Sei sulla pagina 1di 80

8th Visayas IIEE Region VII Conference 2007 Cebu International Convention Center Mandaue City, Sept.

28-29, 2007

Why GROUNDING!!! Is Used?


Jaime V. Mendoza, PEE, MTM Board Member
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

8th Visayas IIEE Region VII Conference Sept. 28, 2007

TERMINOLGY
In Britain people have earth and in North America they have ground. They are exactly the same thing, only different terms are used in different countries. For example: Earth Leakage Circuit Interrupter and Ground-Fault Circuit Interrupter
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

Why Grounding is Used?


To limit voltage imposed by 1. Lightning 2. Line surges 3. Unintentional contact with higher voltage lines Stabilize the voltage to ground during normal operations. Facilitate overcurrent device operation in case of ground fault on a solidly grounded system.
PEC- 2000 Section 2.50.1.2(a)
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

To limit the voltages imposed by lightning or line surge


PEC-2.50.1.2(a)

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

To limit the voltages imposed by lightning or line surge

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

Facilitate overcurrent device operation in case of ground fault

240V

240V

Metal parts of premises wiring are bonded to an effective ground-fault current path that has sufficiently low impedance to quickly clear line-to-case faults by opening the circuit protection device.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

Earth is Not an Effective GroundFault Current Path


240

9.6

I = E/R, E = 240V, R = 25 , I = 240/25 = 9.6 A Insufficient current to trip overcurrent protection device
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

Ground Fault Circuit Interrupter


GFCI A device intended for the protection of personnel that functions to deenergize a circuit or portion thereof within an established period of time when a current to ground exceeds the values established for a device. The GCFI does not protect someone against receiving an electrical shock, but it does limit the time hazards exists. Hazard exist only during period of time fault is there.

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

Ground Fault Circuit Interrupter

GCFI CAN ELIMINATE THIS!


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

10

Ground Fault Circuit Interrupter

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

11

Ground Fault Circuit Interrupter

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

12

Ground Fault Circuit Interrupter

A GFCI is designed to protect persons against electric shock. It operates on the principles of monitoring the unbalanced current Between the ungrounded and the grounded neutral conductor.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

13

GFCI Protection for Personnel


1. Dwelling Bathroom Receptacle

and /or 250 V

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

14

GFCI Protection for Personnel


2. Dwelling Garage Receptacle

[Sec. 2.10.1.8(a)(2)Ex 1]

All 15/20A, 125/250V receptacles installed in a dwelling unit garage must have GFCI protection.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

15

GFCI Protection for Personnel


2. Dwelling Garage Receptacle

All 15 and 20 A, 125/250 V receptacles in accessory buildings and similar work areas must be GFCI protected.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

16

GFCI Protection for Personnel


3. Dwelling Outdoor Receptacle

Section 2.10.1.8(3)

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

17

GFCI Protection for Personnel


4. Dwelling Basement Receptacle

All 15/20A, 125/250V receptacles in unfinished areas of basements must be GFCI protected.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

18

GFCI Protection for Personnel


5. Dwelling Unfinished Basement

All 15/20A, 125/250V receptacles in unfinished Areas of basements must be GCFI protected.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

19

GFCI Protection for Personnel


6. Kitchens for Countertop Appliances

All 15/20A, 125/250V, receptacles that serve dwelling unit kitchen countertop surfaces must be GFCI protected.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

20

GFCI Protection for Personnel


6. Dwelling Laundry or Utility Sink

All 15/20A, 250V receptacles located within 6 ft or 1.8 m of a laundry or utility sink must be GFCI protected.

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

21

GFCI Protection for Personnel


7. Dwelling Wet Bar Sinks

GFCI protection required if within 1.8 m of sink

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

22

GFCI Protection for Personnel


PEC 2000- Section 2.10.1.8 (a)

a) Dwelling Units 1. Bathrooms 2. Garages 3. Outdoors 4. Crawl spaces at or below grade level 5. Unfinished basements 6. Kitchens for countertop appliances 7. Wet bar sinks
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

23

Electric Shock
Electric Shock Severity 1. Path of Current through Body 2. Length of Time Current Flows 3. Amount of Current through Body

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

24

Effects of AC Electric Shock


RMS Current Effects
1- 5 mA Threshold of sensation 10-20 mA Involuntary muscle contractions

20-100 mA Pain, breathing difficulties

100 - 300 mA Ventricular fibrillation, possible death

> 300 mA Respiratory paralysis, burns, unconsciousness

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

25

Identification of Equipment Grounding Conductors


PEC 2.50.6.10

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

26

Identification of Equipment Grounding Conductors


But, for a grounding conductor larger than No. 6 AWG or 14 mm2, an insulated conductor of other than green color or green with yellow stripes may be used provided one of the following steps is taken: PEC-2.50.6.10(a) 1. Stripping the insulation from an insulated conductor of another color (say black) for the entire length that is exposed on the box or other enclosure so that the conductor appear as a bare conductor. 2. Painting the exposed insulation green for its entire length within the enclosure. 3. Wrapping the entire length of exposed insulation with green-colored tape or green-colored adhesive labels.

