NTP 399.

006 : 2003
TUBO CONDUIT ELÉCTRICO F.G. Tubo PVC-U para canalizaciones eléctric
Øn Øn Øex Øex Øn Øn Øex
L [m] L [m]* e [mm]
[pulg] [mm] [pulg] [mm] [pulg] [mm] [mm]
1/2 12.70 0.84 21.30 3.00 6.00 1/2 10.00 12.70 1.10
3/4 19.05 1.05 26.70 3.00 6.00 5/8 13.00 15.90 1.10
1 25.40 1.32 33.40 3.00 6.00 3/4 15.00 19.10 1.20
1 1/4 31.75 1.66 42.20 3.00 6.00 1 20.00 25.40 1.30
1 1/2 38.10 1.90 48.30 3.00 6.00 1 1/4 25.00 31.80 1.30
2 50.80 2.38 60.30 3.00 6.00 1 1/2 30.00 38.10 1.60
2 1/2 63.50 2.88 73.00 3.00 6.00 2 40.00 50.80 1.70
3 76.20 3.50 88.90 3.00 6.00
4 101.60 4.50 114.30 3.00 6.00
5 127.00 5.56 141.30 3.00 6.00
6 152.40 6.63 168.30 3.00 6.00

DIÁMETRO ESPESOR DIÁMETRO


TUBO DIÁMETRO
PVC EXTERIOR DE PARED INTERIOR
NOMINAL
PROMEDIO MINIMO PROMEDIO
Øn Øn Øex Øex e e Øint Øint Peso
Tipo L [m] L u [m]
[pulg] [mm] [mm] [pulg] [mm] [pulg] [mm] [pulg] [kg/t]
SEL 1/2'' 11 12.70 0.50 1.10 0.06 10.50 0.38 0.187 3 2.99
SEL 5/8'' 13 15.90 0.63 1.10 0.06 13.70 0.51 0.239 3 2.99
SEL 3/4'' 15 19.10 0.75 1.20 0.06 16.70 0.63 0.314 3 2.98
SEL 1/1'' 20 25.40 1.00 1.30 0.06 22.80 0.88 0.458 3 2.98
SEL 5/4'' 25 31.80 1.25 1.30 0.07 29.20 1.11 0.577 3 2.97
SEL 3/2'' 30 38.10 1.50 1.60 0.08 34.90 1.34 0.852 3 2.97
SEL 2/1'' 40 50.80 2.00 1.70 0.10 47.40 1.80 1.217 3 2.96

SAP 1/2'' 15 21.00 0.84 1.8 0.07 17.40 0.70 0.506 3 2.98
SAP 3/4'' 20 26.50 1.05 1.8 0.07 22.90 0.91 0.650 3 2.98
SAP 1/1'' 25 33.00 1.31 1.8 0.07 29.40 1.17 0.820 3 2.97
SAP 5/4'' 35 42.00 1.66 2 0.08 38.00 1.50 1.167 3 2.97
SAP 3/2'' 40 48.00 1.90 2.3 0.09 43.40 1.72 1.533 3 2.96
SAP 2/1'' 50 60.00 2.37 2.8 0.11 54.40 2.15 2.335 3 2.96
SAP 5/2'' 65 73.00 2.87 3.5 0.14 66.00 2.59 3.545 3 2.95
SAP 3/1'' 80 88.50 3.50 3.8 0.15 80.90 3.20 4.690 3 2.94
SAP 4/1'' 100 114.00 4.50 4 0.16 106.00 4.19 6.410 3 2.93

