Sei sulla pagina 1di 11

Corrosion Rate Evaluation and Prediction for Piles Based

on Long-Term Field Performance


Jeramy B. Decker1; Kyle M. Rollins2; and Jared C. Ellsworth3

Abstract: A study to evaluate corrosion rates was conducted using pile foundations abandoned during the reconstruction of I-15 through
Salt Lake Valley, Utah. Corrosion rates were measured for 20 piles extracted from five sites after service lives of 34–38 years. Measure-
ments were made of soil index properties, resistivity, pH, cation/anion concentrations, and water table elevation. The critical zone for
corrosion was typically located within the groundwater fluctuation zone; but correlations with soil properties were generally poor. Despite
low resistivity, average corrosion rates for pile caps in native soil were typically between 2 and 9 ␮m / year with a maximum of
19 ␮m / year and did not pose any structural integrity problems. Nevertheless, for abutment piles where chloride concentration was very
high, the average pile corrosion rate increased to 13 ␮m / year within the embankment and the maximum corrosion rate was 48 ␮m / year
in the underlying native soil. Based on data from this and previous studies, equations were developed to predict maximum corrosion loss
for piles in nonaggressive soil as a function of time.
DOI: 10.1061/共ASCE兲1090-0241共2008兲134:3共341兲
CE Database subject headings: Corrosion; Driven piles; Infrastructure; Chlorides; Sulfates; Predictions.

Introduction to be more severe in moist fine-grained soils with low resistivity


共⬍1,000– 3,000 ⍀ cm兲 and extreme pH 共⬍5 or ⬎10.5兲 共Peabody
Corrosion of steel pile foundations may result in reduced capacity 1967兲. Roberge 共2000兲 categorizes potential soil corrosivity based
in axial and lateral loading. Therefore, an understanding of the on soil resistivity as summarized in Table 1. Elias and Christopher
potential for pile corrosion is essential such that excessive deflec- 共1997兲 identified high concentrations of sulfates 共⬎200 pm兲 and
tion and failure may be avoided. Because piles are installed un- chlorides 共⬎100 ppm兲 as being indicative of corrosive soil in
Federal Highway Administration 共FHwA兲 guidelines for me-
derground and are not easily inspected, pile corrosion is a difficult
chanically stabilized earth 共MSE兲 wall fill.
problem to monitor or to remedy once the pile is in place. How-
Research indicates the water table fluctuation zone is generally
ever, if the thickness loss during the design life can be reasonably
the zone in which the greatest corrosion occurs on piles because
estimated, additional wall thickness may be added as sacrificial
both oxygen and moisture are necessary for corrosion. Below the
steel to account for the potential loss. Additionally, the cost- water table the oxygen content decreases and drastically reduces
effectiveness of noncorrosive pile materials can be more accu- corrosion 共Elias and Christopher 1997; Picozzi et al. 1993兲.
rately evaluated. Most research previously performed on metal corrosion in soil
The corrosion of metals is a process of electrochemical cell has focused on the degradation of buried pipelines or tanks. How-
corrosion with the soil and pore fluid acting as an electrolyte, ever, available data suggest that the potential for pile corrosion
while the metal acts as the anode at one location and the cathode may be significantly less than for buried pipelines and that the
at another location due to variations in soil conditions along the rate of pile corrosion may not be influenced by the same factors
metal surface. Metal is consumed at the anode, where current that govern corrosion of buried pipelines 共Romanoff 1962; Escal-
leaves to enter the surrounding electrolyte. At the anode, electrons ante 1992; Manning and Morley 1981; Ohsaki 1982; Tungesvik
are lost and positively charged iron atoms combine with OH− ions et al. 1975; Wong and Law 1999兲. Pipelines are usually installed
to form ferrous hydroxide and ferric hydroxide, commonly known in an open trench and backfilled, resulting in a highly disturbed
as rust. In general, the potential for metallic corrosion is thought and oxygenated soil environment conducive to corrosion. In con-
trast, driven piles are installed such that the surrounding soil re-
1
Tunnel Engineer, Kiewit Underground, 930 Oddstad Blvd., Pacifica, mains relatively undisturbed, with little free oxygen or change in
CA 94044. E-mail: jeramy.decker@kiewit.com
2
Professor, Civil and Environmental Engineering Dept., Brigham
Young Univ., 368 CB, Provo, UT 84602. E-mail: rollinsk@byu.edu Table 1. Corrosion Severity Ratings Based on Resistivity 共Roberge
3
Project Engineer, Williams Northwest Pipline, Inc., 295 Chipeta 2000兲
Way, Salt Lake City, UT 84108. E-mail: jared.ellsworth@williams.com Soil resistivity 共⍀ cm兲 Corrosivity rating
Note. Discussion open until August 1, 2008. Separate discussions
must be submitted for individual papers. To extend the closing date by ⬎20,000 Essentially noncorrosive
one month, a written request must be filed with the ASCE Managing 10,000–20,000 Mildly corrosive
Editor. The manuscript for this paper was submitted for review and pos- 5,000–10,000 Moderately corrosive
sible publication on August 24, 2006; approved on May 21, 2007. This 3,000–5000 Corrosive
paper is part of the Journal of Geotechnical and Geoenvironmental 1,000-3,000 Highly corrosive
Engineering, Vol. 134, No. 3, March 1, 2008. ©ASCE, ISSN 1090-0241/
⬍1,000 Extremely corrosive
2008/3-341–351/$25.00.

JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008 / 341


corrosion were evaluated: soil classification, Atterberg limits, re-
sistivity 共using CPT, laboratory, and Wenner array methods兲, pH,
cation/anion concentrations, and water table elevations. Finally, a
number of tensile load tests were performed on sections of the
piles to determine how capacity was affected by section loss. Full
details of the study are provided elsewhere 共Decker and Rollins
2001; Ellsworth 2004兲.
Measured corrosion was then analyzed in three ways. First, the
corrosion that took place at each site relative to soil and water
conditions was evaluated. Second, efforts were concentrated on
correlations between corrosion rate and soil parameters for all the
Salt Lake data with a focus on the water table fluctuation zone.
Fig. 1. Extracted pile being pulled from pit at 6th South, Salt Lake Finally, data from this and previous studies was used to develop
City, Utah correlations between maximum corrosion rate and exposure time.

the soil structure. Whereas most pile corrosion studies have fo- Corrosion Behavior at Individual Sites
cused on steel piles in undisturbed soil, piles are often driven
through fills where corrosion conditions might be similar to those 2100 South
for pipelines.
Currently, there is no widely accepted method of predicting The soil profile at 2100 South consists of interbedded layers of
pile corrosion in the United States and pile corrosion is often silt and clay with occasional sand layers as shown in Fig. 2. The
ignored in practice. Nevertheless, recent research indicates that a water table elevation was above the base of the pile cap at this
failure to account for pile corrosion may lead to unsafe conditions location. The chloride and sulfate content were both above the
if piles are located in fills containing slags, ash, cinders, or salt FHwA boundary for corrosive soil 共Elias and Christopher 1997兲
contamination 共Greene et al. 1995; Beavers and Durr 1998兲. and the resistivity was generally below 1,000 ⍀ cm. This criteria
Therefore, additional research is needed to provide a better un- places the soil in the extremely corrosive category 共see Table 1兲.
derstanding of pile corrosion and to predict when corrosion may Three pipe piles 共Piles 1–3兲 were extracted from a pile cap at this
pose a threat to the long-term integrity of a structure. As no pre- site. These steel pipe piles were 305 mm 共12 in.兲 in diameter,
vious research had been conducted on the corrosion of piles in the 4.90 mm 共0.19 in.兲 thick, and were filled with concrete with rein-
Salt Lake Valley, this study was also undertaken to provide some forcement limited to the top meter. These piles were obtained
basic information relating to pile performance and longevity for after being exposed to the soil-water environment for 36 years.
the soil conditions. The measured average corrosion rate is plotted for each pile as
a function of depth in Fig. 2. The corrosion rates are relatively
constant with depth. Despite the low resistivity and the high chlo-
Scope and Test Procedures ride and sulfate concentrations, the maximum measured corrosion
rate for Piles 1–3 was only 6 ␮m / year on Pile 3 at a depth of
During the reconstruction of Interstate 15 through the Salt Lake 2.59 m 共8.50 ft兲 below the pile cap. The average corrosion rate
Valley, essentially all of the original 30 to 40 year old pile foun- for the three piles was just 2.43 ␮m / year with a standard devia-
dations used for the original construction were abandoned. This tion of 1.39 ␮m / year. The corrosion rates for these piles are
presented an opportunity to extract a sampling of old piles from within the mild range, with a maximum section loss of 4% and an
different sites, to measure corrosion rates, and to correlate corro- average loss of 2% 共refer to Table 2兲 after 36 years of soil
sion rates with soil properties using new and previously published embedment.
data. With the water table elevation 0.94 m 共3.08 ft兲 above the bot-
Based on findings from previous research, the majority of this tom of the pile cap these piles were primarily beneath the water
study focused on the ground water fluctuation zone. As shown in table fluctuation zone, which may explain the low and relatively
Fig. 1, sections from 20 piles that penetrated the groundwater constant corrosion rates. The high water table along with the fine
fluctuation zone at five locations were extracted in 2 – 6 m grained soils at the top of the profile likely prevented aeration and
lengths. At four of the locations the piles were driven in natural contributed to low corrosion rates. As a result, the soil parameters
soils with little fill; however, at a fifth site the piles extended did not significantly influence corrosion rate. For example, the
through a 5 m thick approach fill and into natural materials. cone penetration test 共CPT兲 resistivity dropped from a very high
Thickness loss was measured in 0.3 m segments along the length value of around 1 ⫻ 106 ⍀ cm to a low value of about 1,000 ⍀ cm
of each pile after cleaning and sandblasting the surface. Average at about 0.5 m, but this discontinuity did not affect the corrosion
corrosion rates were then defined as the total thickness loss di- rate.
vided by the years since placement. Corrosion thickness loss was
classified as follows: 0–10% as mild, 10–20% as moderate, and
greater than 20% as severe. These values are based on the fact South Temple
that a 25% section loss is generally considered very serious
共Picozzi et al. 1993兲. For a typical 1960-era I-15 pile thickness The soil profile at the South Temple site consists of interbedded
共4.76 mm or 3 / 16 in.兲 with a 36 year exposure time, this equates layers of silt and clay with one sand layer as shown in Fig. 3. The
to corrosion rates of 0–13, 13–26, and greater than 26 ␮m / year water table was about 0.9 m below the base of the pile cap and
for the mild, moderate, and severe categories, respectively. the estimated zone of water table fluctuation is shown on the soil
In addition, the following soil parameters thought to influence profile. As indicated previously, moist fine-grained soils are be-

342 / JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008


Fig. 2. Soil profile and measured soil parameters versus depth along with corrosion rates for 2100 South test site 共groundwater is above the top
of the piles兲

lieved to be more susceptible to corrosion. Four 305 mm 共12 in.兲 piles are referred to as Piles 7–10. These piles were exposed to
diameter spiral-welded steel pipe piles originally installed to sup- the soil-water environment for 38 years prior to extraction.
port a bridge bent in 1962 were extracted from this location. The In addition to the soil profile, Fig. 3 provides plots of the
steel pipe piles were 4.76 mm 共3 / 16 in.兲 thick and filled with measured soil parameters related to corrosion as a function of
concrete with reinforcement limited to the top meter. These four depth. The low resistivity values from the Wenner and laboratory

