ENGINEERING DATA
Model SN
Model SN
Louvered Face
Square/Round Diffusers
CD
300
0.006
400
0.010
500
0.016
600
0.022
700
0.031
800
0.040
900
0.051
1000
0.062
1200
0.090
1400
0.122
Airflow (CFM)
6"
Total Pressure
Ak = 0.16 Horizontal Throw
Noise Criteria
60
0.009
1-2-4
<15
80
0.016
2-3-6
<15
100
0.025
2-3-7
<15
120
0.036
3-4-8
<15
135
0.045
3-5-9
<15
155
0.060
4-5-11
20
175
0.076
4-6-12
23
195
0.095
4-7-13
26
235
0.137
5-8-16
33
275
0.188
6-9-19
37
Airflow (CFM)
8"
Total Pressure
Ak = 0.22 Horizontal Throw
Noise Criteria
105
0.014
2-3-6
<15
140
0.024
2-4-8
<15
175
0.038
3-5-10
<15
210
0.054
3-6-12
<15
245
0.074
4-7-14
21
280
0.096
4-8-16
26
315
0.122
5-9-18
30
350
0.150
5-10-21
32
420
0.217
6-12-25
37
490
0.295
8-14-29
40
Airflow (CFM)
6"
Total Pressure
Ak = 0.16 Horizontal Throw
Noise Criteria
60
0.009
1-1-3
<15
80
0.016
1-2-3
<15
100
0.025
1-2-4
<15
120
0.036
2-3-5
<15
140
0.048
2-3-6
<15
160
0.063
2-3-7
17
180
0.080
3-4-8
21
200
0.099
3-4-9
25
240
0.142
3-5-10
33
270
0.180
4-6-12
37
Airflow (CFM)
8"
Total Pressure
Ak = 0.26 Horizontal Throw
Noise Criteria
105
0.010
1-2-4
<15
140
0.018
2-3-6
<15
175
0.028
2-4-7
<15
210
0.041
3-4-8
<15
245
0.056
3-5-10
17
280
0.073
4-6-11
22
315
0.092
4-6-13
28
350
0.114
5-7-14
30
420
0.164
6-8-17
36
490
0.223
7-10-20
39
Airflow (CFM)
10"
Total Pressure
Ak = 0.37 Horizontal Throw
Noise Criteria
165
0.012
2-4-7
<15
220
0.022
3-5-10
<15
275
0.034
4-6-12
<15
325
0.048
5-7-15
15
380
0.065
6-8-17
20
435
0.086
6-10-19
26
490
0.109
7-11-22
28
545
0.134
8-12-24
31
655
0.194
10-15-29
36
765
0.265
11-17-34
42
Airflow (CFM)
12"
Total Pressure
Ak = 0.51 Horizontal Throw
Noise Criteria
235
0.013
3-4-9
<15
315
0.024
4-6-12
<15
395
0.038
5-8-15
<15
470
0.053
6-9-18
20
550
0.073
7-10-21
24
630
0.096
8-12-24
28
705
0.120
9-13-27
31
785
0.149
10-15-30
34
940
0.213
12-18-36
41
1100
0.292
14-21-42
45
Airflow (CFM)
14"
Total Pressure
Ak = 0.62 Horizontal Throw
Noise Criteria
320
0.015
4-6-12
<15
430
0.026
5-8-16
<15
535
0.041
7-10-20
18
640
0.058
8-12-24
22
750
0.080
10-14-29
24
855
0.104
11-16-33
28
960
0.131
12-18-37
33
1070
0.163
14-20-41
36
1285
0.235
16-24-49
43
1495
0.318
19-28-57
47
Airflow (CFM)
16"
Total Pressure
Ak = 0.78 Horizontal Throw
Noise Criteria
420
0.018
5-8-16
<15
560
0.032
7-11-22
15
700
0.050
9-13-27
22
840
0.072
11-16-32
22
980
0.098
38-19-13
30
1120
0.128
14-22-43
34
1260
0.162
16-24-48
39
1400
0.200
18-27-54
41
1680
0.288
22-32-65
47
1950
0.388
25-37-75
51
CD
24x24 Module
CD-1
05/06
07/06
30
www.tuttleandbailey.com
02/09
53
ENGINEERING
ENGINEERINGDATA
DATA
Model SA
Model SA
CD
400
0.010
500
0.016
600
0.022
700
0.031
800
0.040
900
0.051
1000
0.062
1200
0.090
1400
0.122
Airflow (CFM)
6"
Total Pressure