Accesorios de PVC CONDUIT TIPO LIVIANO


CURVAS DE 90º CAMPANA X ESPIGO
DIÁMETRO RADIO LONGIT
NOMINAL R UD B

MINIM MINIM
(mm) (pulg) O mm O mm

21 ½ 100 38
26 ¾ 114 38

33 1 146 48

42 1¼ 184 50
48 1½ 210 50
60 2 241 50

CURVAS DE 45º CAMPANA X ESPIGO


DIÁMETRO RADIO LONGIT
NOMINAL R UD B

MINIM MINIM
(mm) (pulg) O mm O mm

21 ½ 100 38
26 ¾ 114 38
33 1 146 48
42 1¼ 184 50
48 1½ 210 50
60 2 241 50

ADAPTADOR TERMINAL DE PVC

DIÁMETRO L
NOMINAL
(mm) (pulg) (mm) (pulg)
21 ½ 17.48 0.688
26 ¾ 18.26 0.719
33 1 22.23 0.875
42 1¼ 23.83 0.938
48 1½ 27.79 1.094
60 2 29.36 1.155
NTP 399.006 : 2003
nalizaciones eléctricas TUBERIA PVC - SAP
Øint Peso Øn Øn Øex e Øint Peso
L [m]*
[mm] [kg] [pulg] [mm] [mm] [mm] [mm] [kg]
10.50 3.00 1/2 15.00 21.00 1.80 17.40 0.48
13.70 0.22 3.00 3/4 20.00 26.50 1.80 22.90 0.62
16.70 0.29 3.00 1 25.00 33.00 1.80 29.40 0.87
22.80 0.43 3.00 1 1/4 30.00 42.00 2.00 38.00 1.11
29.20 0.56 3.00 1 1/2 40.00 48.00 2.30 43.40 1.46
34.90 0.79 3.00 2 50.00 60.00 2.80 54.40 2.18
47.40 1.14 3.00 2 1/2 65.00 73.00 3.50 66.00 3.31
3 80.00 88.50 3.80 80.90 4.38
4 100.00 114.00 4.00 106.00 5.98
Tuberías Conduit PAVCO
Øn Øn Øex e Øint Peso
L [m]* L [m]*
[pulg] [mm] [mm] [mm] [mm] [kg/m]
3.00 1/2 21.00 21.34 1.52 17.40 0.13 3.00
3.00 3/4 26.00 26.67 1.52 22.90 0.17 3.00
3.00 1 33.00 33.40 1.52 29.40 0.21 3.00
3.00 1 1/4 42.00 42.16 1.78 38.00 0.32 3.00
3.00 1 1/2 48.00 48.26 2.03 43.40 0.42 3.00
3.00 2 60.00 60.32 2.54 54.40 0.65 3.00
3.00
3.00
3.00
SANEAMIENTO
Electrificación - SEL
TUBERÍAS Y ACCESORIOS PARA INSTALACIONES ELECTRICAS
Fabricadas de acuerdo a norma técnica peruana NTP 399.006
La Clase pesada S.E.L. ( Standard Europeo Pesado ) para instalaciones domésticas.

CLASE LIVIANA ( largo de tubería 3m )


Espeso Diámetro
Diámetro nominal Diámetro exterior Peso aprox. por
r inferior

en pulgadas (Plg.) en mm en mm en mm tubo en Kg.

5/8” 15.9 1.1 13.7 0.22


3/4“ 19.1 1.2 16.7 0.29
1“ 25.4 1.3 22.8 0.43
1 1/4“ 31.8 1.3 29.2 0.54
1 1/2“ 38.1 1.6 34.9 0.83
2“ 50.8 1.7 47.4 1.13
ACCESORIOS
IMPORTANTE:

En los accesorios considerar una tolerancia en las longitudes de ± 10%. Así mismo la longitud de la campana es de 80% del
diámetro exterior.

CURVAS A 90º
Ø R Y Peso
Plg. mm mm Kg
5/8" 90 15 0.012
3/4" 109 19 0.015
1" 145 25 0.031
1 1/4 " 182 31 0.050
1 1/2 " 218 38 0.082
2" 291 50 0.175

CONEXIONES A CAJA
Ø X Peso
Plg. mm Kg
5/8" 16 0.002
3/4" 20 0.003
1" 25 0.005
1 1/4 " 31 0.006
1 1/2 " 38 0.013
2" 50 0.024
EDIFICACION
Electrificación - SAP
TUBERÍAS Y ACCESORIOS PARA INSTALACIONES ELECTRICAS
Fabricadas de acuerdo a norma técnica peruana NTP 399.006
La Clase pesada S.A.P. ( Standard Americano Pesado ) para instalaciones industriales.

CLASE PESADA ( largo de tubería 3m )


Espeso Diámetro
Diámetro nominal Diámetro exterior Peso aprox. por
r interior

en pulgadas (Plg.) en mm en mm en mm tubo en Kg.

1/2“ 21 1.8 17.4 0.466


3/4“ 26.5 1.8 22.9 0.599
1“ 33 1.8 29.4 0.757
1 1/4“ 42 2 38 1.078
1 1/2“ 48 2.3 43.4 1.417
2“ 60 2.8 54.4 2.16
2 1/2" 73 3.5 66 3.28
3“ 88.5 3.8 80.9 4.34
4“ 114 4 106 5.94
ACCESORIOS
IMPORTANTE:

En los accesorios considerar una tolerancia en las longitudes de ± 10%. Así mismo la longitud de la campana es de 80% del
diámetro exterior.

CURVAS A 90º
Ø R Y Peso
Plg. mm mm Kg
1/2" 120 21 0.035
3/4" 151 26 0.047
1" 189 33 0.065
1 1/4 " 240 42 0.130
1 1/2 " 275 48 0.180
2" 343 60 0.360
3" 505 88 1.080
4" 653 114 1.930

CONEXIONES A CAJA
Ø X Peso
Plg. mm Kg
1/2" 21 0.005
3/4" 26 0.006
1" 33 0.010
1 1/4 " 42 0.019
1 1/2 " 48 0.026
2" 60 0.050
3" 88 0.145
4" 114 0.245
NUMEROS MAXIMO DE CONDUCTORES ELECTRICOS A USARSE EN LA TUBERIA CO
CALIBRE TUBO

Cond. Cond. ≈
Cond. [AWG] [mm²] [mm²] 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3"