Table 2. Summary of Maximum Corrosion Rate, Length of Exposure, and Soil Properties from This and Other Previous Studies
Corrosion rate Years Resistivity Chloride
共␮m / year兲 exposed pH 共⍀ cm兲 共ppm兲 Source
18 22 5.1–6.0 50,000–70,000 16–59 Wong and Law 1999
30 20 Not given Not given Not given Manning and Morley 1981
15 12 Not given Not given Not given Manning and Morley 1981
30 46 Not given Not given Not given Manning and Morley 1981
58.9 6.8 Not given Not given Not given Escalante 1992
25.6 6.8 7 1,170 Not given Escalante 1992
12.9 12.9 7.7 2,080 Not given Escalante 1992
43.6 2.8 7 1,170 Not given Escalante 1992
47.8 2.8 7.2 455 Not given Escalante 1992
37.8 6.8 7.4 710 Not given Escalante 1992
16.5 12.9 7.4 710 Not given Escalante 1992
17.5 2.8 Not given Not given Not given Escalante 1992
14 12.9 Not given Not given Not given Escalante 1992
58 4.5 Not given Not given Not given Ohsaki 1982
47.6 7 7.4–8.2 850–7,000 0.3 Romanoff 1962
20.7 23 Not given Not given Not given Romanoff 1962
82.3 11 6.9 4,300–11,000 0.6 Romanoff 1962
47.6 11 8.1 800–1,290 0.5 Romanoff 1962
34.6 11 Not given 950–1,610 0 Romanoff 1962
15.9 12 7.7–8.4 345–1,300 0.5 Romanoff 1962
19 34 8.2 300,000 17.8 This study
13.3 35 7.7 150,000 256 This study
15.3 38 7.5 150,000 444 This study

JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008 / 343


Fig. 3. Soil profile and measured soil parameters versus depth along with corrosion rates for South Temple site

tests fall in the highly corrosive range 共see Table 1兲, although the water table, which suggest petroleum contamination in the
CPT resistivity values are much higher below the water table. In groundwater was likely acting as an insulator. The laboratory
addition, the chloride and sulfate concentrations far exceed the measurements did not indicate high resistivity in these clays, but
limits for mildly corrosive soil identified by Elias and Christopher they were performed several months after the samples were taken
共1997兲 for MSE walls. In addition, the pH is quite high near the from the ground and the contaminants may have volatilized. As
surface. Under these conditions high corrosion rates would gen- shown in the photograph in Fig. 4, the piles also had small soft
erally be expected for buried metals. Nevertheless, the measured black deposits in the corrosion pits, which are a characteristic
corrosion rates are generally less than the 12 ␮m / year value feature of attack by SRBs 共Videla 1996兲. Another possible indi-
suggested by Elias and Christopher when designing metallic re- cation of biocorrosion was evidenced by the many pile sections
inforcement strips for MSE walls with chloride and sulfate con- that exhibited noticeable corrosion with a shiny silver appearance,
centrations below the limits. The maximum measured corrosion which rusted over within days after being sand blasted.
rate for Piles 7–10 was 15 ␮m / year on Pile 9 at a depth of 1.37 m
共4.49 ft兲. The average corrosion rate was 6.32 ␮m / year with a
2nd South
standard deviation of 4.13 ␮m / year. The corrosion rates for these
piles were moderate to mild with a maximum section loss of 12% The soil profile at 2nd South consisted entirely of sand, as shown
and an average loss of 5% 共refer to Table 2兲. The presence of the in Fig. 5. Three 305 mm 共12 in.兲 diameter corrugated steel piles
water table fluctuation zone appears to be the greatest factor con- were extracted from a pile cap at this site. The corrugated steel
tributing to the maximum corrosion rate, as the highest values
occur within this zone.
The corrosion rates drop off somewhat below the maximum
value; however, they do not decrease significantly with depth
below the water table as would be expected. One possible reason
for this discrepancy might be that the water table fluctuation zone
was larger than estimated. However, further investigation pro-
vided strong evidence that biocorrosion is the cause of the higher
corrosion rates at depth below the water table. Biocorrosion is
typically caused by sulfate reducing bacteria 共SRBs兲 which are
commonly associated with saturated clays, a pH value near neu-
tral and anaerobic conditions. SRBs also thrive where contami-
nants provide nutrients for bacterial growth and contribute to
anaerobic conditions 共Videla 1996兲.
The South Temple site was located in a heavy industrial area
near a railroad yard, suggesting that it was a high risk area for Fig. 4. Steel section from Pile 8 extracted at South Temple site
contamination. The CPT soundings at South Temple also mea- showing soft black material in corrosion pits typical of biocorrosion
sured abnormally high resistivity values in the clays below the from sulfate reducing bacteria

