TERMINOLGY
In Britain people have earth and in North America they have ground. They are exactly the same thing, only different terms are used in different countries. For example: Earth Leakage Circuit Interrupter and Ground-Fault Circuit Interrupter
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
240V
240V
Metal parts of premises wiring are bonded to an effective ground-fault current path that has sufficiently low impedance to quickly clear line-to-case faults by opening the circuit protection device.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
9.6
I = E/R, E = 240V, R = 25 , I = 240/25 = 9.6 A Insufficient current to trip overcurrent protection device
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
10
11
12
A GFCI is designed to protect persons against electric shock. It operates on the principles of monitoring the unbalanced current Between the ungrounded and the grounded neutral conductor.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
13
14
[Sec. 2.10.1.8(a)(2)Ex 1]
All 15/20A, 125/250V receptacles installed in a dwelling unit garage must have GFCI protection.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
15
All 15 and 20 A, 125/250 V receptacles in accessory buildings and similar work areas must be GFCI protected.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
16
Section 2.10.1.8(3)
17
All 15/20A, 125/250V receptacles in unfinished areas of basements must be GFCI protected.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
18
All 15/20A, 125/250V receptacles in unfinished Areas of basements must be GCFI protected.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
19
All 15/20A, 125/250V, receptacles that serve dwelling unit kitchen countertop surfaces must be GFCI protected.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
20
All 15/20A, 250V receptacles located within 6 ft or 1.8 m of a laundry or utility sink must be GFCI protected.
21
22
a) Dwelling Units 1. Bathrooms 2. Garages 3. Outdoors 4. Crawl spaces at or below grade level 5. Unfinished basements 6. Kitchens for countertop appliances 7. Wet bar sinks
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
23
Electric Shock
Electric Shock Severity 1. Path of Current through Body 2. Length of Time Current Flows 3. Amount of Current through Body
24
25
26
27
28
29
30
31
32
Section 2.50.6.9
33
34
35
36
This means that you can use either white or gray to identify the grounded neutral conductor of a single wiring system
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
37
38
39
40
41
42
43
44
45
46
When the service entrance conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor shall be 12 % of the largest phase conductor.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
47
48
49
50
51
52
53
Bonded
54
55
56
57
325 mm2 conductors 2.50.5.13, Table 2.50.3.17 50 mm2 Equipment Bonding Jumper
58
59
Effective Grounding
A violation of PEC Art. 2.50.3.11 which prohibits using the same grounding electrode for a lightning rod system and a system supply.
VIOL ATIO N!!!
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
60
Effective Grounding
PEC Art. 250.5.17 Lightning Protection System. The bonding of a system grounding electrode and a lightning rod grounding electrode.
BONDING REQUIRED!!!
61
Effective Grounding
When different grounding electrodes are used for a building and are not bonded together, a voltage hazard will exist!!!
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
62
Effective Grounding
Older designs, have independent grounding systems.
63
Effective Grounding
How surges enter facilities
64
65
Effective Grounding
Section 2.50.5.17
66
Effective Grounding
67
Effective Grounding
68
69
EQUIPMENT GROUNDING
70
Potential Difference
71
Potential Difference
72
Potential Difference
There is a Voltage!
73
Potential Difference
There is a Voltage!!
74
Potential Difference
75
Neutral Conductor (PEC2.50.2.17(b)) The neutral conductor from the neutral point of the transformer or the generator to its connection point to the grounding impedance shall be fully insulated. The neutral conductor shall have an ampacity of not less than the maximum current rating of the grounding impedance. In no case shall the neutral conductor be smaller than 8.0 mm2 copper or 14 mm2 aluminum or copperclad aluminum.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.
76
77
Grounded Conductor
78
Grounded Conductor
79
80