on the side of an operation to open ODU EVO/EVB,
electric box) can be independently IDU EVI, and Hi/Low pressure Bi-
detached from the lower panel (on pass SVB
the compressor chamber side)

15
High Efficiency

EFFICIENCY RATIO

APF: Annual Performance Factor


APF
6.0 5.9 6.0
5.7 5.6
5.5 5.5 5.5
5.2 5.4 5.4 5.3 5.5 5.2
5.5
5.1 5.0 4.9 5.1
High Efficiency of
4.5 Overall lineup,
with APF improved by
3.0
7
% on average.

1.5

0.0
8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0

Old New
NOTES:
APF (As Reference in the Japanese seasonal performance benchmark for VRF)
APF is meant for cooling/heating capacity per 1kW of operating power consumption under certain conditions throughout the year.
APF = Accumulated cooling/heating loads (kWh) / Accumulated power input in cooling/heating (kWh)

NS Type

EER COP
7.00 7.00
7.00

6.00 6.00
6.00
5.01
5.01 4.91
4.91
5.00 5.00
5.00
4.35 4.27
4.27
4.00 3.93
4.00 4.00
4.00
3.49 3.49
3.49 3.44
3.44 3.44
3.44 3.52
3.52 3.58
3.58
3.26 3.32 3.07 3.18
3.18
3.00
3.00 2.94
2.94
3.00 3.00
3.00

2.00 2.00
2.00

1.00 1.00
1.00
8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0
22.0 24.0
24.0 8.0
8.0 10.0
10.0 12.0
12.0 14.0
14.0 16.0
16.0 18.0
18.0 20.0
20.0 22.0
22.0 24.0
24.0
HP HP
HP
NOTES:
1. The graphs below show the EER/COP of single units for Oceania.
2. The above values indicate the EER/COP per outdoor unit when it is combined with specified indoor units.
3. The specification of EER/COP of each country is different according to the regulation. Please contact to the Sales person for more information.
4. EER = Energy efficiency ratio = Cooling capacity or Heating capacity ÷ Power consumption of an air conditioner
5. COP = Coefficient of performance of an air conditioner = Output KW (cooling capacity) ÷ Input KW (power consumption)

WHAT'S IMPROVED?

1) FAN 2) Heat Exchanger 3) Compressor 4) Compressor Control

16
High Efficiency

IMPROVED FAN POWER

Expansion of Air Outlets


Current model New model

Twin-fan

1211mm 1210mm
Air outlets
are increased
Air volume area : 4403cm2 Air volume area : 6334cm2 by more than

40%
Improvement in bell-mouth
Current model New model

Narrower!
Less short
circuit

Smoother
air Flow

• Improvement of airflow volume by 23% (12HP)


• Energy consumption in the driving shaft has decreased by 20% on average

17
IMPROVED HEAT EXCHANGER

New shape
Current model (14,16HP) New model (14-24HP)

Split left-right
heat exchanger

New angle
Current model (14,16HP) New model (14-24HP)

Improved angle
of the curve

• The heat exchange area has been increased by more than 10% (12HP)
• Gre-ater heat exchange efficiency

18
High Efficiency

IMPROVED COMPRESSOR

New design compressor

Fixed Scroll

Pressure bypass valve The 13 colored parts are new!

Orbiting Scroll
Oldham’s Coupling
Main Bearing
Thrust Bearing

Frame Seal The performance increased


Crankshaft by 2.2-4.6%
APF
Counterweight 10.0
9.8
9.6
Motor Rotor 104.6%
9.4 103.3%
102.2%
9.2 100.0%
Motor Stator
9.0
8.8
8.6 8.98 9.17 9.39 9.27
Sub Bearing 8.4
8.2
8.0
DA65PHD-A1Y2 AA50PHD-A2Y2 DB65PHD-A2Y2 DC80PHD-A2Y2
Oil Pump
Current model New model

Greater capacity control Current model* New model*

The highly improved performance as well


as greater energy saving is achieved by 100% 100% 15Hz ~ 100Hz 100% 100% 11Hz ~ 110Hz
adopting newly developed high efficiency 85 Steps 990 Steps
(by 1Hz) (by 0.1Hz)
Inverter Compressor

Inverter Compressor
Inverter Compressor

Inverter Compressor

DC inverter compressor, with outstandingly


Control Capacity

Control Capacity
Control Capacity

Control Capacity

precise control technology of 0.1Hz


increments inverter frequency. Another
feature is the dramatically extended
InverterInverter InverterInverter
working range, menabled by expanding the
Compressor
Compressor Compressor
Compressor
compressor’s operating frequency band, 20% 20% 10% 10%
both upwards and downwards. Min. Min. Load Load Max. Max.
CoolingCooling
Min. Min. CoolingCooling
Load Load Max. Max.

*Example at 12HP

19
IMPROVED COMPRESSOR CONTROL

Smooth Drive
The model calculates the appropriate
amount of coolant supplied by the outdoor
units on the basis of information about
the required load from the individual
indoor units. The model employs smooth
operation control to control the number of Charge proper
revolutions of the inverter compressor. The amount of refrigerant
model supplies the appropriate amount of
coolant to the indoor units according to the
Calculation of proper Refrigerant flow
required load. The model increases energy- Piping
refrigerant amount
saving efficiency by operating smoothly
while controlling the switching on and off
of the compressor at low-load operation.

INV
compressor IDU IDU

Transmit Transmit
load load
information information

ODU

Transmission Wire

Current model New model

Room 30 Room 30
Temp Temp
(°C) (°C)
25 25
Unstable Temperature Constant Room Temperature
20 20

15 15 Around 40% less


energy consumption
10 10
Energy Consumption Loss
5 5 Smoother operation
Power Power
(kW) (kW)
0 0
60 Time(mm) 120 180 60 Time(mm) 120 180

Room Temperature(°C) Room Temperature(°C)


Hitachi
Power(kW) Power(kW) Original!

20
High Efficiency

FOR BOTH YOU AND THE EARTH

Significant reduction of CO2 emissions


CO2 EMISSIONS (FOR A 10HP EQUIVALENT SYSTEM)
By reducing power consumption, we
have significantly reduced CO2 emissions
and reduced the environmental impact. 15 years ago Model About 5,188 kg/year

(Reduction amount)

New Model About 2,523 kg/year

Reduction
About 2,665
kg/year
NOTE:
1. CO2 emissions are a trial calculation value based on JIS B 8616: 2015 (Tokyo office). The CO2 emissions coefficient is 0.534 kg-CO2/kWh.
2. Based on the end-use intensity of CO2 emissions (actual emission coefficient in FY 2014) specified by the Federation of Electric Power Companies.
3. As reference in Japanese domestic model

Significant reduction of power consumption


By increasing the performance of air COMPARISON OF SEASONAL POWER CONSUMPTION (FOR A SYSTEM EQUIVALENT TO 10HP)
blowers, heat exchangers and compressors
and improving compressor control, we 15 years ago Model 9,331 kWh/year
have significantly reduced annual power
consumption. (Comparison of power
consumption during a specific period)

New Model 4,537 kWh/year

Reduced by
about % 51
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000
(kwh/year)
NOTE:
1. Seasonal power consumption is a calculated value based on JIS B 8616: 2015 (Tokyo office), and it may vary depending on the area or usage conditions.
2. As reference in Japanese domestic model

21
Specifications /
Dimensions
Service space
NOTES:
The cooling and heating performances are the values when combined with our
specified indoor units.
Cooling Operation Heating Operation
Conditions Conditions
Indoor Air Inlet Temperature: Indoor Air Inlet Temperature:
1 27oC DB (80oF DB) / 19.0oC WB (66.2oF WB) 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: Outdoor Air Inlet Temperature:
35oC DB (95oF DB) 7oC DB (45oF DB) / 6oC WB (43oF WB)
Piping Length: 7.5 Meters
Piping Lift: 0 Meter
The sound pressure is based on the following conditions.
The above data is based on the cooling mode. In case of heating mode, the sound
2 pressure level increases by approximately 1~2 dB.
The above data was measured in an anechoic chamber so that reflected sound
should be taken into consideration in the field.
Except for the specified combination in the table (26~54HP), there is no other
3
combination of the base unit.
The width of outer dimension, it is the value when each distance between the base
4
outdoor units is specified to 20mm.
Specifications / Dimension

Model RAS-8FSNS RAS-10FSNS RAS-12FSNS RAS-14FSNS RAS-16FSNS RAS-18FSNS


Power Supply AC 3φ, 380-415V/50Hz, 400V/50Hz, 380V/60Hz, 220V/60Hz
Nominal Cooling Capacity kW 22.4 28.0 33.5 40.0 45.0 50.0
Nominal Heating Capacity kW 25.0 31.5 37.5 45.0 50.0 56.0
Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Dimensions H*W*D mm 1,675 × 950 × 765 1,675 × 1,210 × 765
Footprint m2 0.73 0.93
380-415V/50Hz,
400V/50Hz, kg 190 210 268 310 311
N/W 380V/60Hz
220V/60Hz kg 185 205 263 305 306
Weight
380-415V/50Hz,
400V/50Hz, kg 206 226 286 328 329
G/W 380V/60Hz
220V/60Hz kg 201 221 281 323 324
Type R410A
Refrigerant Gas
Charged Amount kg 5.0 7.2 8.9 9.9 10.7
Type FVC68D
Refrigeration Oil
Charged Amount L/Unit 6.0 6.9 7.9
Flow Control Micro-Computer Control Expansion Valve
Type Hermetic (Scroll)
AA50PHD
Model AA50PHD DC80PHD
Compressor AA50PHD
Number per unit 1 2
Motor Output (Pole) kW 3.3(6) 4.3(6) 5.4(6) 8.0(6) 4.5(6) × 2 5.0(6) × 2
Type Multi-Pass Cross-Finned Tube
Number of Coil per Unit 1 2
Maximum Operating Pressure MPa 4.15
Total Face Area m2 2.36 3.12
Material Copper Tube
Heat Exchanger
Diameter φmm 7.0
Tube
Rows 2 3
Number of tubes 116 174
Material Aluminium
Finn
Pitch mm 1.7
Type Propeller Fan
Number per unit 1 2
Condenser Fan
Outer Diameter mm 644 544 + 544
Nominal Air Flow Rate m3/min. 165 170 190 239 256
Type Drip-Proof Type Enclosure
Starting Method DC Motor
Outdoor Fan Motor Motor Output (Pole) kW 0.26(8) 0.28(8) 0.42(8) 0.33(8) × 2 0.39(8) × 2
Number per unit 1 2
Insulation Class E
Main Refrigerant Liquid Line mm (in.) φ9.52 (3/8) φ12.7 (1/2) φ15.88 (5/8)
Piping Gas line mm (in.) φ19.05 (3/4) φ22.2 (7/8) φ25.4 (1) φ28.58 (1-1/8)
Sound Power Level dB(A) 80 82 85 86
Sound Level
Sound Pressure Level dB(A) 58 60 59 63 65
Dimentions H*W*D mm 1,800 × 1,030 × 810 1,800 × 1,290 × 810
Package
Measurement m3 1.5 1.9