344 / JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008


Fig. 5. Soil profile and measured soil parameters versus depth along with corrosion rates for 2nd South site

pipe was 1.66 mm 共0.065 in.兲 thick and filled with reinforced piles from 2100 South and South Temple, then the maximum
concrete. Due to the sandy profile and high water table at this section loss would be 10% and the average would be 5%. These
location, the excavation required to remove these piles could only section losses values would range from moderate to mild.
be extended to a depth of about 1.8 m 共6 ft兲 before the saturated
sand collapsed into the excavation. These piles were obtained
6th South
after 35 years of exposure to the soil-water environment. These
piles are referred to as Piles 11–13. The soil profile at 6th South consisted of a wide variety of soil
Fig. 5 presents the soil profile, soil parameters, and measured types ranging from high plasticity clays to well-graded sands as
corrosion rates as a function of depth for this site. The corrosion illustrated in Fig. 6. Four corrugated steel piles were extracted
rate does not appear to be strongly correlated with any of the from a pile cap at the site. The piles were filled with reinforced
parameters illustrated in Fig. 5 and the corrosion rates remain low concrete and step-tapered with depth. The first 1.09 m 共3.58 ft兲 of
even though chloride and sulfate concentrations are high. The the piles was 457 mm 共18 in.兲 in diameter, the next 3.71 m
corrosion rate peaks just above the existing water table in the 共12.17 ft兲 was 406 mm 共16 in.兲 in diameter, and the last segment
water table fluctuation zone, which seems to be the strongest fac- of the extracted length was 356 mm 共14 in.兲 in diameter. The
tor influencing the corrosion rate. The maximum measured corro- corrugated steel shell segments ranged in thickness from 1.14 to
sion rate for Piles 11–13 was 13 ␮m / year on Pile 11 at a depth of 1.40 mm 共0.045 to 0.055 in.兲. The piles were obtained after 34
0.67 m 共2.20 ft兲. The minimum was 2 ␮m / year on Pile 12 at a years of exposure to the soil-water environment. These piles are
depth of 0.30 m 共0.98 ft兲. The average corrosion rate was referred to as Piles 15–18. Pile 17 was not measure due to its
6.02 ␮m / year with a standard deviation of 2.67 ␮m / year. The short length, abundant extraction wounds, and time constraints.
average corrosion rate is very close to the average corrosion rate Along with the soil profile, Fig. 6 presents the soil parameters
measured for South Temple 共6.32 ␮m / year兲, even though this site and the measured corrosion rates as a function of depth. The
had predominately granular soils and South Temple had predomi- maximum measured corrosion rate for Piles 15–18 was
nately fine grained soils. However, the standard deviation is much 19 ␮m / year on Pile 15 at a depth of 0.48 m 共1.57 ft兲. The mini-
smaller than at South Temple 共4.13 ␮m / year兲. The corrosion in- mum was 1 ␮m / year on Pile 16 at a depth of 3.33 m 共10.93 ft兲.
creases with depth and peaks within the water table fluctuation The average corrosion rate was 5.10 ␮m / year with a standard
zone just above the average water table depth. Below the water deviation of 3.07 ␮m / year. The corrosion rates for these piles are
table depth, the corrosion drops back down and stabilizes at about severe to moderate with respect to percent of section loss, with a
5 ␮m / year. maximum of 51% and an average of 14% 共refer to Table 2兲.
The corrosion rates for these piles are severe to moderate with However, the pile wall was only 1.14– 1.40 mm 共0.045–
respect to the percent of section loss, with a maximum section 0.055 in.兲 thick and like the piles at 2nd South these piles were
loss of 29% and an average of 13% 共refer to Table 2兲. However, most likely used just as casing for reinforced concrete. If the piles
the pile section was only 1.66 mm 共0.065 in.兲 thick and was most had been 4.76 mm 共3 / 16 in.兲 structural piles, the maximum sec-
likely used only as casing for the reinforced concrete. If these tion loss would have been 14%, with an average of only 4%. This
piles were typical structural piles having a thickness of 4.76 mm severity of section loss would range from moderate to mild.
共3 / 16 in.兲 and were used more for structural support, as were the The maximum corrosion rate on Piles 15 and 16 occurred

JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008 / 345


Fig. 6. Soil profile and measured soil parameters versus depth along with corrosion rates for 6th South site

0.20 m 共0.67 ft兲 below the interface between the top layer of clay As a result of drought conditions the preceding 4 years, the water
and the underlying sand 共Pile 18 did not experience the same table elevation was likely close to the lower boundary of water
corrosive attack at this depth兲. As shown in Fig. 7共a兲, the corro- table fluctuation zone.
sion at this depth penetrated the thin corrugated steel piles. This Two steel pipe piles 共Piles 19 and 20兲 were extracted at
layer was 0.70 m 共2.30 ft兲 above the water table fluctuation zone. this site. The steel pipe piles were 318 mm 共12.5 in.兲 in dia-
It is possible that this elevated corrosion rate is due to a difference meter, 6.3 mm 共0.25 in.兲 thick, and were filled with concrete
of electrical potential between the clay and the sand or simply 共⬇28 MPa兲 with reinforcement limited to the top meter. These
localized water infiltration. Several factors may have lead to a
piles, which were driven at a 1:4 batter, were obtained after 37
difference in electric potential and the creation of a corrosion
years exposure to the soil-water environment.
“macrocell.” First, the moisture content in the clay layer was
Within the fill, the average corrosion rate for Piles 19 and 20
relatively high at around 40%, whereas the sand was low at
around 10%. The soil types were also very different, with one was only about 13 ␮m / year with a standard deviation of 2.1,
layer being high plasticity clay and the other nonplastic sand. despite the fact that the resistivity was less than 500 ⍀ cm, the
Next, there were noticeable differences in chemical properties chloride concentration averaged approximately 2,100 ppm, and
from the clay to the sand, such as pH, sulfate content, sulfate the soil consisted of moist silty clay. The high chloride content is
absorption rate, and potassium content. Lastly, there was a large likely a result of deicing salt used heavily on the pavement during
difference in resistivity as measured by the laboratory resistivity winter months.
test. Resistivity in the sand was 18 times greater than that for the The corrosion rate increased significantly in the native soil
clay. as the zone of water table fluctuation was approached. The maxi-
There is another peak in corrosion rate within the water table mum corrosion rates for Piles 19 and 20 were 48 and
fluctuation zone. This peak is comparable to the corrosion rates 38 ␮m / year, respectively. The average corrosion rate in the na-
found at the other sites investigated during this study. The corro- tive soil at this site was 22.3 ␮m / year with a standard deviation
sion rate decreases with depth below the water table despite the of 13.8. A photograph showing the corrosion of a section of pile
fact that sulfate concentration increases and resistivity values re- at 118th South is provided in Fig. 7共b兲.
main at the same, relatively low values and sulfate concentration
Visual observations indicated that there was substantial differ-
increases
ence in the corrosion rates on opposite faces of the battered piles.
Therefore, separate corrosion measurements were made on both
118th South sides of the piles and then averaged to obtain the value at each
The piles at the abutment for the 118th South overpass on I-15 depth shown in Fig. 8. For example, at the base of Pile 19 the
were installed through 5 m of silty clay embankment fill before corrosion rate on one side was 77 ␮m / year, whereas that on the
extending into the native clay soil at the site. The soil profile and opposite side was only 19 ␮m / year resulting in an average of
soil properties as a function of depth are presented in Fig. 8. The 48 ␮m / year.
water table was located at about 2.6 m below the natural ground For the 6.3 mm wall thickness, these corrosion rates for these
surface or 7.6 m below the top of the fill at the time of extraction. piles were moderate to severe with an average section loss of