Ak = 0.18 Horizontal Throw
Noise Criteria
60
0.007
1-1-3
<15
80
0.012
1-2-4
<15
100
0.019
2-2-5
<15
120
0.027
2-3-5
<15
135
0.034
2-3-6
<15
155
0.045
2-3-7
21
175
0.058
3-4-8
24
195
0.072
3-4-9
27
235
0.104
4-5-11
35
275
0.143
4-6-12
38
Airflow (CFM)
8"
Total Pressure
Ak = 0.28 Horizontal Throw
Noise Criteria
105
0.009
2-3-6
<15
140
0.016
3-4-8
<15
175
0.025
3-5-10
<15
210
0.036
4-6-12
<15
245
0.049
5-7-14
15
280
0.064
5-8-16
20
315
0.081
6-9-19
26
350
0.100
7-10-21
28
420
0.144
8-12-25
33
490
0.196
10-14-29
37
Airflow (CFM)
6"
Total Pressure
Ak = 0.18 Horizontal Throw
Noise Criteria
60
0.007
1-1-3
<15
80
0.012
1-2-3
<15
100
0.019
1-2-4
<15
120
0.028
2-3-4
<15
140
0.038
2-3-6
<15
160
0.049
2-3-7
16
180
0.063
3-4-8
21
200
0.077
3-4-9
25
240
0.111
3-5-10
31
270
0.141
4-6-12
34
Airflow (CFM)
8"
Total Pressure
Ak = 0.31 Horizontal Throw
Noise Criteria
105
0.007
1-2-4
<15
140
0.013
2-3-5
<15
175
0.020
2-3-7
<15
210
0.029
3-4-8
<15
245
0.039
3-5-9
<15
280
0.051
4-5-11
20
315
0.065
4-6-12
25
350
0.080
4-7-13
27
420
0.115
5-8-16
33
490
0.157
6-9-19
37
Airflow (CFM)
10"
Total Pressure
Ak = 0.47 Horizontal Throw
Noise Criteria
165
0.008
2-3-6
<15
220
0.014
3-4-8
<15
275
0.022
3-5-10
<15
325
0.030
4-6-12
<15
380
0.041
5-7-14
<15
435
0.054
5-8-16
18
490
0.069
6-9-18
24
545
0.085
7-10-20
27
655
0.123
8-12-24
33
765
0.168
9-14-28
38
Airflow (CFM)
12"
Total Pressure
Ak = 0.66 Horizontal Throw
Noise Criteria
235
0.008
2-3-7
<15
315
0.014
3-5-9
<15
395
0.023
4-6-12
<15
470
0.032
5-7-14
<15
550
0.044
5-8-16
20
630
0.057
6-9-19
21
705
0.072
7-10-21
25
785
0.089
8-12-23
31
940
0.127
9-14-28
36
1100
0.175
11-16-33
43
Airflow (CFM)
14"
Total Pressure
Ak = 0.82 Horizontal Throw
Noise Criteria
320
0.010
3-5-10
<15
430
0.017
4-7-13
<15
535
0.027
6-8-17
<15
640
0.038
7-10-20
20
750
0.052
8-12-23
22
855
0.068
9-13-27
24
960
0.086
10-15-30
30
1070
0.107
11-17-33
33
1285
0.154
13-20-40
40
1495
0.209
16-23-47
45
Airflow (CFM)
16"
Total Pressure
Ak = 1.03 Horizontal Throw
Noise Criteria
420
0.010
5-7-15
<15
560
0.018
7-10-20
<15
700
0.029
8-12-25
17
840
0.041
10-15-30
20
980
0.056
12-17-35
21
1120
0.073
13-20-39
26
1260
0.093
15-22-44
33
1400
0.114
16-25-49
35
1680
0.164
20-30-59
35
1950
0.222
23-34-69
46
24x24 Module
31
54 02/09
www.tuttleandbailey.com
05/06
07/06
CD-1
CD
Louvered Face
Square/Round Diffusers
300
0.006
ENGINEERING DATA
ENGINEERING DATA
Model SA
Model SA
Louvered Face
Square/Round Diffusers
CD
300
0.006
400
0.010
500
0.016
600
0.022
700
0.031
800
0.040
900
0.051
1000
0.062
1200
0.090
1400
0.122
Airflow (CFM)
6"
Total Pressure
Ak = 0.13 Horizontal Throw
Noise Criteria
60
0.013
2-3-5
<15
80
0.022
2-3-7
<15
100
0.035
3-4-8
<15
120
0.050
3-5-10
<15
135