23
1 2 3 4 5 6 7 8
317T158469

A DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE A

( OUTDOOR UNIT ,MODELS: RAS-8FSNS,RAS-10FSNS and RAS-12FSNS


RAS-8FSNS, RAS-10FSNS AND RAS-12FSNS
Knockout Hole/Drain Hole
Power Source
Cable Outlet (Top View)
131 (※2)688 131 Mounting Position for
(Ø65 Knockout Hole) 720 115 Drain Boss (Optional)
(Anchor Bolt Hole Pitch) (Ø26×2)
18 Power Transition

(Anchor Bolt Hole Pitch)


Cable Outlet
(Ø33 Knockout Hole) Mounting Position for
Drain Cap (Optional)
(Ø26×2)
Control Cable Outlet
B (Ø33 Knockout Hole) B
729

M12 Anchor Bolt


Mooting Hole

80
65 80

382
(4-38×15 Long Hole]

245

87
205 ※N/A in This Unit
18

239 127
Refrigerant Piping Outlet (Gas,Liquid)
(Knockout Square Hole)

Service cover
267

C C
Refrigerant Piping and
Electrical Control Box Wiring Connection
Control Cable Outlet
Access Door
(Ø33 Knockout Hole)
TB Box
(Only 380-415V/50Hz Power Transition
380V/60Hz model) Cable Outlet
(Ø55 Knockout Hole)
1675

Gas Line Refrigerant


Piping Connection 305 65
1348

268 Liquid Line

Liquid Line Refrigerant


163 Gas Line

Piping Connection D
D
Refrigerant Piping and
225
Wiring Connection Hole
(Knockout Hole)
Hole for Suspention
32

100
253
248
269
14

60

331

92
95 92 576 92 117 Liquid Line Hole for Suspention
950 131 Gas Line 240 127
E E
765
NOTES: Power Source Refrigerant Not Used
1.Refer to "System Pipe Drawing"for diameters. Cable Outlet Piping Outlet
1 2 3 4 5 6 (Ø65 Knockout Hole) 7 (Gas,Liquid) 8
2.Drainage to come out during heating or defrost operation,and rain water,too. (Knockout
Square Hole)
317T158470
Choose a well drained place to install units or provide a ditch to drain.
A DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE A
RAS-14FSNS,
3.Do RAS-16FSNS
not install above the corridors.Drainage may AND
fall. RAS-18FSNS
If inevitable,provide the second drain pan to run drainage. ( OUTDOOR UNIT ,MODELS: RAS-14FSNS,RAS-16FSNS and RAS-18FSNS
4.Use a drain boss(optional)if drain setup for Outdoor Unit is necessary. DATE REVD. CHKD. APPD.
SYM.
Knockout Hole/Drain Hole REVISIONS
However,installation of the drain131 948
boss in regions where drainage may frozen 131 Power Source REMARKS TITLE PROJECTION SCALE
Cable Outlet (Top View)
DIMENSIONAL
152

is prohibited.Drainage in the pipes may frozen and (Anchor


cause cracks
BoltonHole
the pipes. 230 520 230 DRAWING Mounting Position
115 NTSfor
18

Pitch) (Ø65 Knockout Hole)


SHIMIZU DrainDWG.BossNO.(Optional)
SH. REV.REGD. F
(Anchor Bolt Hole Pitch)

F Follow the instructions on Installation Manual provided with drain boss. DWN. Y.KAGEYAMA 23- 01- 2017
Power Transition CHKD. Y.UCHINO 23- 01
- 2017 (Ø26×2)
Cable Outlet APPD. 23- 01
- 2017 317T158469
1 2 3 4 (Ø33 Knockout5 Hole) This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hongfor
Mounting Position Kong)Limi
ted CAD
Drain Cap (Optional)
(Ø26×2)
Control Cable Outlet
729

B
M12 Anchor Bolt B
(Ø33 Knockout Hole)
Mooting Hole
(4-38×15 Long Hole]
483
80
65 80
245
18

87

147 127
※N/A in This Unit
Refrigerant Piping Outlet
(Gas,Liquid)(Knockout Square Hole)
267

Service cover

C Electrical Control Box C

Access Door Refrigerant Piping and


Wiring Connection
TB Box
(Only 380-415V/50Hz, Control Cable Outlet
380/60Hz) (Ø33 Knockout Hole)
1675

Gas Line Refrigerant Power Transition


Piping Connection Cable Outlet
1348

(Ø55 Knockout Hole)


263 Liquid Line

Liquid Line Refrigerant


160 Gas Line

Piping Connection
212 65
Refrigerant Piping and D
D
Wiring Connection Hole
(Knockout Hole) 132
Hole for Suspention
32

178
60

239 92 92
14

100
253

112 Liquid Line


248

95 836
1210 130 Gas Line Hole for Suspention
93

765

E 147 127 E
NOTES:
1.Refer to "System Pipe Drawing"for diameters. Power Source Refrigerant Not Used
Cable Outlet Piping Outlet
2.Drainage to come out during heating or defrost operation,and rain water,too. (Ø65 Knockout Hole) (Gas,Liquid)
Choose a well drained place to install units or provide a ditch to drain. (Knockout
Square Hole)
3.Do not install above the corridors.Drainage may fall.
If inevitable,provide the second drain pan to run drainage.
4.Use a drain boss(optional)if drain setup for Outdoor Unit is necessary. DATE REVD. CHKD. APPD.
SYM.
However,installation of the drain boss in regions where drainage may frozen REVISIONS
REMARKS TITLE PROJECTION
is prohibited.Drainage in the pipes may frozen and cause cracks on the pipes. DIMENSIONAL
SCALE 24
DRAWING NTS
F Follow the instructions on Installation Manual provided with drain boss. DWN. Y.KAGEYAMA 23- 01
- 2017 SHIMIZU DWG. NO. SH. REV.REGD. F
CHKD. Y.UCHINO 23- 01
- 2017
Specifications / Dimension

Model RAS-20FSNS RAS-22FSNS RAS-24FSNS


Power Supply AC 3φ, 380-415V/50Hz, 400V/50Hz, 380V/60Hz, 220V/60Hz
Nominal Cooling Capacity kW 56.0 61.5 67.0
Nominal Heating Capacity kW 63.0 69.0 77.5
Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Dimensions H*W*D mm 1,675 × 1,600 × 765
Footprint m2 1.22
380-415V/50Hz,
400V/50Hz, kg 350 364 365
N/W 380V/60Hz
220V/60Hz kg 345 359 360
Weight
380-415V/50Hz,
400V/50Hz, kg 370 384 385
G/W 380V/60Hz
220V/60Hz kg 365 379 380
Type R410A
Refrigerant Gas
Charged Amount kg 11.3 11.6
Type FVC68D
Refrigeration Oil
Charged Amount L/Unit 8.4
Flow Control Micro-Computer Control Expansion Valve
Type Hermetic (Scroll)
AA50PHD DC80PHD
Model
Compressor AA50PHD DC80PHD
Number per unit 2
Motor Output (Pole) kW 5.5(6) × 2 6.7(6) × 2 7.1(6) × 2
Type Multi-Pass Cross-Finned Tube
Number of Coil per Unit 2
Maximum Operating Pressure MPa 4.15
Total Face Area m2 3.58
Material Copper Tube
Heat Exchanger
Diameter φmm 7.0
Tube
Rows 3
Number of tubes 174
Material Aluminium
Finn
Pitch mm 1.7
Type Propeller Fan
Number per unit 2
Condenser Fan
Outer Diameter mm 644 + 644
Nominal Air Flow Rate m3/min. 329 348
Type Drip-Proof Type Enclosure
Starting Method DC Motor
Outdoor Fan Motor Motor Output (Pole) kW 0.48(8) × 2 0.56(8) × 2
Number per unit 2
Insulation Class E
Main Refrigerant Liquid Line mm (in.) φ15.88 (5/8)
Piping Gas Line mm (in.) φ28.58 (1-1/8)
Sound Power Level dB(A) 86 84 86
Sound Level
Sound Pressure Level dB(A) 65 64 66
Dimentions H*W*D mm 1,800 × 1,680 × 810
Package
Measurement m3 2.4

25
Knockout Hole/Drain Hole
Mounting Position
669 131 (Top View) for Drain Cap
Power Source (Optional)
(Anchor Bolt Hole Pitch) 339 462 339 239
Cable Outlet
(Ø26×2)

18
(Ø65 Knockout Hole)
Power Transition Mounting Position

(Anchor Bolt Hole Pitch)


Cable Outlet for Drain Boss
(Ø33 Knockout Hole) (Optional)
(Ø26×2)
Control Cable Outlet B
(Ø33 Knockout Hole)

729

635
80
65 80
250
110 ※N/A in This Unit
18

110
g Hole 147 127 Refrigerant Piping Outlet
(Gas,Liquid)(Knockout Square Hole)

C
267

RAS-20FSNS, RAS-22FSNS AND RAS-24FSNS

Refrigerant Piping and


Wiring Connection
1 2 3 4 5 6 7 8
317T158471
DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE Control Cable Outlet
1675

(Ø33 Knockout Hole)


1348

( OUTDOOR UNIT ,MODEL: RAS-20FSNS,RAS-22FSNS and 24FSNS


259 Liquid Line

D
160 Gas Line

Power Transition
1 2 3 4 5 Hole/Drain Hole
Knockout 6 7
Cable Outlet
Mounting Position
131 669 669 131
317T158471
(Top View)
(Ø55 Knockout Hole) for Drain Cap
DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE
Power Source
A (Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) 339 462 339 239 (Optional)
Cable Outlet
( OUTDOOR UNIT ,MODEL: RAS-20FSNS,RAS-22FSNS and 24FSNS (Ø26×2)
18

(Ø65 Knockout Hole)


212 65
Power Transition Mounting Position
(Anchor Bolt Hole Pitch)

Knockout Hole/Drain Hole


32

Cable Outlet for Drain Boss M


131 669 669 131 (Ø33 Knockout Hole) 132 (Top View) (Optional) fo
92 Power Source (Ø26×239
2) (O
(Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) 339 462 339
Control Cable Outlet Cable Outlet
14

60

132 Liquid Line (Ø


18

(Ø33 Knockout Hole) (Ø65 Knockout Hole)


729

Power Source Cable Outlet

635
152 Gas Line (Ø65 Knockout Hole) Power Transition E M
(Anchor Bolt Hole Pitch)

80
Cable Outlet fo

100
765

65 80

253
(Ø33 Knockout Hole)

248
(O

250
Hole for Suspention (Ø
B Control Cable Outlet

93
(Ø33 Knockout Hole)
Refrigerant Piping Outlet ※N/A in This Unit
729

110
18

n,and rain water,too.