346 / JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008


much greater than the percent section loss. However, Tungesvik
et al. 共1975兲 performed compression tests which are difficult to
directly compare with our tension test results because compres-
sion can be controlled by buckling.

Evaluation of Results

Typical Corrosion Expected in Salt Lake Valley Soils

The average corrosion rates for piles below pile caps driven into
native soil were between 2 and 9 ␮m / year with a maximum of
19 ␮m / year. The percent thickness loss for a pile with a 9.53 mm
共3 / 8 in.兲 wall thickness typically used in the Utah Department of
Transportation practice today would be between 1 and 4% with a
maximum of 7% for exposure times of 34–38 years. For future
projects in the Salt Lake Valley, with soil conditions similar to the
soils at these sites, designs should allow for a maximum thickness
loss of about 7% for piles in the water table fluctuation zone for a
35 year design life.
For the abutment piles driven through the approach fill at
118th South, the average corrosion rate was about 13 ␮m / year in
the fill with a maximum of 48 ␮m / year near the groundwater in
the underlying native soil. For a 9.5 mm pile wall thickness, this
corresponds to an average thickness loss of 5% in the fill and a
maximum loss of 18.6% in the native soil for a 37-year design
life. The cause of these elevated corrosion rates appears to be
deicing salts which produced average chloride concentrations of
1,600 ppm, 16 times higher than the accepted limit for MSE wall
reinforcements, along with resistivity values of only 600 ⍀ cm.
These factors led to higher corrosion rates particularly in the
water table fluctuation zone. These high corrosion rates are a
serious concern and demonstrate the need to either design for
these rates at approach fills where deicing salts will be used or to
take measures to prevent salt infiltration.

Location of Corrosion
The maximum corrosion rate at each site typically occurred
within the water table fluctuation zone, with the exception of 6th
Fig. 7. Photographs of 共a兲 corrugated steel casing at South Temple South where the maximum rate occurred above the ground water
site; 共b兲 steel pipe pile as 118th South site table zone. The corrosion rate tended to drop off below the water
table fluctuation zone except at South Temple where biocorrosion
appeared to take place below the water table.
about 8% in the fill material, 13% in the native soil, and a maxi-
mum section loss of 28% near the water table fluctuation zone. Methods for Predicting Corrosion

Existing Methods
Thickness Loss versus Tensile Capacity Loss
We evaluated several methods used to predict corrosion rates or
the potential for corrosion of buried steel. These methods in-
Axial tension tests were conducted on 12 specimens of piles that
were 203.2 mm 共8 in.兲 long and 25.4 mm 共1 in.兲 wide. These cluded the steel pipe corrosion classification method based on
specimens had measured thickness losses between 5 and 29%. resistivity 共Palmer 1967兲, the FHwA criteria for MSE reinforce-
The tension tests indicated that the loss of tensile capacity was ments 共Elias and Christopher 1997兲, and the National Institute of
directly related to the loss of thickness. The average thickness Standards and Technology 共NIST兲 共American Iron and Steel In-
loss for the specimens was 13.3%, whereas the average loss in stitute 1994兲 method for buried culverts. All three of these meth-
tensile load capacity was 10.7%. These results suggest that per- ods proved to be inadequate for predicting pile corrosion. The
cent loss in tensile capacity is essentially the same as the percent methods generally tended to be overly conservative. For example,
section loss. These results are in agreement with most studies; the measured corrosion rates were typically only 33–67% of those
however, they contrast with compression test results presented by predicted using the NIST method with resistivity obtained from
Tungesvik et al. 共1975兲 in which the percent strength loss was lab tests.

JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008 / 347


Fig. 8. Soil profile and measured soil parameters versus depth along with corrosion rates for 118th South site

Correlations Based on Soil Parameters


To improve the prediction of corrosion rates for driven steel piles,
single variable and multiple variable correlation equations were
developed with regression techniques using the data collected
from the sites in the Salt Lake Valley. Soil parameters predicted
corrosion better in the water table fluctuation zone where corro-
sion was not limited by a lack of oxygen or a lack of moisture.
For example, the correlation between corrosion rate and chloride
concentration had an r2 value of 0.43 within the water table fluc-
tuation zone with a general trend of higher corrosion rates with
higher concentrations of chloride 共see Fig. 9兲. However, after in-
cluding data along the full pile length, the r2 value dropped to
only 0.22. Correlations were also developed between corrosion
rate and resistivity in the water fluctuation zone. The correlation

Fig. 9. Relationship between corrosion rate and chloride Fig. 10. Relationship between corrosion rate and 共a兲 laboratory
concentration for data in the water table fluctuation zone from Salt resistivity; or 共b兲 CPT resistivity in the water table fluctuation zone
Lake Valley data set based on Salt Lake Valley data

348 / JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008


equations relative to CPT and lab resistivity measurements only
had r2 values of 0.39 and 0.22, respectively, but did show a gen-
eral trend of higher corrosion rates as the soil resistivity decreased
as shown in Fig. 10. There were no CPT resistivity measurements
taken at 118th South, therefore, the CPT and lab resistivity cor-
relations cannot be adequately compared.
Multivariable regression models were developed using the
data within the water table fluctuation zone. In developing these
models, the lab resistivity data were used because CPT resistivity
data were not available for 118th South. The first model was
developed strictly by determining the best statistical fit with
measured parameters and included laboratory resistivity, total dis-
solved solids, hydrogen carbonate concentration, sulfate concen-
tration, ammonium concentration, and sodium concentration. The
corrosion rate 共CR兲 in ␮m / year is given by
Fig. 11. Corrosion rate versus exposure time for data from this and
CR = − 4.58 ln共␳Lab兲 + 35.61 ln共TDS兲 + 13.87 ln共HCO3兲 previous studies listed in Table 2

− 17.97 ln共SO4兲 + 9.12 ln共NH4兲 − 0.06 Na − 198.08 共1兲


Correlation Based on Exposure Time for Mildly Corrosive
where ␳Lab⫽resistivity in ⍀ cm and concentrations are given in Soil
parts per million. Eq. 共1兲 and had an r2 value of 0.91. A regression Previous research indicates that the corrosion rate for metals in
equation, using the same parameters as Eq. 共1兲, was also devel- soil decreases with time, due to the depletion of oxygen and the
oped using all the data above and below the groundwater fluctua- build-up of corrosion products that form a protective layer
tion zone. Using all the data, the r2 value decreased from 0.91 to 共Ohsaki 1982; Schlosser and Bastick 1991兲. Because the corro-
0.53 and a few of the parameters 共laboratory resistivity, hydrogen sion rate for piles does not appear to be strongly influenced by
carbonate concentration, and ammonium concentration兲 became soil parameters within typical ranges, it may be possible to esti-
statistically insignificant. mate the maximum corrosion rate at a site based only on the
Although a better correlation was found within the groundwa- exposure time for many practical design purposes. To evaluate the
ter fluctuation zone, the model is not likely to be a viable method decrease in corrosion rate with time, we plotted thickness loss
for predicting corrosion for three reasons. First, the data are lim- versus exposure time using data in the literature along with data
ited and some of the parameters used had small ranges. Second, from this study. We excluded data points for piles located entirely
some of the variables in the regression model do not agree with below the water table because their maximum corrosion rates
basic physical principles governing corrosion. For example, the were generally much lower. In addition, we excluded data for less
corrosion rate should increase with higher concentrations of so- common, highly aggressive soil conditions such as noted by vari-
dium, but the model actually shows the corrosion rate decreasing ous researchers 共Greene et al. 1995; Beavers and Durr 1998兲.
as sodium concentration increases. Third, basic parameters such Specifically, we excluded any measurements with a pH less than
as pH and chloride concentration are not included in the model. or equal to 5 or greater than 8.5, a resistivity lower than
A second regression model was attempted considering only 340 ⍀ cm, or a chloride concentration greater than 450 ppm.
parameters thought to have a significant effect on corrosion, based These criteria excluded the piles at the 118th South site be-
on previous studies, such as chloride concentration and resistivity. cause of the high measured chloride concentration. They also ex-
Although pH is considered an important parameter, the data set cluded several cases in the literature where corrosion rates were
did not have a large range of pH values and the data correlated much higher than typical values for piles and either the pH or the
poorly, therefore, pH was not used for this regression model. chloride concentration were more extreme 共Elias and Christopher
Using this approach, the regression equation 1997, Beavers and Durr 1998兲. We set the above-mentioned cri-
teria using the extreme measurement of each parameter in the
CR = − 1.6997 ln共␳Lab兲 + 14.92 ln共Cl兲 − 63.27 共2兲 data we used. It is possible that these criteria may be overly
conservative, but there is presently insufficient conclusive data to
where ␳Lab⫽resistivity in ⍀ cm and chloride concentrations are change the criteria. Data points were kept in the model when pH,
given in parts per million. This equation has an r2 value of 0.38. resistivity, or chloride concentration measurements were not all
Like the first model, the regression model given by Eq. 共2兲 specified because this was considered conservative.
does not provide a reliable method to predict corrosion rates. Table 2 shows the data points used in the analysis along with
First, the r2 value was fairly low demonstrating that the fit was the corrosion rate, soil parameters, and source for the data. The
not good. Next, the t-stat for the lab resistivity parameter was low thickness loss is defined as the loss of thickness from one side of
共−0.4兲, indicating that this parameter is likely not statistical sig- metal; therefore, H-piles will actually have twice the thickness
nificant. This low t-stat is reasonable as the lab resistivity param- loss since they have two exposed sides. The data set consists of
eter had a low r2 value. 23 points and the time of exposure ranges from 2 to 46 years.
Therefore, efforts to predict corrosion rates based on soil pa- Each data point represents the maximum corrosion rate measured
rameters were not successful in this study. This result is consistent for any test specimen at a given site. Therefore, there are only
with previous studies which found that pile corrosion was not three data points from the Salt Lake Valley testing. The Salt Lake
strongly related to soil parameters. A reliable regression model data points, while only a small portion of the entire data set, have
approach must await additional data from other sites with a wider some of the longest exposure times 共34–38 years兲 of any data in
range of values for the various parameters. the set.

JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008 / 349


Fig. 12. Total thickness loss from corrosion versus exposure time for
data from this and previous studies listed in Table 2

Fig. 11 presents the corrosion rate versus exposure time on an


arithmetic scale and demonstrates the decrease in corrosion rate
over time. Fig. 12 presents the maximum thickness loss as a func- Fig. 13. Example using Eq. 共4兲 to estimate the maximum pile
tion of exposure time on a log-log plot. The average trend line is thickness loss over the expected design life and the time to 25%
shown in Fig. 12 along with lines representing the 68% confi- thickness loss
dence interval and the 95% confidence interval. Eqs. 共3兲–共5兲 are
derived from the data in Fig. 12. The average thickness loss in
Fig. 12 is given by There are several precautions in using Eqs. 共3兲–共5兲. First, the
⌬e = 59t 0.67
共3兲 data only have measured values up to 46 years of exposure. Be-
yond this time span there are no data to verify that the equations
where ⌬e⫽thickness loss due to corrosion and t⫽exposure time are appropriate. However, the design life of many buried struc-
in years. This best-fit line has an r2 value of 0.55. Eqs. 共4兲 and 共5兲 tures will be within 50 years so that extrapolation beyond the
provide the maximum thickness loss for the 68 and 95% confi- range of the data set will not be required. As indicated previously,
dence interval upper limits, respectively if the soil has a pH less than or equal to 5 or greater than 8.5, a
resistivity of less than 340 ⍀ cm, or a chloride concentration
⌬e = 83t0.81 共4兲
greater than 450 ppm, corrosion rates may be significantly higher
than predicted by Eqs. 共4兲–共6兲. The equations also may not be
⌬e = 120t0.95 共5兲
adequate for piles driven in fills containing slags, ashes, cinders,
The exponents in Eqs. 共3兲–共5兲 represent the slope of the lines and heavily polluted soils that have high cation/anion
on the log-log plot whereas the coefficient is the intercept or the concentration 共besides chloride concentration兲 or severe anaerobic
thickness loss in micrometers at 1 year of exposure. The average conditions.
line has an exponent of 0.67, which compares favorably with that
suggested by previous investigators. For example, Romanoff
共1962兲 recommended an exponent of 0.55 for metals in the Findings and Conclusions
ground whereas Schlosser and Bastick 共1991兲 proposed an expo-
nent of 0.65 for galvanized steel.
The plot in Fig. 12 indicates that all the measured data lie 1. The water table fluctuation zone was generally the critical
within the 95% confidence interval, or within 2 SD from the zone for corrosion. The corrosion rate along the length of the
mean. All but four data points lie within the 68% confidence piles was controlled more by location relative to the water
interval, or within 1 SD from the mean. There are only two data table than any other individual soil parameter. The peaks in
points that plot above the upper limit of the 68% confidence level corrosion rate were generally near the measured ground
bound. For design purposes, we recommend that the maximum water table.
corrosion rate be estimated using the upper limit of the 68% con- 2. In most cases, the corrosion rate below the water table fluc-
fidence interval 关Eq. 共4兲兴. The upper limit of the 68% confidence tuation zone decreased significantly as oxygen was depleted.
interval is greater than about 82% of the data. Fig. 13 provides an However, at the South Temple site, the corrosion rate re-
example of how Eq. 共4兲 can be used in design to estimate the mained relatively high below the water table. Evidence
maximum percent loss of thickness over the life expectancy of a strongly suggests that this anomaly is a result of biocorro-
pile. Eqs. 共3兲–共5兲 were all derived from maximum corrosion rates. sion; however, greater variation in the groundwater level
Therefore, if the equation for the upper limit of the 95% confi- could also be a factor.
dence interval is used, the computed change of thickness could be 3. Soil interfaces above the water table may produce corrosion
well above any maximum measured value. This may be too con- when potential differences create macrocells. Macrocells
servative and costly. produced by two adjacent soils with large differences in re-

