Sei sulla pagina 1di 15

IEC

60044-2 IEC 60044-5 IS 3156 PART 1 IS 3156 PART 2 IS 3156 PART 3 IS 3156 PART 4 IS 4146 IS 5547

Is

an instrument transformer which steps


the voltage level of to to a fulfill suitable the &

down

measurable requirement protection.

measurement

Electromagnetic Capacitor

Pot. Transformer

Pot. transformer

It Is A Step Down Transformer. Similar As A Power Transformer. It Is Designed To Have Very Less Leakage Reactance.

Economical Upto 66 Kv.

Suitable For Supplying Measuring Inst. &


Protec. Relays.

Coupling Of Carrier Signal On Power Line. Used above 66 kV.

Ratio

Error (KN VS-VP)/VP

KN = Rated Transformation Ratio VP =Actual Primary Voltage VS = Actual Sec. Voltage

Phase

Angle Error

phase difference between the secondary voltage & applied voltage.


Voltage Factor Maximum System Voltage PT Can Withstand

eg for 765 kV 1.2 Continous 1.5 For 30 sec

Accuracy Classes 0.1 0.2 0.5 1.0 3.0

Ratio Error % 0.1 0.2 0.5 1.0 3.0

Application Measurement Measurement Measurement Measurement Protection

6.0

6.0

Protection

Coupling
It

capacitors act as voltage divider.

step downs the line voltage to

intermediate level(5- 15 kV)

Compensating

reactor cancels the

coupling capacitor reactance thus prevents ph. Shift between primary & sec voltages.
The

step down transformer further

reduces the intermediate voltage to 115V -110 V.

VOLTAGE kV
220

L1 mm
2870

L2 mm
2430

D mm
450

OIL WT kgs
62

TOTAL WT kgs
456

400

4632

4192

450

90

585

765

5870

5430

450

154

845