0.064
4-6-11
20
155
0.084
4-7-13
24
175
0.107
5-7-15
30
195
0.133
5-8-16
34
235
0.193
7-10-20
36
275
0.265
8-12-23
39
Airflow (CFM)
8"
Total Pressure
Ak = 0.19 Horizontal Throw
Noise Criteria
105
0.019
4-5-11
<15
140
0.007
5-7-14
<15
175
0.011
6-9-18
<15
210
0.015
7-11-22
24
245
0.021
3-13-25
27
280
0.027
10-14-29
32
315
0.035
11-16-32
34
350
0.043
12-18-36
35
420
0.062
14-22-43
38
490
0.084
17-25-50
42
Airflow (CFM)
6"
Total Pressure
Ak = 0.14 Horizontal Throw
Noise Criteria
60
0.011
1-1-2
<15
80
0.019
1-1-2
<15
100
0.030
1-1-3
<15
120
0.044
1-2-3
<15
140
0.060
1-2-4
<15
160
0.078
1-2-4
18
180
0.099
2-2-5
23
200
0.122
2-3-5
27
240
0.175
2-3-6
33
270
0.222
2-4-7
37
Airflow (CFM)
8"
Total Pressure
Ak = 0.23 Horizontal Throw
Noise Criteria
105
0.013
1-2-3
<15
140
0.024
1-2-4
<15
175
0.037
2-3-5
<15
210
0.053
2-3-6
15
245
0.072
2-4-7
21
280
0.094
3-4-8
25
315
0.119
3-5-9
30
350
0.147
4-5-11
32
420
0.212
4-6-13
35
490
0.288
5-7-15
40
Airflow (CFM)
10"
Total Pressure
Ak = 0.31 Horizontal Throw
Noise Criteria
165
0.017
2-4-7
<15
220
0.031
3-5-10
<15
275
0.048
4-6-12
<15
325
0.067
5-7-14
22
380
0.092
6-8-17
25
435
0.121
6-10-19
28
490
0.153
7-11-22
31
545
0.190
8-12-24
33
655
0.274
10-14-29
38
765
0.374
11-17-34
43
Airflow (CFM)
12"
Total Pressure
Ak = 0.42 Horizontal Throw
Noise Criteria
235
0.019
3-4-8
<15
315
0.035
4-5-11
<15
395
0.055
4-7-13
21
470
0.077
5-8-16
23
550
0.106
6-9-19
26
630
0.139
7-11-21
28
705
0.174
8-12-24
32
785
0.216
9-13-27
35
940
0.309
11-16-32
42
1100
0.424
12-19-37
48
Airflow (CFM)
14"
Total Pressure
Ak = 0.54 Horizontal Throw
Noise Criteria
320
0.022
4-6-12
<15
430
0.040
6-8-17
20
535
0.062
7-10-21
22
640
0.088
8-12-25
24
750
0.121
10-15-29
28
855
0.158
11-17-33
31
960
0.199
12-19-37
35
1070
0.247
14-21-41
39
1285
0.356
17-25-50
46
1495
0.482
19-29-58
49
Airflow (CFM)
16"
Total Pressure
Ak = 0.63 Horizontal Throw
Noise Criteria
420
0.027
5-7-14
15
560
0.049
6-9-18
21
700
0.076
8-11-23
21
840
0.109
9-14-27
27
980
0.149
11-16-32
31
1120
0.195
12-18-37
36
1260
0.246
14-21-41
39
1400
0.304
15-23-46
41
1680
0.438
18-27-55
49
1950
0.590
21-32-64
54
CD
24x24 Module
Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-1991 at isothermal conditions.
2. Tests conducted with a straight rigid inlet condition. Other inlet conditions may alter performance.
3. Units: Neck Velocity = fpm; Total Pressure = in. wc; Ak = ft.2; Velocity Pressure = in. wc; Effective Area (Ak) = ft.2.
4. Throw = feet at 150 fpm, 100 fpm and 50 fpm terminal velocities.
5. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 thru 4000 Hz octave bands.
6. Flow hoods are recommended for system balancing.
CD-1
05/06
07/06
32
www.tuttleandbailey.com
02/09
55