110
(Gas,Liquid) 147 127

635
80
itch to drain. M12 Anchor Bolt Mooting Hole (Knockout Square Hole) 147 127 Not Used
Refrigerant Piping Outlet

65 80
(6-38 ×15 Long Hole] (Gas,Liquid)(Knockout Square Hole)

250
DATE
REVD. CHKD. APPD.
SYM.
REVISIONS
is necessary. REMARKS TITLE 110 PROJECTION
SCALE ※N/A in This Unit
18

Service cover

110
DIMENSIONAL
rainage may frozen
267

Electrical DRAWING NTS


M12 Anchor Bolt Mooting Hole 147
SHIMIZU DWG. NO. 127
SH. REV.REGD. F Refrigerant Piping Outlet
cracks on the
Control pipes.
Box (6-38 ×15 Long Hole] DWN. Y.KAGEYAMA 23- 01
- 2017
CHKD. Y.UCHINO 23- 01
- 2017 (Gas,Liquid)(Knockout Square Hole)
ith drain boss. 317T158471
Access Door APPD. 23- 01
- 2017
3 4 5 This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong Kong)Limi
ted CAD
TB Box(Only C Service cover
380-415V/50Hz, Refrigerant Piping and
267

380/60Hz) Electrical
Control Box Wiring Connection
Gas Line
Refrigerant Access Door
Piping Connection Control Cable Outlet
1675

TB Box(Only (Ø33 Knockout Hole)


Liquid Line
1348

380-415V/50Hz, Refrigerant
259 Liquid Line

Refrigerant
160 Gas Line

Piping Connection 380/60Hz) Power Transition Wiring Con


Gas Line Cable Outlet
Refrigerant Refrigerant (Ø55 Knockout Hole)
Piping and wiring Piping Connection Control Cab
1675

Connection Hole (Ø33 Knock


(Knockout Hole) Liquid Line 0
1348

259 Liquid Line

D Refrigerant
160 Gas Line

Piping Connection 212 65


Power Tran
32

Cable Outle
Refrigerant
132 (Ø55 Knock
177 Piping and wiring
239 92
Connection Hole 92
0
14

60

(Knockout Hole) 1226 132 Liquid Line


95
Power Source Cable Outlet 212
Hole for
Suspention 1600 152 Gas Line (Ø65 Knockout Hole)
32

100

765 132
253
248

177
NOTES: 92 92
239 Hole for Suspention
14

60

1.Refer to "System Pipe Drawing"for diameters.


93

95 1226 132 Liquid Line


Refrigerant Piping Outlet
2.Drainage to come outHole
during Power Source Cable Outlet
forheating or defrost operation,and rain water,too. (Gas,Liquid) 147 127
E drainedSuspention 1600 152 Gas Line (Ø65 Knockout Hole)
Choose a well place to install units or provide a ditch to drain. (Knockout Square Hole) Not Used
100

765
253
248

3.Do not install above the corridors.Drainage may fall.


4 NOTES: 5 6 7 8 DATE REVD. CHK
If inevitable,provide the second drain pan to run drainage. Hole for Suspention SYM.
1.Refer to "System Pipe Drawing"for diameters.
93

REVISIONS
4.Use a drain
CONDITIONER,SET-FREE boss(optional)if drain setup for Outdoor Unit is necessary. REMARKS TITLE
Refrigerant Piping Outlet PROJECTION
SCALE
2.Drainage to come out during heating or defrost operation,and rain water,too. A (Gas,Liquid) DIMENSIONAL
However,installation of the drain boss in regions where drainage may frozen 147
DRAWING NTS
-20FSNS,RAS-22FSNS and 24FSNSin Choose
is prohibited.Drainage
a well drained place to install units or provide a ditch to drain.
the pipes may frozen and cause cracks on the pipes. DWN. Y.KAGEYAMA 23- 01
(Knockout Square Hole)
- 2017 SHIMIZU DWG. NO. SH.
3.Do not install above the corridors.Drainage may fall. CHKD. Y.UCHINO 23- 01
- 2017
Follow the instructions on Installation Manual provided with drain boss. 317T158471
If inevitable,provide the second drain pan to Knockout Hole/Drain Hole
run drainage. APPD. 23- 01
- 2017 SYM.
Mounting Position
This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong Kot
1 2
4.Use a drain boss(optional)if drain setup for Outdoor(Top
UnitView)
3is necessary. 4 for Drain Cap 5 REMARKS TITLE
Power Source (Optional) DIMENSIONAL
However,installation
Cable Outlet 339drainage may462
of the drain boss in regions where frozen 339 239
(Ø26×2) DRAWING
(Ø65isKnockout Hole)
prohibited.Drainage in the pipes may frozen and cause cracks on the pipes. DWN. Y.KAGEYAMA 23- 01
- 2017 SHIMI
F
Power Transition
Follow the instructions on Installation Manual provided with drain boss. Mounting Position CHKD. Y.UCHINO 23- 01
- 2017
(Anchor Bolt Hole Pitch)

Cable Outlet APPD. 23- 01


- 2017 317T158
for Drain Boss
1
(Ø33 Knockout Hole) 2 3 4
(Optional) 5 This drawing is under license by Johnson Controls-Hitachi Air Con
(Ø26×2)
Control Cable Outlet B
(Ø33 Knockout Hole)
635
80
65 80
250

110 ※N/A in This Unit


110

147 127 Refrigerant Piping Outlet


(Gas,Liquid)(Knockout Square Hole)

26
Refrigerant Piping and
Wiring Connection
Specifications / Dimension

Model RAS-26FSNS RAS-28FSNS RAS-30FSNS RAS-32FSNS RAS-34FSNS RAS-36FSNS


RAS-14FSNS RAS-16FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS
Combination of Base Unit
RAS-12FSNS RAS-12FSNS RAS-12FSNS RAS-14FSNS RAS-16FSNS RAS-18FSNS
Power Supply AC 3φ, 380-415V/50Hz, 400V/50Hz, 380V/60Hz, 220V/60Hz
Nominal Cooling Capacity kW 73.0 77.5 85.0 90.0 95.0 100.0
Nominal Heating Capacity kW 82.5 90.0 95.0 100.0 106.0 112.0
Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Dimensions H*W*D mm 1,675 × 2,180 × 765 1,675 × 2,440 × 765
Footprint m2 1.67 1.87
380-415V/50Hz,
400V/50Hz, kg 210 + 268 210 + 310 210 + 311 268 + 311 310 + 311 311 + 311
N/W 380V/60Hz
220V/60Hz kg 205 + 263 205 + 305 205 + 306 263 + 306 305 + 306 306 + 306
Weight
380-415V/50Hz,
400V/50Hz, kg 226 + 286 226 + 328 226 + 329 286 + 329 328 + 329 329 + 329
G/W 380V/60Hz
220V/60Hz kg 221 + 281 221 + 323 221 + 324 281 + 324 323 + 324 324 + 324
Type R410A
Refrigerant Gas
Charged Amount kg 16.1 17.1 17.9 19.6 20.6 21.4
Type FVC68D
Refrigeration Oil
Charged Amount L/Unit 12.9 13.9 14.8 15.8
Flow Control Micro-Computer Control Expansion Valve
Type Hermetic (Scroll)
DC80PHD DC80PHD DC80PHD DC80PHD AA50PHD AA50PHD
DC80PHD AA50PHD AA50PHD AA50PHD AA50PHD AA50PHD
Model
Compressor AA50PHD AA50PHD AA50PHD AA50PHD AA50PHD
AA50PHD AA50PHD
Quantity 2 3 4
Motor Output (Pole) kW 5.4 (6) × 1 + 8.0 (6) × 1 5.4 (6) × 1 + 4.5 (6) × 2 5.4 (6) × 1 + 5.0 (6) × 2 8.0 (6) × 1 + 5.0 (6) × 2 4.5 (6) × 2 + 5.0 (6) × 2 5.0 (6) × 2 + 5.0 (6) × 2
Type Multi-Pass Cross-Finned Tube
Number of Coil per Unit 3 4
Maximum Operating Pressure MPa 4.15
Total Face Area m2 2.36 + 3.12 3.12 + 3.12
Material Copper Tube
Heat Exchanger
Diameter φmm 7.0
Tube
Rows 3+3
Number of tubes 174 + 174
Material Aluminium
Finn
Pitch mm 1.7
Type Propeller Fan
Number per unit 3 4
Condenser Fan
Outer Diameter mm 644 + 544 + 544 544 + 544 + 544 + 544
Nominal Air Flow Rate m3/min. 190 + 239 190 + 256 239 + 256 256 + 256
Type Drip-Proof Type Enclosure
Starting Method DC Motor
Outdoor Fan Motor Motor Output (Pole) kW 0.42 (8) + 0.33 (8) × 2 0.42 (8) + 0.39 (8) × 2 0.33 (8) × 2 + 0.39 (8) × 2 0.39 (8) × 2 + 0.39 (8) × 2
Number per unit 3 4
Insulation Class E+E
Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4)
Piping Gas Line mm (in.) φ31.75 (1-1/4) φ38.1 (1-1/2)
Sound Power Level dB(A) 87 89
Sound Level
Sound Pressure Level dB(A) 64.5 66 67 68

27
to Indoor Unit

1 2 3 4 5 6 7 8
317T158472
A A

DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE


( OUTDOOR UNIT ,MODELS: RAS-26FSNS,RAS-28FSNS and RAS-30FSNS
RAS-26FSNS, RAS-28FSNS AND RAS-30FSNS )
MIN.
131 948 282 688 131
Combination of Base Unit Models
(Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) Outdoor Unit Model
Combination of Base Unit Models

18
OUTDOOR UNIT A OUTDOOR UNIT B
Outdoor Unit Model

(Anchor Bolt Hole Pitch)


B
RAS-26FSNS
OUTDOOR UNITRAS-14FSNS
A OUTDOOR RAS-12FSNS
UNIT B B

RAS-28FSNS RAS-16FSNS RAS-12FSNS


RAS-26FSNS RAS-14FSNS
RAS-30FSNS RAS-18FSNS RAS-12FSNS
RAS-12FSNS

729
RAS-28FSNS RAS-16FSNS RAS-12FSNS

RAS-30FSNS Combination of RAS-18FSNS


Base Unit Models
Drawing NO.of
Dimension RAS-12FSNS

M12 Anchor Bolt Mooting Hole RAS-12FSNS 317T158469

18
(8-38 ×15 Long Hole]
RAS-14FSNS 317T158470
C C
OUTDOOR UNIT A OUTDOOR UNIT B RAS-16FSNS 317T158470
RAS-18FSNS 317T158470