16 1.31 1.5 6 10 17 30 41 68 98 150


14 2.08 2.5 4 6 10 18 25 41 58 90
12 3.31 4 3 5 8 15 21 34 50 76
10 5.26 6 1 4 7 13 17 29 41 64
8 8.36 10 1 3 4 7 10 17 25 38
6 13.3 16 1 1 3 4 6 10 15 23
4 21.15 25 1 1 1 3 5 8 12 18
3 26.67 25 - 1 1 3 4 7 10 16
2 33.62 35 - 1 1 3 3 6 9 14
1 42.41 50 - 1 1 1 3 4 7 10

INSTALACIONES INTERIORES
Diámetros exteriores mínimos de los tubos
en función del número y la sección de los conductores o cables a conducir
(ITC-BT-21)
Tubos en canalizaciones fijas en superficie

Diámetros exteriores mínimos de los tubos en función del número


y la sección de los conductores o cables a conducir

Diámetro exterior de los tubos (mm)


Número de conductores
S [mm²] 1 2 3 4 5
1.5 12 12 16 16 16
2.5 12 12 16 16 20
4 12 16 20 20 20
6 12 16 20 20 25
10 16 20 25 32 32
16 16 25 32 32 32
25 20 32 32 40 40
35 25 32 40 40 50
50 25 40 50 50 50
70 32 40 50 63 63
95 32 50 63 63 75
120 40 50 63 75 75
150 40 63 75 75 --
185 50 63 75 -- --
240 50 75 -- -- --
Para más de 5 conductores por tubo o para conductores aislados o cables de secciones diferentes a instalar en el mismo tubo,
Tubos en canalizaciones empotradas
Diámetros exteriores mínimos de los tubos en función del número
y la sección de los conductores o cables a conducir
Sección nominal de los
conductores unipolares Diámetro exterior de los tubos (mm)
(mm2) Número de conductores
S [mm²] 1 2 3 4 5
1.5 12 12 16 16 20
2.5 12 16 20 20 20
4 12 16 20 20 25
6 12 16 25 25 25
10 16 25 25 32 32
16 20 25 32 32 40
25 25 32 40 40 50
35 25 40 40 50 50
50 32 40 50 50 63
70 32 50 63 63 63
95 40 50 63 75 75
120 40 63 75 75 --
150 50 63 75 -- --
185 50 75 -- -- --
240 63 75 -- -- --
Para más de 5 conductores por tubo o para conductores aislados o
cables de secciones diferentes a instalar en el mismo tubo, su
sección interior será, como mínimo igual a 3 veces la sección
ocupada por los conductores.

Tubos en canalizaciones aéreas o con tubos al aire

Diámetros exteriores mínimos de los tubos en función del número


y la sección de los conductores o cables a conducir.

Se recomienda no utilizar este tipo de instalación para secciones


nominales de conductor superiores a 16 mm 2.

Diámetro exterior de los tubos (mm)


Sección nominal de los
Número de conductores
conductores (mm2)
1 2 3 4 5
1.5 12 12 16 16 20
2.5 12 16 20 20 20
4 12 16 20 20 25
6 12 16 25 25 25
10 16 25 25 32 32
16 20 25 32 32 40
Para más de 5 conductores por tubo o para conductores aislados o
cables de secciones diferentes a instalar en el mismo tubo, su
sección interior será, como mínimo igual a 4 veces la sección
ocupada por los conductores.
Tubos en canalizaciones enterradas

Diámetros exteriores mínimos de los tubos en función del número


y la sección de los conductores o cables a conducir

Sección nominal de los Diámetro exterior de los tubos (mm)


conductores unipolares Número de conductores
(mm2) <6 7 8 9 10
1.5 25 32 32 32 32
2.5 32 32 40 40 40
4 40 40 40 40 50
6 50 50 50 63 63
10 63 63 63 75 75
16 63 75 75 75 90
25 90 90 90 110 110
35 90 110 110 110 125
50 110 110 125 125 140
70 125 125 140 160 160
95 140 140 160 160 180
120 160 160 180 180 200
150 180 180 200 200 225
185 180 200 225 225 250
240 225 225 250 250 --
Para más de 10 conductores por tubo o para conductores aislados
o cables de secciones diferentes a instalar en el mismo tubo, su
sección interior será, como mínimo igual a 4 veces la sección
ocupada por los conductores.
SARSE EN LA TUBERIA CONDUIT

4"

-
155
132
110
67
41
31
28
24
18

nstalar en el mismo tubo, su sección interior será, como mínimo igual a 2,5 veces la sección ocupada por los conductores.
Cables UTP dentro de una tubería
Cantidad máxima de cables UTP en tubería
(40% de ocupación de la sección)
Conduit Categoría y diámetro exterior
Número de Cat 5e Cat 6 Cat 6A Cat. 6A Cat 6 FTP
Medida de la tuberia cables UTP
Øext: 6,1 0,2" 0,25" 0,354" 0,33" 0,29"
cm pulgadas mm (0,24")
2.1 ¾ 3 3/4 5 4 2 2 3
2.7 1 6 1 9 6 3 4 5
3.5 1¼ 10 1.25 15 10 5 6 7
4.1 1½ 15 1.5 25 14 7 8 11
5.3 2 20 2 40 26 13 15 19
6.3 2½ 30 2.5 70 40 20 23 30
7.8 3 40 3 100 58 29 33 43