TRAFO DISTRIBUSI

POLA PEMBEBANAN TRAFO DISTRIBUSI

SESUAI SPLN NO.50 THN : 1997


SUSUT MINIMAL PADA PEMBEBANAN TRAFO = 50 % - 60 %

DROP TEG. MAKSIMUM DISISI SEKUNDER PD SAAT BEBAN MAX ADALAH 3 %

KORELASI BEBAN TERHADAP SUSUT : LOSSES TRAFO = ( i + c. (Pr)2.LLF)


Dimana : i = rugi besi trafo (kW) ; c = Rugi tembaga (kW);
Pr = pembebanan trafo rata2 (%) LLF = Loss load factor;

LOSSES MAX 1,5 % pada suhu 75 oC


Tabel-1 TRAFO DISTRIBUSI
KAPASITAS TRAFO = 50 KVA
LOAD FACTOR (%) LOSSES (%)
KURVA TRAFO 50 KVA
10 10.30 10.3
11
15 7.10
20 5.56 9
7.1
30 4.16 7 5.56
40 3.60 4.16 4.31
4.75
3.91
50 3.37 5 3.6 3.37 3.31 3.34 3.43 3.57 3.73

60 3.31 3
70 3.34
1
80 3.43
90 3.57 -1
10 15 20 30 40 50 60 70 80 90 100 110 130 150
100 3.73
110 3.91 10 15 20 30 40 50 60
130 4.31 70 80 90 100 110 130 150
150 4.75

KAPASITAS TRAFO = 100 KVA


LOAD FACTOR (%) LOSSES (%) KURVA TRAFO 100 KVA
6 5.15
10 5.15
15 3.55
3.55
20 2.78 4
2.78
30 2.08 2.08 2.16
2.38

1.8 1.86 1.95


1.78
40 1.80 1.68 1.65 1.67 1.72
2
50 1.68
60 1.65
70 1.67 0
80 1.72 10 15 20 30 40 50 60 70 80 90 100 110 130 150
90 1.78
100 1.86 10 15 20 30 40 50 60
110 1.95 70 80 90 100 110 130 150
130 2.16
150 2.38
Tabel -2 TRAFO DISTRIBUSI
KAPASITAS TRAFO = 160 KVA
LOAD FACTOR (%) LOSSES (%)
10 4,29
15 2,95
20 2,30
30 1,71
40 1,47
50 1,37
60 1,33
70 1,34
80 1,37
90 1,42
100 1,48
110 1,55
130 1,70
150 1,87

KAPASITAS TRAFO = 200 KVA

LOAD FACTOR (%) LOSSES (%)


10 4,12
15 2,83
20 2,22
30 1,66
40 1,43
50 1,33
60 1,31
70 1,32
80 1,35
90 1,40
100 1,47
110 1,54
130 1,69
150 1,86
Tabel – 3 TRAFO DISTRIBUSI

TABEL PEMBEBANAN TRAFO DISTRIBUSI TERHADAP SUSUT

SUSUT (%)
DAYA TRAFO PEMBEBANAN TRAFO
KVA 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 110%

25 4,91 2,70 2,08 1,84 1,77 1,78 1,83 1,91 2,00 2,12 2,24
50 4,90 2,68 2,05 1,81 1,72 1,72 1,76 1,83 1,92 2,02 2,13
100 4,90 2,68 2,05 1,81 1,72 1,72 1,76 1,83 1,92 2,02 2,13
160 4,08 2,22 1,68 1,47 1,39 1,38 1,41 1,46 1,53 1,60 1,69
200 3,92 2,14 1,63 1,43 1,36 1,36 1,39 1,44 1,51 1,59 1,67
250 3,92 2,13 1,61 1,41 1,34 1,33 1,35 1,40 1,46 1,54 1,62
315 3,99 2,17 1,65 1,45 1,37 1,36 1,39 1,44 1,51 1,58 1,67
400 3,79 2,06 1,56 1,36 1,29 1,28 1,30 1,35 1,41 1,48 1,56
500 3,59 1,95 1,48 1,30 1,23 1,22 1,24 1,28 1,34 1,41 1,48
630 3,37 1,83 1,39 1,22 1,15 1,14 1,16 1,20 1,26 1,32 1,39
800 3,57 1,95 1,48 1,30 1,24 1,24 1,26 1,31 1,37 1,44 1,52
1000 3,76 2,05 1,56 1,38 1,31 1,31 1,34 1,39 1,46 1,53 1,62
Tabel – 4 TRAFO DISTRIBUSI

SUSUT T RAFO DIST RIBUSI


PADA BEBAN 100% DAN COS q = 0.85
COS Q : 0,85
STANDAR RUGI SESUAI SPLN NO 50 TAHUN 1997
No DAYA RUGI BESI RUGI TEMBAGA (CU) LOSSES
(KVA) (KW) ( KW) %