350 / JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008


sistivity, pH, natural moisture content, aeration, and cation/ edged. The opinions and conclusions expressed in this paper are
anion concentration may, in some cases, be the critical depth those of the writers and do not necessarily reflect the views of
for corrosion, instead of the water table fluctuation zone. UDOT. We also thank Penhall, Inc. for extracting the piles and
4. The maximum measured corrosion rates for piles within pile Samuel Musser at UDOT who served as the project manager for
caps driven in native soils 共2100 South, South Temple, 2nd this study.
South, and 6th South兲 in Salt Lake City were not a serious
threat to the structural integrity of any pile foundations, even
after 34–38 years of exposure. The average corrosion rates References
were between 2 and 9 ␮m / year with a maximum corrosion
rate of 19 ␮m / year. The average percent loss of thickness of American Iron and Steel Institute. 共1994兲. Handbook of steel drainage
a driven pipe pile with a 9.53 mm 共3 / 8 in.兲 thick wall with a and highway construction products, 5th Ed., Washington, D.C.
life expectancy of 35 years in similar soil conditions would Beavers, J. A., and Durr, C. L. 共1998兲. “Corrosion of steel piling in
be in the range of 1–4% with a maximum loss of about 7%. nonmarine applications.” NCHRP Rep. No. 408, Transportation Re-
5. The maximum measured corrosion rate for abutment piles search Board, National Research Council, Washington, D.C.
driven through fill and into native soil at the 118th South site Decker, J. B., and Rollins, K. M. 共2001兲. “Corrosion rate evaluation and
was considerably higher with an average corrosion rate of prediction for piles: Utah case histories.” GET Rep. No. 2001-2, Civil
13 ␮m / year in the fill, 22 ␮m / year in the native soil, and a and Environmental Engineering Dept., Brigham Young Univ., Provo,
maximum of 48 ␮m / year in the native soil near the water Utah.
table fluctuation zone. The high corrosion rates at this site Elias, V., and Christopher, B. R. 共1997兲. “Mechanically stabilized earth
walls and reinforced soil slopes, design and construction guidelines.”
can be attributed to high chloride content 共due to deicing
FHWA-SA-96-071, Federal Highway Administration, Washington,
salt兲, low resistivity, and the piles being driven through fill. D.C., 72–79.
For a driven pipe pile with a typical wall thickness of Ellsworth, J. C. 共2004兲. “Corrosion rate evaluation and prediction for
9.53 mm 共3 / 8 in.兲, these corrosion rates correspond to an piles in disturbed fill material.” MS thesis, Civil and Environmental
average thickness loss of 5% in the fill and 9% in the native Engineering Dept., Brigham Young Univ., Provo, Utah.
soil with a maximum loss of 18.6% for a 35 year exposure Escalante, E. 共1992兲. “Measuring the underground corrosion of steel pil-
period. This percent thickness loss is significant and points ing at Turcot Yard, Montreal, Canada—A 14 year study.” Corrosion
out forms and control for infrastructure, ASTM STP 1137, V. Chaker, ed.,
the potential for pile corrosion for highly corrosive soil Philadelphia, 339–355.
conditions. Greene, N. D., Long, R. P., Badinter, J., and Kambala, P. R. 共1995兲.
“Corrosion of steel pilings in soils.” Corrosion/95, National Associa-
6. The percent loss of tensile load capacity is directly related to
tion of Corrosion Engineers, Houston, Paper No. 17.
the percent loss of thickness due to corrosion.
Manning, J. T., and Morley, J. 共1981兲. “Corrosion of steel piles.” Piles
7. Existing methods for predicting corrosion of buried metals
and foundations, The Institute of Civil Engineers, London, 223–229.
are not reliable for predicting pile corrosion and corrosion
Ohsaki, Y. 共1982兲. “Corrosion of steel piles driven in soil deposits.” Soils
rates are not strongly correlated with soil parameters within
and foundations, Vol. 22, No. 3, Japanese Society of Soil Mechanics
typical ranges. and Foundation Engineering, Tokyo, 57–76.
8. The corrosion rate in the water table fluctuation zone is more Palmer, J. D. 共1967兲. “Environmental characteristics controlling the soil
sensitive to soil parameters than is the corrosion rate above corrosion of ferrous piping.” Effect of soil characteristics on corro-
and below this zone. Future efforts to develop corrosion cor- sion, ASTM STP 1013, V. Chaker and J. D. Palmer, eds., ASTM,
relations should focus on behavior in this zone. Philadelphia.
9. Corrosion rates on piles decrease with time, due to the deple- Peabody, A. W. 共1967兲. Control of pipeline corrosion, National Associa-
tion of oxygen and the build-up of protective layers. For steel tion of Corrosion Engineers, Houston.
piles in soils without extreme properties, the maximum cor- Picozzi, O. E., Lamb, S. E., and Frank, A. C. 共1993兲. Evaluation of
rosion loss on a pile can be reasonably estimated based only prediction methods for pile corrosion at the Buffalo Skyway, New
on the time of exposure for design purposes. York State Dept. of Transportation, Technical Services Division,
10. Sites that have measured soil parameters where the pH is less Albany, N.Y.
Roberge, P. R. 共2000兲. Handbook of corrosion engineering, McGraw-
than or equal to 5 or greater than 8.5, the resistivity lower
Hill, New York.
than 340 ⍀ cm, or a chloride concentration greater than Romanoff, M. 共1962兲. “Corrosion of steel pilings in soils.” NBS Mono-
450 ppm may experience very aggressive pile corrosion and graph No. 58, National Bureau of Standards, U.S. Dept. of Com-
steps may need to be taken to prevent excessive corrosion. At merce, Washington, D.C.
abutments where piles are to be driven through fill, special Schlosser, F., and Bastick, M. 共1991兲. “Reinforced Earth.” Foundation
care should be taken to ensure that the fill soil is not aggres- engineering handbook, H.-Y. Fang, ed., Van Nostrand Reinhold, New
sive and will not become aggressive due to application of York, 778–786.
road deicing salts. Tungesvik, J., Moum, J., and Fischer, K. P. 共1975兲. “Investigation of
corrosion rates on steel piles in Norwegian marine sediments.” Proc.,
7th Scandinavian Corrosion Congress, Trondheim, Norway, 487–502.
Acknowledgments Videla, H. A. 共1996兲. Manual of biocorrosion, Lewis, Boca Raton, Fla.
Wong, I. H., and Law, K. H. 共1999兲. “Corrosion of steel H piles in
This study was funded through a grant from the Utah Department decomposed granite.” J. Geotech. Geoenviron. Eng., 125共6兲, 529–
of Transportation 共UDOT兲. This support is gratefully acknowl- 532.

JOURNAL OF GEOTECHNICAL AND GEOENVIRONMENTAL ENGINEERING © ASCE / MARCH 2008 / 351

Potrebbero piacerti anche