NOTES:
1.Make sure that the outdoor unit A is placed
on the indoor unit side.
Arrange the outdoor units according to the
@@ C` aD
D 2.Check "Piping System" and "Dimensional Drawing" D
1675

for the piping connection kit and piping


connection size.
3.Check the "Dimensional Drawing" for the
Dimension of piping outlet and Cable outlet.
4.This drawing shows that there is 20mm clearance
between the base units.
For outdoor unit snowproof hood,clearance is
50mm or more.
TDs @ @ @ @@¦@ @ E
E
the mounting pitch dimension for anchor bolts.
1210 950
MIN.20
1 2 (2180)
3 4 765 5 6 7 8
317T158473
A A
to Indoor Unit SYM.
DATE REVD. CHKD. APPD.
DIMENSIONAL
Piping DRAWINGKit
Connection OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE REVISIONS
REMARKS TITLE PROJECTION SCALE
DIMENSIONAL
( OUTDOOR UNIT ,MODELS: RAS-32FSNS,RAS-34FSNS and RAS-36FSNS ) DRAWING NTS
DWN. Y.KAGEYAMA 23- 01
- 2017 SHIMIZU DWG. NO. SH. REV. REGD. F
F
RAS-32FSNS, RAS-34FSNS AND RAS-36FSNS CHKD. Y.UCHINO 23- 01
- 2017
317T158472
APPD. 23- 01
- 2017
1 2 3
MIN. 4 5 This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong Kong)Limi
Combination of Base Unit Models
ted
CAD
131 948 282 948 131 Outdoor Unit Model
OUTDOOR UNIT A OUTDOOR UNIT B
(Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) Combination of Base Unit Models
RAS-32FSNS RAS-18FSNS RAS-14FSNS
B Outdoor Unit Model B
18

OUTDOOR
RAS-34FSNS UNIT ARAS-18FSNS OUTDOORRAS-16FSNS
UNIT B
(Anchor Bolt Hole Pitch)

RAS-36FSNS RAS-18FSNS RAS-18FSNS


RAS-32FSNS RAS-18FSNS RAS-14FSNS

RAS-34FSNS RAS-18FSNS RAS-16FSNS


729

Combination of Drawing NO.of


Base Unit Models Dimension
RAS-36FSNS RAS-18FSNS RAS-18FSNS
RAS-14FSNS 317T158470
RAS-16FSNS 317T158470
C M12 Anchor Bolt Mooting Hole C
RAS-18FSNS 317T158470
18

(8-38 ×15 Long Hole]

OUTDOOR UNIT A OUTDOOR UNIT B


NOTES:
1.Make sure that the outdoor unit A is placed
on the indoor unit side.
Arrange the outdoor units according to the
@@ C` aD
D 2.Check "Piping System" and "Dimensional Drawing" D
for the piping connection kit and piping
connection size.
3.Check the "Dimensional Drawing" for the
1675

Dimension of piping outlet and Cable outlet.


4.This drawing shows that there is 20mm clearance
between the base units.
For outdoor unit snowproof hood,clearance is
50mm or more.
TDs @ @ @ @@¦@ @ E
E
the mounting pitch dimension for anchor bolts.

1210 1210
MIN.20
(2440) 765
SYM. DATE REVD. CHKD. APPD.
REVISIONS
REMARKS TITLE PROJECTION
SCALE
DIMENSIONAL
to Indoor Unit DRAWING NTS
Piping Connection Kit SHIMIZU DWG. NO. SH. REV.REGD. F
F DWN. Y.KAGEYAMA 23- 01
- 2017
CHKD. Y.UCHINO 23- 01
- 2017
APPD. 23- 01
- 2017 317T158473
1 2 3 4 5 This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong ted 28
Kong)Limi
CAD
Specifications / Dimension

Model RAS-38FSNS RAS-40FSNS RAS-42FSNS RAS-44FSNS RAS-46FSNS RAS-48FSNS


RAS-24FSNS RAS-22FSNS RAS-24FSNS RAS-22FSNS RAS-24FSNS RAS-24FSNS
Combination of Base Unit
RAS-14FSNS RAS-18FSNS RAS-18FSNS RAS-22FSNS RAS-22FSNS RAS-24FSNS
Power Supply AC 3φ, 380-415V/50Hz, 400V/50Hz, 380V/60Hz, 220V/60Hz
Nominal Cooling Capacity kW 106.0 112.0 118.0 122.0 128.0 136.0
Nominal Heating Capacity kW 118.0 125.0 132.0 140.0 145.0 150.0
Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Dimensions H*W*D mm 1,675 × 2,830 × 765 1,675 × 3,220 × 765
Footprint m2 2.16 2.46
380-415V/50Hz,
400V/50Hz, kg 268 + 365 311 + 364 311 + 365 364 + 364 364 + 365 365 + 365
N/W 380V/60Hz
220V/60Hz kg 263 + 360 306 + 359 306 + 360 359 + 359 359 + 360 360 + 360
Weight
380-415V/50Hz,
400V/50Hz, kg 286 + 385 329 + 384 329 + 385 384 + 384 384 + 385 385 + 385
G/W 380V/60Hz,
220V/60Hz kg 281 + 380 324 + 379 324 + 380 379 + 379 379 + 380 380 + 380
Type R410A
Refrigerant Gas
Charged Amount kg 20.5 22.0 22.3 22.6 22.9 23.2
Type FVC68D
Refrigeration Oil
Charged Amount L/Unit 15.3 16.3 16.8
Flow Control Micro-Computer Control Expansion Valve
Type Hermetic (Scroll)
DC80PHD AA50PHD AA50PHD DC80PHD DC80PHD DC80PHD
DC80PHD AA50PHD AA50PHD DC80PHD DC80PHD DC80PHD
Model
Compressor DC80PHD DC80PHD DC80PHD DC80PHD DC80PHD DC80PHD
DC80PHD DC80PHD DC80PHD DC80PHD DC80PHD
Quantity 3 4
Motor Output (Pole) kW 8.0 (6) × 1 + 7.1 (6) × 2 5.0 (6) × 2 + 6.7 (6) × 2 5.0 (6) × 2 + 7.1 (6) × 2 6.7 (6) × 2 + 6.7 (6) × 2 6.7 (6) × 2 + 7.1 (6) × 2 7.1 (6) × 2 + 7.1 (6) × 2
Type Multi-Pass Cross-Finned Tube
Number of Coil per Unit 4
Maximum Operating Pressure MPa 4.15
Total Face Area m2 3.12 + 3.58 3.58 + 3.58
Material Copper Tube
Heat Exchanger
Diameter φmm 7.0
Tube
Rows 3+3
Number of tubes 174 + 174
Material Aluminium
Finn
Pitch mm 1.7
Type Propeller Fan
Number per unit 4
Condenser Fan
Outer Diameter mm 544 + 544 + 644 + 644 644 + 644 + 644 + 644
Nominal Air Flow Rate m3/min. 239 + 348 256 + 329 256 + 348 329 + 329 329 + 348 348 + 348
Type Drip-Proof Type Enclosure
Starting Method DC Motor
Outdoor Fan Motor Motor Output (Pole) kW 0.33 (8) × 2 + 0.56 (8) × 2 0.39 (8) × 2 + 0.48 (8) × 2 0.39 (8) × 2 + 0.56 (8) × 2 0.48 (8) × 2 + 0.48 (8) × 2 0.48 (8) × 2 + 0.56 (8) × 2 0.56 (8) ×2 + 0.56 (8) ×2
Number per unit 4
Insulation Class E+E
Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4)
Piping Gas Line mm (in.) φ38.1 (1-1/2)

Sound Level Sound Power Level dB(A) 89 88 89 87 88 89


(2 Pipes) Sound Pressure Level dB(A) 68 67.5 68.5 67 68 69

29
1 2 3 4 5 6 7 8
317T158474
A A

DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE

( OUTDOOR UNIT ,MODELS: RAS-38FSNS,RAS-40FSNS and RAS-42FSNS )


RAS-38FSNS, RAS-40FSNS AND RAS-42FSNS
MIN.
131 669 669 282 948 131
Combination of Base Unit Models
(Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) Outdoor Unit Model Combination of Base Unit Models
OUTDOOR UNIT A OUTDOOR UNIT B
Outdoor Unit Model

18
B RAS-38FSNS
OUTDOOR RAS-24FSNS
UNIT A RAS-14FSNS
OUTDOOR UNIT B B

(Anchor Bolt Hole Pitch)


RAS-40FSNS RAS-22FSNS RAS-18FSNS
RAS-38FSNS RAS-42FSNS
RAS-24FSNS
RAS-24FSNS
RAS-14FSNS
RAS-18FSNS

RAS-40FSNS RAS-22FSNS RAS-18FSNS

729
Combination of
RAS-42FSNS Drawing NO.of
RAS-24FSNS RAS-18FSNS
Base Unit Models Dimension

RAS-14FSNS 317T158470
M12 Anchor Bolt Mooting Hole RAS-18FSNS 317T158470

18
(10-38 ×15 Long Hole]
C C
RAS-22FSNS 317T158471
OUTDOOR UNIT A OUTDOOR UNIT B RAS-24FSNS 317T158471

NOTES:
1.Make sure that the outdoor unit A is placed
on the indoor unit side.
Arrange the outdoor units according to the
@@ C` aD
D 2.Check "Piping System" and "Dimensional Drawing" D
for the piping connection kit and piping
1675

connection size.
3.Check the "Dimensional Drawing" for the
Dimension of piping outlet and Cable outlet.
4.This drawing shows that there is 20mm clearance
between the base units.
For outdoor unit snowproof hood,clearance is
50mm or more.
TDs @ @ @ @@¦@ @ E
E
the mounting pitch dimension for anchor bolts.

1600 1210
MIN.20
(2830) 765

1 2 3 4 5 6 7 8
SYM. DATE REVD. CHKD. APPD.
317T158475
A to Indoor Unit REVISIONS A
Piping Connection Kit REMARKS TITLE PROJECTION
SCALE
DIMENSIONAL
DRAWING NTS
F DIMENSIONAL DRAWING OF HITACHI AIR-TO-AIR HEAT PUMP AIR CONDITIONER,SET-FREE DWN. Y.KAGEYAMA 23- 01
- 2017 SHIMIZU DWG. NO. SH. REV.REGD. F
CHKD. Y.UCHINO 23- 01
- 2017
RAS-44FSNS, RAS-46FSNS AND RAS-48FSNS
( OUTDOOR UNIT ,MODELS: RAS-44FSNS,RAS-46FSNS and RAS-48FSNS APPD. -) 2017
23- 01 317T158474
1 2 3 4 5 This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong ted
Kong)Limi
CAD
MIN.
131 669 669 282 669 669 131
(Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) (Anchor Bolt Hole Pitch) Combination of Base
Combination Unit
of Base UnitModels
Models
Outdoor Unit Model
Outdoor Unit Model
OUTDOOR UNIT A OUTDOOR UNIT B
OUTDOOR UNIT A OUTDOOR UNIT B
18

B RAS-44FSNS RAS-22FSNS RAS-22FSNS B


RAS-44FSNS RAS-22FSNS RAS-22FSNS
(Anchor Bolt Hole Pitch)

RAS-46FSNS RAS-24FSNS RAS-22FSNS


RAS-48FSNS RAS-24FSNS RAS-24FSNS
RAS-46FSNS RAS-24FSNS RAS-22FSNS
729

RAS-48FSNS RAS-24FSNS RAS-24FSNS


Combination of Drawing NO.of
Base Unit Models Dimension

RAS-22FSNS 317T158471
M12 Anchor Bolt Mooting Hole
18

(12-38 ×15 Long Hole] RAS-24FSNS 317T158471


C C

OUTDOOR UNIT A OUTDOOR UNIT B

NOTES:
1.Make sure that the outdoor unit A is placed
on the indoor unit side.
Arrange the outdoor units according to the
@@ C` aD
D D
2.Check "Piping System" and "Dimensional Drawing"
for the piping connection kit and piping
1675

connection size.
3.Check the "Dimensional Drawing" for the
Dimension of piping outlet and Cable outlet.
4.This drawing shows that there is 20mm clearance
between the base units.
For outdoor unit snowproof hood,clearance is
50mm or more.
E TDs @ @ @ @@¦@ @ E
the mounting pitch dimension for anchor bolts.