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

27

Sizing Equipment Grounding Conductors (Sec. 2.50.6.13)


The regulations for calculating the size of equipment grounding conductor are:
1. Table 2.50.6.13 shall be used to size the equipment conductor. ( Based on the rating of the protective device ahead of the equipment.) 2. When ungrounded conductors are increased in size and an equipment grounding is installed with them, the equipment grounding conductor is required to be proportionately increased in size according to the circular mil area of the ungrounded conductors.

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

28

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

29

Sizing Equipment Grounding Conductors


The regulations for calculating the size of equipment grounding conductor are:
3. Where more than one circuit is installed in a single raceway or cable, one equipment grounding conductor can be installed in the raceway or cable; it will be sized for the largest overcurrent device protecting conductors in the raceway or cable. 4. An equipment grounding conductor not smaller than 18 AWG copper(0.75 mm2) is permitted for flexible cords when the flexible cord is protected at or over 20 amperes.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

30

Sizing Equipment Grounding Conductors


The regulations for calculating the size of equipment grounding conductor are:
5. The equipment grounding conductor is never required to be larger than the circuit conductors. 6. Where the overcurrent protection is an instantaneous circuit breaker or a motor protector, the equipment grounding conductor is sized according to the size of the motor overload protective device.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

31

Sizing Equipment Grounding Conductors


The regulations for calculating the size of equipment grounding conductor are:
7. When conductors are run in parallel in more than one raceway or cable , as permitted in Sec. 3.10.1.4, the equipment grounding conductor is run in parallel. Each of the paralleled equipment grounding conductors is sized according to the ampere rating of the overcurrent device protecting the conductors in the raceway or cable.

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

32

Section 2.50.6.9

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

33

European Coding of Grounded Conductor


European Coloring Ground wire green wire with yellow stripe color Neutral wire blue color Live wire brown black and black with white strip (for 3-phase)
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

34

US Coding of Grounded Conductor


In the US, Black is the hot wire, white is the neutral or common wire and green is the equipment grounding.

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

35

Means of Identifying Grounded Conductor


The basic rule in PEC- 2.1.1.6(a) requires the grounded conductor Sizes 14 mm2 or smaller to be identified by: 1. A white color 2. A gray color 3. Three continuous white stripes, on other than green insulation, extending along the entire length of the conductor
Prior to the PEC-2000 Code, the gray color was permitted to be used as a hot conductor.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

36

Means of Identifying Grounded Conductor


PEC 2.1.1.6(a)

This means that you can use either white or gray to identify the grounded neutral conductor of a single wiring system
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

37

Means of Identifying Grounded Conductor


PEC 2.1.1.6(a)

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

38

Means of Identifying Grounded Conductor


Insulated grounded conductor larger than 6 AWG or 14 mm2 to be identified by the one of the following methods: PEC 2.1.1.6(b) 1. By a white or gray outer finish 2. By three continuous white stripes, on other than green insulation, running along the entire length of conductor 3. By a distinctive white marking ,encircling the conductor, placed there at the time of installation, and the identifying the grounded conductor at each termination (The identification may be by tagging, marking, painting or other effective means)
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

39

Means of Identifying Grounded Conductor

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

40

Identifying Grounded Neutral Conductors of Different Systems


PEC 2.1.1.6(d)

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

41

Identifying Grounded Neutral Conductors of Different Systems

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

42

Identifying Grounded Neutral Conductors of Different Systems

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

43

Means of Identifying Grounded Conductor

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

44

Sizing the AC Grounding Electrode Conductors


When sizing electrical conductors, the ampacity of the main consideration. This is not the case when sizing electrode conductor, it is sized according to crosssectional area of the service-entrance conductor. The size of the grounding electrode conductor is taken directly from Table 2.50.3.1.17 of PEC, when the size of the service entrance conductors is not larger than 1100 kcmil cu. Or 1750 kcmil aluminum.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

45

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

46

Sizing the AC Grounding Electrode Conductors

When the service entrance conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor shall be 12 % of the largest phase conductor.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

47

Sizing the AC Grounding Electrode Conductors

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

48

Sizing the AC Grounding Electrode Conductors


What are the sizes of the grounding electrode conductors of the following if the service entrance conductors used are: 1. 500 kcmil copper 2. 500 kcmil aluminum 3. 1/0 copper 4. 2 copper
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

