CLASSES OF PROTECTION
CLASS A1 CLASS A2 CLASS B CLASS C
GROUPS OF PROTECTION
Group-1 Group-2
DC source 1 from 1/2 FA section-1 DC source 2 from 1/2 FA section-2
CLASS A1
CAUSES OF CLASS A1 1. GT & UT PROTECTIONS 2. GENERATOR BACKUP PROTECTION 3. OTHER BACKUP PROTECTIONS
PRV BUCHHOLZ RELAY SUDDEN PRESSURE RELAY FIRE PROTECTION UT OLTC SUDDEN PRESSURE RELAY
Note: UT A/B WTI/OTI will trip the corresponding incomer from the transformer and change over to Standby Trf.
DIFFERENTIAL PROTECTION(GT/UT) 87GT/87UT GT HV WINDING + O/H LINE DIFFERENTIAL-87HV RESTRICTED EARTH FAULT (UTs only)87NUT A/B STANDBY EARTH FAULT (GT only)-51NGT OVERCURRENT PROTECTION (UTs only)-51UT A/B BACKUP EARTH FAULT (UTs only)-51 NUT A/B GT OVERFLUXING 99GT EARTH FAULT BEYOND GCB 64GT GT + O/H LINE DIFFERENTIAL 87TL
GENERATOR LBB (For GCB) 50GLBB GENERATOR BACKUP IMPEDANCE 21G DEAD MACHINE RELAY 50GDM
CLASS A1 - ACTIONS
CLASS A1 CAUSES TRIPPING OF
BOTH 400KV BREAKERS OF THE UNIT GCB FIELD BREAKER STEAM TURBINE UNIT TRANSFORMER INCOMERS BA/BB
CLASS A2 - CAUSES
GENERATOR PROTECTIONS
DIFFERENTIAL 87G1/87G2 OVERVOLTAGE 59G1 95% EARTH FAULT -64G1 INTERTURN FAULT 64GIT OVERFLUXING 99G NEGATIVE PHASE SEQUENCE 46G LOW FORWARD POWER 30sec 37G1/2 .. Contd.
CLASS A2 - CAUSES
GENERATOR PROTECTIONS
..contd.
CLASS A2 - CAUSES
SIEMENS MULTIFUNCTION RELAY 96G
CLASS A2 - ACTIONS
CLASS A2 CAUSES TRIPPING OF
GCB FIELD BREAKER STEAM TURBINE UT INCOMER (if both 400kV breakers are
in tripped condition)
CLASS B PROTECTION
CLASS B GENERATOR TRIP FROM TURBINE TRIP THIS IS ACHIEVED THROUGH LOW FORWARD POWER RELAY 2 SEC DELAY- 37 G1/2 NEED FOR CLASS B TRIP PROTECTION OF TURBINE FROM OVERHEATING
CLASS B - ACTIONS
CLASS B CAUSES TRIPPING OF THE FOLLOWING
UNDERFREQUENCY- 81G/96G
(GRID COLLAPSE) Presently connected to Class B at 45Hz.
RESET BOTH CLASS A2 TRIP RELAYS RESET STEAM TURBINE TRIP RESET BOTH CLASS B TRIP RELAYS SYNCHRONISE USNIG GCB
RESET STEAM TURBINE RESET BOTH CLASS B TRIP RELAYS SYNCHRONISE UNING GCB
CLASS C - RESTARTING
THE FOLLOWING SEQUENCE OF ACTIONS MUST BE FOLLOWED
STARTUP/TRIPPING RELAYRESETTING
Just before rolling only, reset the trip
relays After excitation, in case any of the fuse fail relays/50GDM flag has fallen reset them After synchronisation, see that no relays have acted. If the Low forward power relay LED has come, it should be reset.