1600 1600
MIN.20
(3220) 765

SYM. DATE REVD. CHKD. APPD.


to Indoor Unit REVISIONS
Piping Connection Kit REMARKS TITLE PROJECTION
SCALE
DIMENSIONAL
DRAWING NTS
F DWN. Y.KAGEYAMA 23- 01
- 2017 SHIMIZU DWG. NO. SH. REV.REGD. F
CHKD. Y.UCHINO 23- 01- 2017
317T158475
30
APPD. 23- 01
- 2017
1 2 3 4 5 This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(Hong
tedKong)Limi
CAD
Specifications / Dimension

Model RAS-50FSNS RAS-52FSNS RAS-54FSNS


RAS-18FSNS RAS-18FSNS RAS-18FSNS
Combination of Base Unit RAS-18FSNS RAS-18FSNS RAS-18FSNS
RAS-14FSNS RAS-16FSNS RAS-18FSNS
Power Supply AC 3φ, 380-415V/50Hz, 400V/50Hz, 380V/60Hz, 220V/60Hz
Nominal Cooling Capacity kW 140.0 145.0 150.0
Nominal Heating Capacity kW 155.0 160.0 165.0
Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Dimensions H*W*D mm 1,675 × 3,670 × 765
Footprint m2 2.81
380-415V/50Hz,
400V/50Hz, kg 268 + 311 + 311 310 + 311 + 311 311 + 311 + 311
N/W 380V/60Hz
220V/60Hz kg 263 + 306 + 306 305 + 306 + 306 306 + 306 + 306
Weight
380-415V/50Hz,
400V/50Hz, kg 286 + 329 + 329 328 + 329 + 329 329 + 329 + 329
G/W 380V/60Hz
220V/60Hz kg 281 + 324 + 324 323 + 324 + 324 324 + 324 + 324
Type R410A
Refrigerant Gas
Charged Amount kg 30.3 31.3 32.1
Type FVC68D
Refrigeration Oil
Charged Amount L/Unit 22.7 23.7
Flow Control Micro-Computer Control Expansion Valve
Type Hermetic (Scroll)
DC80PHD AA50PHD AA50PHD
AA50PHD AA50PHD AA50PHD
AA50PHD AA50PHD AA50PHD
Model
Compressor AA50PHD AA50PHD AA50PHD
AA50PHD AA50PHD AA50PHD
AA50PHD AA50PHD
Quantity 5 6
Motor Output (Pole) kW 8.0 (6) × 1 + 5.0 (6) × 2 + 5.0 (6) × 2 4.5 (6) × 2 + 5.0 (6) × 2 + 5.0 (6) × 2 5.0 (6) × 2 + 5.0 (6) × 2 + 5.0 (6) × 2
Type Multi-Pass Cross-Finned Tube
Number of Coil per Unit 6
Maximum Operating Pressure MPa 4.15
Total Face Area m2 3.12 + 3.12 + 3.12
Material Copper Tube
Heat Exchanger
Diameter φmm 7.0
Tube
Rows 3+3+3
Number of tubes 174 + 174 + 174
Material Aluminium
Finn
Pitch mm 1.7
Type Propeller Fan
Number per unit 6
Condenser Fan
Outer Diameter mm 544 + 544 + 544 + 544 + 544 + 544
Nominal Air Flow Rate m3/min. 239 + 256 × 2 256 × 3
Type Drip-Proof Type Enclosure
Starting Method DC Motor
Outdoor Fan Motor Motor Output (Pole) kW 0.33 (8) × 2 + 0.39 (8) × 2 + 0.39 (8) × 2 0.39 (8) × 2 + 0.39 (8) × 2 + 0.39 (8) × 2
Number per unit 6
Insulation Class E+E+E

Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4)


Piping Gas Line mm (in.) φ38.1 (1-1/2)
Sound Power Level dB(A) 90 91
Sound Level
Sound Pressure Level dB(A) 69 70

31
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8
317T158476 317T158476
A RAS-50FSNS,
A RAS-52FSNS AND RAS-54FSNS A

DIMENSIONAL
DIMENSIONAL DRAWING DRAWING
OF HITACHI OF HITACHI
AIR-TO-AIR AIR-TO-AIR
HEAT PUMP AIRHEAT PUMP AIR CONDITIONER,SET-FREE
CONDITIONER,SET-FREE

( ( OUTDOOR
OUTDOOR UNIT ,MODELS:UNIT ,MODELS: RAS-50FSNS,RAS-52FSNS
RAS-50FSNS,RAS-52FSNS and RAS-54FSNS
and RAS-54FSNS ) )
MIN. MIN. MIN. MIN.
131 131 948 948 282 282 948 948 282 282 948 948 131 131
(Anchor
(Anchor Bolt Bolt Hole Pitch)
Hole Pitch) (Anchor
(Anchor Bolt Bolt Hole Pitch)
Hole Pitch) (Anchor
(Anchor Bolt Bolt Hole Pitch)
Hole Pitch) Combination ofModels
Base Unit Models
Combination of Base Unit
Outdoor
Outdoor Unit Model Unit Model

18
18
OUTDOOR UNITOUTDOOR
A UNIT A
OUTDOOR UNITOUTDOOR
B UNIT B
OUTDOOR UNITOUTDOOR
C UNIT C

(Anchor Bolt Hole Pitch)


(Anchor Bolt Hole Pitch)
B B RAS-50FSNS RAS-50FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS RAS-14FSNS RAS-14FSNS
B
RAS-52FSNS RAS-52FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS RAS-16FSNS RAS-16FSNS
RAS-54FSNS RAS-54FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS

729
729
Combination of Combination of Drawing NO.of Drawing NO.of
Base Unit Models Dimension Dimension
Base Unit Models

M12 Anchor M12


Bolt Anchor
MootingBolt
HoleMooting Hole RAS-14FSNS RAS-14FSNS 317T158470 317T158470

18
18
(12-38 ×15 (12-38 ×15 Long Hole]
Long Hole]
RAS-16FSNS RAS-16FSNS 317T158470 317T158470
C C C
RAS-18FSNS RAS-18FSNS 317T158470 317T158470

OUTDOOR
OUTDOOR UNIT A UNIT A OUTDOOR
OUTDOOR UNIT B UNIT B OUTDOOR
OUTDOOR UNIT C UNIT C

NOTES: NOTES:
1.Make
1.Make sure that thesure thatunit
outdoor the Aoutdoor
is unit A is
placed on theplaced
indooron theside.
unit indoor unit side.
Arrangeunits
Arrange the outdoor the outdoor
according units according to the
to the
@@ @ @ C ` a b DC ` a b D
2.Check
2.Check "Piping "Piping
System" and System"
"Dimensionaland "Dimensional
D D D
Drawing" for Drawing"
the pipingfor the pipingkitconnection
connection and kit and
pipingsize.
piping connection connection size.
1675
1675

3.Check the "Dimensional


3.Check the "Dimensional Drawing" for Drawing"
the for the
Dimension ofDimension of piping
piping outlet and Cableoutlet and Cable outlet.
outlet.
4.This drawing4.This
showsdrawing shows
that there that there is 20mm
is 20mm
clearance
clearance between between
the base the base units.
units.
For snowproof
For outdoor unit outdoor unithood,clearance
snowproof hood,clearance
is 50mm or more.
is 50mm or more.
TDs @ TDs @ @ @@ @ @@ ¦ @ @@¦@ @
E E E
the mountingthe mounting
pitch dimension pitchfordimension
anchor for anchor
bolts. bolts.
1210 1210 1210 1210 1210 1210 6.The entire
6.The entire modular modular
length lengthbolt
and anchor and anchor bolt

MIN.20 MIN.20 MIN.20 MIN.20 positions arepositions


determinedareby determined by the clearances.
the clearances.
(3670) (3670) 765 765

DATE REVD. CHKD. APPD.


SYM. DATESYM. REVD. CHKD. APPD.
REVISIONSREVISIONS
to Indoor Unitto Indoor Unit Connection
Piping Piping Connection
Kit 1 Kit 1 Piping Connection
Piping Connection
Kit 2 Kit 2 REMARKS REMARKS TITLE TITLE PROJECTION PROJECTION
SCALE SCALE
DIMENSIONAL DIMENSIONAL
DRAWING DRAWING NTS NTS
F F DWN. Y.KAGEYAMA 23-DWN.
- Y.KAGEYAMA
01 2017 23- 01
- 2017 SHIMIZU DWG. SHIMIZU
NO. DWG. NO. REGD.
SH. REV. SH. FREV.REGD
CHKD.Y.UCHINO 23CHKD. - Y.UCHINO
- 01 2017 23- 01
- 2017
APPD. 23APPD.
- 01
- 2017 23- 01
- 2017 317T158476 317T158476
1 1 2 2 3 3 4 4 5 5 This drawing is This
underdrawing
licenseisbyunder
Johnsonlicense by Johnson Controls-Hitachi
Controls-Hitachi Air ConditioningAir ConditioningtedTechnology(Hong
Technology(Hong CAD ted Kong)Limi
Kong)Limi CAD

Combination of Base Unit Models


Outdoor Unit Model
OUTDOOR UNIT A OUTDOOR UNIT B OUTDOOR UNIT C

RAS-50FSNS RAS-18FSNS RAS-18FSNS RAS-14FSNS

RAS-52FSNS RAS-18FSNS RAS-18FSNS RAS-16FSNS

RAS-54FSNS RAS-18FSNS RAS-18FSNS RAS-18FSNS

32
Service Space

SERVICE SPACE
Make the service space when outdoor unit
is installed as follows.
If the service spaces for air inlet and outlet
are insufficient, it may cause a performance
degradation and some abnormalities due to
insufficient air intake.
Additionally, the service space is required (Unit: mm)

for facilitating the maintenance.

Min.

1500
- In the case of no walls on the front side and the rear side,
the service space is required as follows.

* Front Side: Min. 500mm


h2

Vent Hole
* Rear Side: Min. 300mm
* Right and Left Sides: Min. 10mm (In the case that the
field-supplied snow protection food or the air outlet duct
is amounted to the unit, the spaces of min. 50mm are
required.)

- If the wall on the front side is over 1,500mm high, the space

h1
Front Rear
of (500 + h2/2) mm for the front side is required.
Side Side
- If the wall on the rear side is over 500mm high, the space of
1500

(300 + h1/2) mm for the rear side is required.

- When the units are surrounded by walls on more than 2


sides, the space indicated in the figure above is required.

- For walls on more than 2 sides, secure the service space as

500
shown in the following figures.