1 25 0,075 0,425 2,12


2 50 0,150 0,800 2,02
3 100 0,300 1,600 2,02
4 160 0,400 2,000 1,60
5 200 0,480 2,500 1,59
6 250 0,600 3,000 1,54
7 315 0,770 3,900 1,58
8 400 0,930 4,600 1,48
9 500 1,100 5,500 1,41
10 630 1,300 6,500 1,32
11 800 1,750 9,100 1,44
12 1000 2,300 12,100 1,53

o
Catatan Suhu belitan Trafo Distribusi 75 C
Grafik – 1 PEMBEBANAN TRAFO
TERHADAP SUSUT

TRAFO 50 KVA
5,5
TRAFO 200 KVA
5,0

4,5
TRAFO 630 KVA
4,0
N ILA I SU SU T ( %)

3,5

3,0

2,5

2,0

1,5

1,0

10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 110%

PEMBEBANAN
Grafik – 2 PEMBEBANAN TRAFO
TERHADAP SUSUT

TRAFO 25 KVA
TRAFO 160 KVA
5,5

TRAFO 250 KVA


5,0

4,5

4,0
NILAI SUSUT (%)

3,5

3,0

2,5

2,0

1,5

1,0
10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 110%

PEMBEBANAN
Grafik – 3 PEMBEBANAN TRAFO
TERHADAP SUSUT

TRAFO 100 KVA

5,5 TRAFO 315 KVA


5,0
TRAFO 800 KVA
4,5

4,0
NILAI SUSUT (%)

3,5

3,0

2,5

2,0

1,5

1,0
10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 110%

PEMBEBANAN
Grafik – 4 PEMBEBANAN TRAFO
TERHADAP SUSUT

TRAFO 400 KVA


4,0
TRAFO 500 KVA

3,5 TRAFO 1000 KVA

3,0
NILAI SUSUT (%)

2,5

2,0

1,5

1,0
10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 110%

PEMBEBANAN
TRAFO CSP :
Trafo CSP adalah trafo yang dilengkapi pengaman sendiri, me-l
iputi pengaman arus lebih yang penempatannya didalam trafo
dan pada sisi primernya dipasang lightning arrester
TRAFO NON-CSP :

Trafo Non-CSP adalah trafo yang tidak dilengkapi penga-


man sendiri, tetapi sistem pengaman arus lebih ditempat-
kan diluar trafo sedangkan pada sisi primernya dipasang
lightning arrester serta dilengkapi panel tegangan rendah.

CSP = Completely Self Protection


Non CSP = Non Completely Self Protection
HUBUNGAN BELITAN TRAFO :

HUBUNGAN BINTANG [ Y ] :

Hubungan belitan yang disusun sedemikian rupa


sehingga salah satu ujung dari setiap belitan
transformator fasa-tiga, atau salah satu ujung
setiap belitan transformator fasa-tunggal yang
bertegangan pengenal sama dalam gugus
fasa-tiga, dihubungkan ke titik bersama ( titik
netral) dan ujung lainnya adalah terminal fasa.
Gambar Trafo Hubungan Bintang [ Y ] :
HUBUNGAN SEGITIGA [ Δ ] :

Hubungan belitan yang disusun sedemikian


rupa sehingga belitan – belitan fasa transfor-
mator fasa - tiga, atau belitan dari tiga unit
transformator fasa-tunggal yang bertegangan
pengenal sama dalam gugus fasa-tiga, dihu-
bungkan seri hingga membentuk sirkit tertutup.
Gambar Trafo Hubungan Segitiga [ Δ ] :
HUBUNGAN ZIGZAG [ Z ] :

Hubungan belitan yang disusun sedemikian


rupa sehingga salah satu ujung dari setiap
belitan fasa transformator fasa-tiga, dihu-
bungkan ke titik bersama (titik netral) dan
tiap belitan fasa terdiri dari dua bagian yang
tegangan induksinya berbeda fasa. Kedua
bagian ini mempunyai jumlah lilitan yang
sama.
Gambar Trafo Hubungan Zigzag [ Z ] :
HUBUNGAN
DAN
ANGKA LONCENG
TRAFO DISTRIBUSI
ANGKA LONCENG GTT 160 KVA [Yzn5] :

V
12 U V W
11 1
u
10 2
n
9 n 3 Hubungan Bintang
w (sisi Primer)

8 4
U v W U V W
7 5
6 Hubungan Zig-zag
(sisi Sekunder)
ANGKA LONCENG GTT 200 KVA [Dyn5] :
V
12 U V W U V W
11 1
n
10 2

w u n
9 3 Hubungan Delta Hubungan Bintang
v (sisi Primer) (sisi Sekunder)

8 4
U W
7 5
6
TERIMA KASIH