49

Installation of Grounding Rods


Basic Requirements for a rod or pipe electrode are: Section 2.50.3
1. 2. 3. 4. 5. Minimum length of 2.5 m or 8 ft When metal pipe or conduit is used for electrode, it is required to be not smaller than trade size conduit. Iron or steel pipe electrodes are required to have a galvanized surface or other corrosive resistant material. Rod electrode may be iron, steel, or stainless steel and are required to have a minimum diameter of 5/8 inch (16mm) diameter. Nonferrous rods, or their equivalent are required to have a minimum diameter of inch (13 mm).
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

50

Installation of Grounding Rod


Section 2.50.13.15(G)*

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

51

Main Bonding Jumper

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

52

Main Bonding Jumper

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

53

Bonded

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

54

Sizing the Main Bonding Jumper (Sec. 2.50.2.9(d))


Three methods for sizing the main bonding jumper are given in Table 2.50.3.17. When sizing the main bonding jumper, the size and material of service entrance conductors and material used for the main bonding conductor are taken into consideration.

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

55

Sizing the Main Bonding Jumper


Three methods for sizing the main bonding jumper are:
1. Basic Rule: Use Table 2.50.3.17, the grounding electrode conductor table, is also used for the main bonding jumper. 2. 12 Percent Rule for Large Conductors. When the total circular area of any service entrance phase conductor exceeds the maximum circular-mil area listed in Table 2.50.3.17, the main bonding jumper shall not be smaller than 12 % of the service phase conductors.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

56

Sizing the Main Bonding Jumper


Three methods for sizing the main bonding jumper are: 3. Rule for Using Different Materials. This rule applies when the main bonding jumper is a different material than the service-entrance conductors. One could be aluminum and the other copper for example. In this case, the minimum size of the main bonding jumper is based on assuming that the service entrance conductors are of the same material as the main bonding jumper and that ampacity is equivalent to the installed phase conductors.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

57

Sizing the Main Bonding Jumper (Sec. 2.50.5.13(c))

325 mm2 conductors 2.50.5.13, Table 2.50.3.17 50 mm2 Equipment Bonding Jumper

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

58

What is Effective Grounding?

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

59

Effective Grounding
A violation of PEC Art. 2.50.3.11 which prohibits using the same grounding electrode for a lightning rod system and a system supply.
VIOL ATIO N!!!
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

60

Effective Grounding
PEC Art. 250.5.17 Lightning Protection System. The bonding of a system grounding electrode and a lightning rod grounding electrode.

BONDING REQUIRED!!!

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

61

Effective Grounding

When different grounding electrodes are used for a building and are not bonded together, a voltage hazard will exist!!!
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

62

Effective Grounding
Older designs, have independent grounding systems.

The more recent trend is to bond all the ground systems.


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

63

Effective Grounding
How surges enter facilities

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

64

Understanding the Lightning Discharge


Cloud electrification charge particle separation, quasi static E Field est. between cloud & ground Upward leader propagates toward downleader to complete ionised path between cloud & ground

Downleader approaches, E Field increases to point of initiation of upward streamers


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

65

Effective Grounding
Section 2.50.5.17

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

66

Effective Grounding

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

67

Effective Grounding

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

68

Why Ground Noncurrent-Carrying Conductive Materials Enclosing Electrical Equipment?

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

69

Why Ground Noncurrent-Carrying Conductive Materials Enclosing Electrical Equipment?

EQUIPMENT GROUNDING

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

70

Potential Difference

Potential difference between a grounded water pipe and an ungrounded motor.


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

71

Potential Difference

Motor ground-fault. A hazard now exists.


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

72

Potential Difference

There is a Voltage!

The hazard results in an electric shock.


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

73

Potential Difference

There is a Voltage!!

Another shock hazard exists.


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

74

Potential Difference

Shock hazard eliminated by installing a bonding jumper.


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

75

Neutral Conductor (PEC2.50.2.17(b)) The neutral conductor from the neutral point of the transformer or the generator to its connection point to the grounding impedance shall be fully insulated. The neutral conductor shall have an ampacity of not less than the maximum current rating of the grounding impedance. In no case shall the neutral conductor be smaller than 8.0 mm2 copper or 14 mm2 aluminum or copperclad aluminum.
BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

76

Neutral Conductor (PEC 2.50.2.17(b))

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

77

Grounded Conductor

Not a neutral because it is not a 3 0r 4 wire system.


BOARD OF ELECTRICAL ENGINEERING
INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

78

Grounded Conductor

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

79

Grounding and bonding at the service equipment BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?

8th Visayas IIEE Region VII Conference Sept. 28, 2007

80

BOARD OF ELECTRICAL ENGINEERING


INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC.

Why Grounding is Used?