- If the space between the unit and an obstacle above the unit
is less than 1,500mm or the space above the unit is closed,
set up the duct at the air outlet side in order to prevent
short circuit.

- When there are obstacles above the unit, the four (front,
rear, right and left) sides of the unit shall be open in
principle. 765

Min. 500 + h2/2 Min. 300 + h1/2

< Side View >

33
No limit for No limit for No limit for
side wall height. side wall height. side wall height.

Min. 300 Min. 300 Min. 300


(Rear Side Space) (Rear Side Space) (Rear Side Space)
*1)
Min. 10 Min. 200

Front Side Front Side Front Side Front Side Front Side
Min. 500 + h2/2
<Top View> Min. 400 Min. 400
<Top View>
<Top View>

1) Walls on 2 Sides
In case that the units are installed adjacent
• SINGLE INSTALLATION
to tall buildings and there are no walls on
No limit for No limit for No limit for
2 sides, the minimum rear side space must No limit for Noside
limitwall
for height. No limit for Noside
limitwall
for height. “ ” limit for
No Noside
limitwall
for hei
side wall height. side wall height. side wall height. side wall height. side wall height. side wall heigh
be 300mm.
Min. 300 Min. 300
Min. 300 (Rear
Min. Side
300 Space) This indicates
Min. 300 the (Rear
Min.Side
300 Space) M
No limit for No limit for No limit for
(Rear Side Space)
Min.
*1) (Rear Side Space) Min. wall direction
(Rear
200 height. of the
Side Space) (Rear Side Space) (Rear
side10
wall height. side side wall hei
*1) *1)
Min. 200 Min. 200
unit(Front Side) when
Min. 10 Min. 10
Min. 300 + h1/2 installing the units.
Front Side Min. 300 Front Side Front Side Min. 300 Fro
(Rear Side Space) (Rear Side Space)
*1) Front Side Front
<Top Side
View> Front Side Front Side Front Side Min.Front
400 Side Front Side Front Side Front
Min. 10 *1) M
<Top View> Min. 10<Top View> Min.Min.
400 200 Min. 400
<Top View> Min. 400
<Top View> <Top View>
Front Side • MULTIPLE / SERIAL INSTALLATION
Min. 500 + h2/2 Front Side Front Side Front Side <Top View> Fro
NoNolimit
limit
forfor NoNolimit
limit
forfor NoNo
limit
limit
forfor
side
sidewall
wall
height.
height. side wall
side height. <Top View>
height.
wall side
side
wall
wall
height.
height. Min. 400
No limit for side wall height. <Top View>
<Top
Min.
Min. View>
300
300 Min.
Min. 300
300 Min.
Min.
300
300
(Rear
(Rear
Side
Side
Space)
Space) (Rear Side
(Rear Space)
Side Space) (Rear
(Rear
Side
Side
Space)
Space)
*1)*1)
Min.
Min.1010 Min.
Min.200
200

“ ” “
Front
Front
Side
Side Front
Front
Side
Side Front
Front
Side
Side Front
Front
Side
Side Front
Front
Side
Side
Min.
Min.
500
500
+ h2/2
+ h2/2
<Top
<TopView>
View> Min.
Min. 400
400 Min.
Min.400
400 This indicate
<Top
<TopView>
View> This indicates the direction
This of “t
indicates
unit(Front Si
Min. 500direction
+ h2/2 of the direction of the
<Top
<Top
View>
View>
Min. 300 + h1/2 Min. 300 + h1/2 unit(Front Side) when installingSide
unit(Front the
Front Side
*1) Min. 300 + h1/2
Min. 300 + h1/2 *1) installing the units. installing the u
Min.10 Min.10
2) Walls on 3 Sides *1) This indicate
Min. 10 (Side direction of t
*1) • SINGLE INSTALLATION
*1) Space)
Min. 10 Min. 10 unit(Front Si
Front Side
Min. 500 Min. 900 installing the
Front Side Min. 300 + h1/2
Min. 500 + h2/2
Front Side Front Side
Min.
*1)500 + h2/2 Min. 500 + h2/2
Min. 10 “ “ ” ”
No limit for side wall height.
FrontNo limit for <Top
sideView> Front
Min.20 side wall height.
No limit for wall height.
*1) *1) *1) *1)
Min.20 Side Min. 500 + h2/2 Min.20 Side Min.20 Min. 500 + h2/2
<Top View> <Top Front Side
View> Min. 500 + h2/2 This
Thisindicates
indicates the
the
No limit for side wall height. direction
Nodirection
limit forofof
the
side the
wall height.
<Top View> unit(Front
unit(Front
<TopSide)Side)
View> when
when
No limit for side wall height.
Min.
Min.
300
300+ h1/2
+ h1/2 installing
installingthethe
units.
units.
<Top View>

*1)*1)
Min.
Min.1010 • MULTIPLE / SERIAL INSTALLATION
[ INSTALLATION IN THE SAME DIRECTION ] [ REAR TO REAR INSTALLATION ]
Min. 300 + h1/2 Min. 5
Front
Front
Side
Side Front Side
Min.
Min.500
500
+ h2/2
+ h2/2 Min. 500 + h2/2 Min. 500
Min. 300 + h1/2 Min. 300 + h1/2
Min.10
*1) Front Side
Min.10
*1) Front Side
*1) *1) *1) *1)
NoNo
limit
limit
forfor
side
side
wall
wall Min.10
height.
height. Min.10 Min.10 (Side
Min.10
(Side Space)
(Side
<Top
<TopView>
View> Front Side
Min. 300 + h1/2 Space) Space) Min. 5
Min. 500
Front Side Min. 900
Front Side Front Side
Min. 500
*1) Min. 500 *1) Min. 900 Min. 900
Min.10 Min.10
(Side
Space)
*1) Front
FrontSide *1) Front *1) *1)
Min.20 Side Min.20
Min. 500 Min. 500 + h2/2 Min.20 Min.20Min. 900M
Side
*1) Front *1) *1) Front *1) *1) Front *1) Front
*1) *1)
Min.20 Side Min.20 Min.20Min. 500Side+ h2/2 Min.20 Min. 500 + h2/2 Min.20 Side Min.20 Min.20 Min. 500
Side+ h2/2 Min.20 Min.
No limit for side wall height. No limit for side wall height.
No limit for side wall height <Top
No. limit for sideView>
wall height. Min.
Min. No+ limit
500
500 h2/2 for side wall height
+ h2/2 <Top
No. limit for sideView>
wall height.
Min.
Min.300
300
+ h1/2
+ h1/2
<Top View> <Top
*1) View>
Front *1) Front
FrontSide
Side <Top View> <Top
*1) View>
Front *1)
*1)*1)
Min.20 Side Min.20
*1)*1) 20Min. 500 + h2/2 Min.20 Side P5417001
Min.20 M
Min.10
Min.10 Min.10
Min.10
*1): In the case that the field-supplied(Sidesnow protection hood or the air outlet duct is adopted, the space of minimum 50mm is
(Side
required. No limit for side wall height. No limit for side wall height.
Space)
Space)
Front
Front
Side
Side <Top View> <Top View>
Min.
Min.
500
500 Min.
Min.900
900

34
Service Space

No limit for
3) Walls on 4 Sides side wall height.

Min. 300 + h1/2


• SINGLE INSTALLATION
No limit for
Min.side
200wall height. Min. 200

▼ Min. 300 + h1/2


No limit for
*2) Front Side side wall height.
Min. 800
OpenMin. 200 Min. 200
No limit for
side wall height.
▼ Min. 500 + h2/2
Min. 300 + h1/2 No limit for
*2) <Top View> side wall height.
Min. 800 Front Side
Min.
Open 200 Min. 200


No Min. 500 + h2/2
limit for
*2) side wall height.
Min. 800 <Top
Front Side View>
Open

No limit for • MULTIPLE / SERIAL INSTALLATION Min. 500 + h2/2


side wall height. [ INSTALLATION IN THE SAME DIRECTION ] <Top View>

Min. 300 + h1/2

Min. 200 Min. 200 Min. 300 + h1/2

▼ Min. 200 Min. 200


No limit for Min. 200
*2)
Min. 800 Front Side side wall height. ▼ (Side Space)
Front Side Min. 300 + h1/2
Open Min.Min.
900300 + h1/2
No limit for No limit for Front Side
Min. 500 + h2/2 side wall height. No limit for
Min.
Min.200 Min. 200 side wall
Min. 200height. ▼ ▼
200
<Top View> Min. 200 side wallMin. 200
height.
▼ ▼ (Side Space) (Side Space)
*2)
FrontFront
Side SideMin.▼900 *2 )
Min. 800for
No limit Front Side Min.
No 900 Min. 800
limit for
No side
limitwall
for No limit for
No limit for
Open height. side wall height.
Open wall height. No limit for
side wall height. side wall side
height. *2)

Min.
side 800
wall height.
Min. 800
*2)
Min. 200 Min. 200 Min. 800
*2 ) Open
Front Side ▼ Min. 500
Open
+ h2/2 ▼
Open*2) *2 )
Min. 800 <Top Front
View>Side Min. 800 Min. 800
*2) Front Side
Open Min. 200 Min. 200 Open Open
Min. 500 + h2/2 *2)
[ REAR TO REAR INSTALLATION ] Min. 800
<Top View>
Min. 200 Min. 200 Open
Min. 200 Min. 20
Min. 500 + h2/2
<Top View>
Min. 300 + h1/2 <Top View> Min. 500 + h2/2
Front Side
▼ ▼ ▼
Min. 200 Min. 200
Min. 200 Min. 200
▼ (Side Space)
Front Side
Min. 900
No limit for No limit for
side wall height. side wall height. No limit for Min. 1600
side wall height. No limit for
side wall height.

*2) *2 )
Min. 800 Front Side Min. 800
Open Open ▼
*2) Front Side *2)
Min. 800 Min. 800
Min. 200 Min. 200 Open Open
Min. 500 + h2/2
<Top View>
Min. 200 Min. 200 Min. 500 + h2/2
<Top View>

*2): Partly open a wall if the unit is surrounded by walls on four sides. 1 Group (Max. 6 Outdoor Units)
Min. 1m
NOTES:
1. Keep the upper side open to prevent mutual interference of inlet and
outlet air of each outdoor unit. 1 Group (Max. 6 Outdoor Units)
2. The figure dimensions indicate sufficient spaces around outdoor units Min.
for operation and maintenance at typical installation conditions as
follows. [ Operation Mode: Cooling Operation, Outside Temp.: 35oC ]
In case that the outdoor unit ambient temperature is higher and
also the short circuit is likely to occur compared to the installation 1 Group (Max. 6 Outdoor Units)
condition, find an appropriate dimension by calculating air flow M
current.
3. For the multiple installation, 1 group shall consist of 6 outdoor units
(max.).Keep 1-meter interval between each unit group.

35
Options
Options

1. PIPING CONNECTION KIT


Piping Connection Kit for the divergence between outdoor units

Applicable Outdoor Unit


Item Model Remarks
HP Connectivity Number
for Gas: 1
26 - 48 2 MC-NP21SA
Piping for Liquid: 1
Connection Kit for Gas: 2
50 - 54 3 MC-NP30SA
for Liquid: 2

NOTE:The old model (MC-TTA1) is not available.

images:MC-NP30SA

For Piping from Bottom Base


Accessory Pipe -Perform the piping connection between outdoor
(Z-Shape) units according to this figure.
Base
(Field-Supplied) Outdoor Unit A -Refer to “Installation & Maintenance Manual” of the
outdoor unit for the dimension and distance between
outdoor units and between piping connection kits.
Accessory Pipe
(Z-Shape)
Gas Piping Outdoor Unit B
(Field-Supplied)
Outdoor Unit C
Liquid Piping
(Field-Supplied)

Piping Connection
Kit 1 (Liquid)

Piping Connection
Kit 1 (Gas) Gas Piping
(Field-Supplied)

Accessory Pipe Piping Connection


(L-Shape) Kit 2 (Liquid)

Piping Connection
Accessory Pipe
Kit 2 (Gas)
(L-Shape)

Liquid Piping Gas Piping


(Field-Supplied) (Field-Supplied)
*Perform the piping connection between outdoor units according to this figure.
*Refer to the Installation & Maintenance Manual of the outdoor unit for the dimensions and distance between outdoor units and between piping connection kits.

37
Dimensions

MC-NP21SA

GAS Side Liquid Side

469 469 378 378


ID22.2 ID22.2 ID9.52 ID9.52
ID31.75 ID25.4
ID31.75 ODUID25.4 ODU ID15.88 ID12.7
ID15.88 ID12.7
ID38.1 469 ID28.58
ID38.1 ID28.58 ID19.05 ID15.88 ID19.05 ODU
378 ID15.88 ODU
ID22.2 ID9.52
ID31.75 ID25.4 ODU ID15.88 ID12.7
158

158

ODU

130
ID38.1 ID28.58
95

80
ID19.05 ID15.88

130
95

80
IDU IDU

Insulation Insulation
ID28.58 ID28.5883 ID19.05 Insulation 61 61
158

Insulation ID19.05

130
95

83

80
382 382 IDU
IDU ODU 303 ODU
303 ODU
IDU ODU
Insulation ID28.58 ID19.05 61
382 83 Insulation
IDU OD28.58 ODU OD19.05
OD28.58 OD19.05 303 ODU
OD28.58 OD28.58
ID22.2 ID22.2
Reducer Reducer Reducer
Reducer Reducer
ID25.4 ID25.4
ID28.58 OD28.58
ID28.58 OD19.05
ID28.58 ID28.58
ID15.88 ID15.88
OD28.58
ID22.2 ID25.4 ID25.4
ID12.7
Reducer Reducer ID12.7
Reducer ID25.4 ID22.2 ID22.2
Reducer ID9.52 ID9.52
ID28.58 ID28.58 ID15.88
ID25.4
ID12.7
Reducer ID22.2
ID9.52

MC-NP30SA

GAS Side Liquid Side


472 378
472 378
ID25.4 ID9.52
ID25.4 ID9.52
ID31.75 ID28.58
ID31.75 ID28.58 ID15.88 ID12.7
ID38.1 472 ID31.75 ODU 378 ID15.88 ID12.7
ID38.1 ID25.4 ID31.75 ODU ID19.05 ID15.88 ODU
ID19.05 ID15.88 ODU
ID9.52
ID31.75 ID28.58
ID15.88 ID12.7
ID38.1 ID31.75 ODU ODU
ID19.05 ID15.88
130
158
95

80

130
158

IDU
95

80

IDU
130
158
95

80

Insulation 83 IDU ID19.05 61


ID28.58
Insulation 83 Insulation ID19.05 61
ID28.58 Insulation
382 ODU 303 ODU
382 ODU 303 ODU
IDU Insulation 83 ID19.05 61
IDU ID28.58 Insulation
382 ODU 303 ODU
ID31.75 OD28.58 OD19.05
IDU ID31.75 OD28.58 OD19.05
Reducer Reducer
Reducer ID38.1
ID38.1
Reducer ID31.75 OD28.58 OD19.05 Reducer
Reducer
OD31.75 Reducer
OD31.75 ID28.58Reducer
ID28.58 ID15.88
ID25.4 ID25.4 ID15.88 OD31.75
ID38.1 OD31.75
Reducer ID25.4 ID25.4 ID12.7 Reducer
ID12.7 Reducer
OD31.75 ID28.58 ID22.2 Reducer
OD28.58 ID28.58
ID28.58 ID22.2 ID9.52
OD28.58 ID15.88 ID9.52
OD31.75
ID25.4 ID25.4
Reducer OD15.88 Reducer
Reducer ID12.7 Reducer Reducer
OD15.88
ID28.58 ID22.2
OD28.58 ID9.52

Reducer OD15.88ID19.05Reducer
ID19.05

ID19.05

38
Options

2. MULTI-KIT

Branching for indoor and outdoor connecting pipes

Line Branch
First branching pipes Pipe diameter after the first branch and multi-kit
Outdoor Unit HP Model Diameter (mm)
Total Indoor Unit HP Model
5 - 10 MW-NP282A3 Gas Pipe Liquid Pipe
12 - 16 MW-NP452A3 < 6 Φ 15.88 Φ 9.52
18 - 24 MW-NP692A3 6 - 8.99 Φ 19.05 Φ 9.52 MW-NP282A3
26 - 54 MW-NP902A3 9 - 11.99 Φ 22.2 Φ 9.52
12 - 15.99 Φ 25.4 Φ 12.7
MW-NP452A3
16 - 17.99 Φ 28.58 Φ 12.7
18 - 25.99 Φ 28.58 Φ 15.88 MW-NP692A3
26 - 35.99 Φ 31.75 Φ 19.05
MW-NP902A3
< 36 Φ 38.1 Φ 19.05

images:MW-NP282A3

Header branch
Total Indoor Unit HP No. of Header Branches Model
5-8 4 MH-NP224A
5 - 10 8 MH-NP288A

images:MH-NP224A

39
426
ID15.88 ID15.88 67
ID19.05 ID19.05
ID22.2 ID22.2

ID12.7
main piping Ins
Dimensions

206
ODU
ID19.05

178
Insulation ID15.88
ID12.7
ODU
MW-NP282A3
251 IDU
GAS Side Liquid Side Reducer
426 426 256 256 main piping
main piping
ID9.52
ID15.88 ID15.88ID15.88 ID15.88 67 67 ID6.35 50
ID6.35 50
ID19.05 ID19.05ID19.05 ID19.05 ID9.52 ID9.52
ID9.52 ID9.52
ID22.2 ID22.2ID22.2 ID22.2 OD6.35
Reducer
ID12.7 ID12.7

122

122
main piping
100

main piping

100
Insulation Insulation
206

206

ODU ODU
ID19.05 ID19.05 ID9.52 ID9.52
178

178

ID15.88 ID15.88 ID6.35 ID6.35


Insulation Insulation 365 mai
ID12.7 170 IDU
170 IDU
ID12.7 ID25.4 ID28.58
ODU ODU
ID22.2 ID28.58
251 251 IDU IDU

ODU
ID9.52 ID9.52 365 main piping
262
ID25.4 ID28.58 77

219
OD6.35 ID22.2 ID28.58 ID22.2
OD6.35 Insulation ID12.7
Reducer Reducer
ID19.05
ID15.88
MW-NP452A3 ODU
ID12.7
290 IDU
GAS Side Liquid Side Reducer

251
219
ID22.2
365 365 main piping main piping main piping
Insulation Insulation
262 262 main piping ID25.4
ID25.4 ID25.4 ID28.58 ID28.58 ID19.05 OD28.58 ID15.88 ID9.52
77 77 ID9.52 ID9.5256 56
ID22.2 ID22.2 ID28.58 ID28.58 ID12.7 ID12.7 ID15.88 173
ID12.7 ID12.7
ID12.7
ID12.7 ODU
OD6.35
290 IDU
Reducer ID22.2 ID19.05 Reducer
ODU ODU
ID12.7
163

ID12.7
163

ID25.4
139
139

OD28.58 ID15.88
251

ID9.52
251

ID9.52 ID9.52
219
219

ID22.2 ID22.2 ID6.35


Insulation Insulation Insulation ID6.35
Insulation
ID19.05 ID19.05 ID12.7 OD6.35
ID15.88 ID15.88 173 173IDU IDU Reducer ID22.2 ID19.05 Reducer
ID12.7 ID12.7
ODU ODU
ID19.05
290 290 IDU IDU Insulation 55
ID15.88

ID25.4 ID25.4 OD6.35 ID9.53


OD28.58 OD28.58 ID15.88 ID15.88 ID9.52 ID9.52
109

ID12.7 ID12.7
OD6.35 OD6.35
Reducer ReducerID19.05
ID22.2 ID22.2 ID19.05 Reducer Reducer 60 ID15.88
3×60=180 ID12.7
MH-NP224A 400

GAS Side Liquid Side Reducer


Insulation
ID19.05 55
ID19.05 55 Insulation
Insulation ID15.88
ID15.88
OD6.35 ID9.53
81

OD6.35 ID9.53
109
109

60
3×60=180
60 375 ID15.88
60 ID15.88
3×60=180 ID6.35 ID12.7
3×60=180 ID12.7
Insulation
400
400
ID9.53 ID9.53
85

Insulation
Insulation
81
81

60
60
3×60=180
3×60=180
375
375
ID6.35
40
ID6.35 Insulation
Insulation
Options

365 main piping


ID22.2 ID28.58 77 ID
ID25.4
ID28.58

Dimensions
ODU

251
219
Insulation ID22.2

MW-NP692A3 ODU ID19.05


ID15.88
GAS Side Liquid Side Reducer ID12.7
290 IDU

365 365 main piping main piping 387 387 main piping main piping
ID25.4
ID22.2 ID22.2 ID28.58 ID28.58 77 77 ID15.88 ID15.88 ID12.7 ID12.7
67 67
ID25.4 ID25.4 ID19.05 ID19.05 ID15.88 ID15.88 OD28.58 ID15.88 ID9.52
ID28.58 ID28.58 ID22.2 ID22.2
ID12.7 OD6.35
Reducer ID22.2 ID19.05 Reducer
ID9.52 ID9.52
219

219
ODU ODU
251

251

191

191
ID15.88 ID15.88
219

219

Insulation Insulation
ID22.2 ID22.2 Insulation Insulation
ID12.7 ID12.7
ODU ODU ID19.05 ID19.05
ID9.52 ID9.52
ID15.88 ID15.88 ID6.35 ID6.35
ID12.7 ID12.7 main piping
251 251 IDU IDU 477
290 290 IDU IDU
ID31.75 87
ID38.1 ID38.1
ID25.4 ID25.4
OD28.58 OD28.58 ID15.88 ID15.88 ID9.52 ID9.52
ID34.92

257
ID12.7 ID12.7
OD6.35 OD6.35 main piping ID31.75

220
477 429
Reducer ID22.2Reducer
ID19.05
ID22.2 ID19.05 Reducer Reducer Insulation
ID31.75 87 ID15.88
ID38.1 ODU
ID38.1 ID19.05 ID19.0
MW-NP902A3 ID28.58 ID22.2 ID22.2
308 IDU

GAS Side Liquid Side Reducer ID34.92

257
main piping main piping ID31.75
477 477 429 429 ID22.2220 OD28.58 Insulation O
Insulation ID25.4 ID15.88
ID31.75 ID31.75 87 87ID15.88 ID12.7
ID15.88 main ID12.7
piping main piping ID28.58 ODU I
ODU
ID38.1 ID38.1 ID38.1 ID38.1 ID19.05 ID19.05ID19.05 ID19.0567 67 ID9.52 I
ID22.2 ID22.2 ID22.2 ID22.2 ID28.58 ID12.7
ID6.35
308 OD31.75
IDU ID25.4 Reducer ID22.2 ID19.05 ID
Re
251
Reducer
ID34.92 ID34.92 ID15.88 ID15.88
257

257

ID31.75 ID31.75 ID9.52 ID9.52


240

240
220

220

Insulation Insulation OD28.58 OD6.35


212

212

ID22.2
Insulation Insulation ID28.58 ID25.4 ID15.88
ODU ID15.88
ODU ID15.88 ID9.52
ODU ODU
ID9.52 ID12.7 ID9.52 ID12.7 ID12.7
ID28.58 ID28.58
ID6.35 ID6.35
308 308
IDU IDU IDU IDU OD31.75 ID25.4 Reducer80ID22.2 ID19.05 55
Reducer
251 ID19.05 251
ID22.2 Reducer
ID15.88 Insulation
OD15.88 ID19.05 OD6.35 ID9.53

ID22.2 OD28.58
ID22.2 OD28.58 OD6.35 OD6.35
ID28.58 ID28.58 ID25.4 ID15.88 ID25.4 ID15.88
ID9.52 ID9.52
111

ID12.7 ID12.7
OD31.75 OD31.75Reducer ID22.2 ID15.88
ID25.4 Reducer ID22.2 Reducer
ID25.4 ID19.05 ID19.05 Reducer
Reducer Reducer ID12.7
60

MH-NP288A 7×60=420
615

GAS Side Liquid Side Reducer


Insulation
80 55
ID19.05 ID22.2 80 55
ID15.88 Insulation ID19.05 ID22.2
OD15.88 ID19.05 OD6.35 ID9.53
84

ID15.88 Insulation
OD15.88 ID19.05 OD6.35 ID9.53
111

60
7×60=420
111

ID15.88 685
ID12.7 ID15.88
60 ID6.35 Insulation
ID9.53 ID12.7
7×60=420 60
ID9.53
ID12.7
85

615 7×60=420
615

Insulation
Insulation
84

84

60
7×60=420
60
685 7×60=420
685
ID6.35 Insulation
ID9.53
41 ID9.53
ID6.35 Insulation
ID9.53
ID12.7
85

ID9.53
ID12.7
85
3. DRAIN BOSS
The drain boss is for the drain pipe connection in order to use the bottom base of the outdoor unit as a drain pan.

Model Name Quantity


Name Model Applicable Outdoor Unit HP Q'ty
Drain Boss DBS-TP10A 8 - 18 1
20 - 36 2
38 , 40 3
42 - 48 4
50 - 54 3
4
- 5
6

images:DBS-TP10A Dimensions
Drain Boss + Rubber Cap Drain Cap + Rubber Cap Drain Boss×2 Drain Cap×2
To close the drain hall

Ø32 Ø32 Ø32 Ø32


43

43

43

43
30

30

30

30
Ø20 Ø20
Ø25 Ø25 Ø25 Ø25

Drain Water Treatment install Drain


install
capDrain cap
(247) (247)
2 points 2 points
Drain water is discharged during heating and defrosting operation. (Rain water is also discharged.) Pay attention to the following.
1. Choose a location where well drainage is available, Ø32 or provide a drain ditch. Ø32
Ø32 Ø32
(90) (90)
2. Do not install the unit over a walkway, as condensation water may drip onto people.
back back
In the case of installing the unit in such a location, provide an additional drain pan.
43

43
43

43
30

30
30

30

42

42

3. Do not use the drain boss in a cold area. The drain water in the drain pipe may freeze, and the drain pipe may crack.
Ø20
90

90

Ø20
Ø25 Ø25 Ø25
Ø25
(48)

(48)

Drain piping
Drain piping bottom bas
bo
field supplyed
field supplyed install Drain
install
bollDrain
2 points
boll 2 points
ODU rearODUsiderear side
Drain boss
Drain boss Drain capDrain cap
How to use
Bottom view Side view
install Drain cap install Drain cap (247)
2 points (247)
2 points

(90) (90)

back back front front


42
42

90
90

(48)

Drain piping bottom base


(48)

Drain piping bottom base


field supplyed field supplyed install Drain boll install
2 pointsDrain boll 2 points
ODU rear side ODU rear side Drain boss Drain cap
Drain boss Drain cap

42
Options

4. CABINET COVER

Air Inlet Grille Protection Net


HP HP
Rear Right Left Rear Right Left
8 - 12 PSN-TP20BA PSN-TP20R PSN-TP20L 8 - 12 PN-TP20BA PN-TP20R PN-TP20L
14 - 18 PSN-TP20BB PSN-TP20R × 2 14 - 18 PN-TP20BB PN-TP20R × 2
20 - 24 PSN-TP20BC PSN-TP20R × 2 20 - 24 PN-TP20BC PN-TP20R × 2

image:Air Inlet Grille image:Protection Net

Left Side Left Side

Right Side Rear Side Right Side Rear Side

Snow Protection Hood HP Toppling Prevention Tool


HP Upper Rear Right Left 8 - 24 ASG-SW20A
Zinc Coated Steel
8 - 12 ASG-TP50FA ASG-TP50BA ASG-TP50R ASG-TP50L
14 - 18 ASG-TP50FB ASG-TP50BB ASG-TP50R × 2
20 - 24 ASG-TP50FC ASG-TP50BC ASG-TP50R × 2
Stainless
8-12 ASG-TP50FAS ASG-TP50BAS ASG-TP50RS ASG-TP50LS
14-18 ASG-TP50FBS ASG-TP50BBS ASG-TP50RS × 2
20-24 ASG-TP50FS ASG-TP50BCS ASG-TP50RS × 2
NOTE:Refer to the Technical Catalog for the Optional Parts selection.

image:Snow Protection Hood image:Toppling Prevention Tool

(for Left Side


Air Inlet)

(for Air Outlet)


φ2 Wire

Outdoor Unit
Fastening Fitting
(for Rear Side
Air Inlet) Anchor Bolt
(Field-Supplied)
(for Right Side
Air Inlet)
Foundation

43
Resistance to Salt Damage Specifications
Products for Order
About the installation location
Resistance to salt damage specifications Resistance to heavy salt damage specifications

A location that is not exposed A place that is susceptible to sea breezes


to sea breezes, but that (But the device is not directly exposed to
ODU ODU
Installation

appears to be suitable for water containing salt.)


Location

such an atmosphere
ODU ODU

sea sea sea sea

- A location where the outdoor unit is rinsed by the rain - A location where the outdoor unit receives little rain
installation location

- A location that is not exposed to sea breezes - A location that is directly exposed to sea breezes
Requirements for

- A location where the distance from the installation location of the - A location where the distance from the installation location of the outdoor unit to the
outdoor unit to the sea is between approximately 300 meters and sea is up to approximately 300 meters
one kilometer - A location where the outdoor unit is mounted on the front of a building (beach side)
- A location where the outdoor unit is in the shelter of a building - A location where corrugated iron roofs and the steel parts of balconies near the
installation location of the outdoor unit are often repainted

The standard of the installation distance from the beach


(conditions vary according to the installation environment)

1 A location that receives direct sea breezes


The standard of the installation distance
(1) A region that faces an inland sea 300 m 500 m 1000 m
(2) A region that faces the open sea
(3) Okinawa and remote islands
Resistance to salt damage Resistance to heavy salt damage

2 A location that does not receive direct sea breezes


The standard of the installation distance
(1) A region that faces an inland sea 300 m 500 m 1000 m
(2) A region that faces the open sea
(3) Okinawa and remote islands
Resistance to salt damage Resistance to heavy salt damage

Points to note for installation, maintenance and management


• Points to note for installation (regarding maintenance and management)
The units of JRA specifications for resistance to salt damage and resistance to heavy salt damage are made with strengthened materials and
paints, but they are not fully protected against corrosion.
It is therefore necessary to increase the anti-corrosion effects by carrying out the following installation plans and maintenance work.
(1) Please install the device in a location that avoids direct sea water splashes and sea breezes as much as possible.
-Please install the device on the leeward side of a building.
-If you have to install a device on the side of the beach, please avoid exposing it to direct sea breezes by erecting a wind-protective board.
-Please be careful about the direction of installation. (The degree of corrosion differs depending on whether a device is installed parallel to the coastline
or perpendicular to the coastline.)
(2) Please ensure that any sea salt particles that adhere to the exterior panels will be washed away by the rain.
(3) Because the pooling of water on the bottom base of the outdoor unit significantly boosts the corrosion effects, please be careful about the inclination so
that the ability for water to run through the bottom base of an outdoor unit will not be affected.
(4) For a device installed in a beach area, please rinse it with water on a regular basis to remove all salt adhering to the device.
(5) Please install the device in a location where water drains away well. In particular, please secure the drainage of the foundation parts.
(6) Please be sure to repair any scratches that are created during the installation and maintenance work.
(7) Please inspect the conditions of the device on a regular basis. (If necessary, please apply anti-rust treatments or replace parts.)

• Points to note for maintenance


-Please carry out sufficient maintenance work on the device.
-If you stop using the device for a long time, such as during the off-season, please take measures such as putting a cover on the device.

*If you install the device in a special atmosphere, you will need to undertake sufficient special consideration.
Units that are resistant to salt damage are based on the “Standard of Testing Resistance to Salt Damage of Air Conditioning Devices JRA9002” of the Japan Refrigeration and Air
Conditioning Industry Association (JRAIA).

44
Global Footprint

Global Footprint

45
46
Johnson Controls - Hitachi Air Conditioning
http://www.jci-hitachi.com

Manufactured by

Distributed by

ISO 9000 series The quality of our design and manufacturing systems has been approved.
We are a domestic business office designing and manufacturing air conditioners. We have obtained the
international standard ISO 9001 certification regarding quality management systems.

Shimizu Air Conditioning Headquarters, Professional-Use Air Conditioning Business Division, Johnson Controls
– Hitachi Air Conditioning
JQA-1084 JQA-1084 obtained in November 1995

ISO 14000 series Our environmental preservation activities have been approved.
We are a domestic business office designing and manufacturing air conditioners. We have obtained the
international standard ISO 14001 certification regarding environmental management systems.

Shimizu Business Office, Johnson Controls – Hitachi Air Conditioning


EC97J1107 EC97J1107 obtained in October 1997

Potrebbero piacerti anche