Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
TOPICS COVERED: Transformer Basics Transformer Construction Transformer Operating Principles Transformer Symbols And Testing StepStep-up And Step-down StepTransformer
2
TOPICS COVERED:
TransformerTransformer- Isolation Device Transformer Current Calculation and Efficiency Transformer Rating Power Losses Impedance Matching Transformer Application
3
TRANSFORMER BASICS
When an AC voltage is applied in a coil, the electromagnetic field expands, collapses and reverses as the current increases, decreases and reverses. When two coils are placed very close to each other, the changing magnetic field produced by the first coil will cause an induced voltage in the second coil because of the mutual inductance between the two coil.
HOW???
When two coils are placed very close to each other, the changing magnetic flux line produced by the first coil will cut through the second coil. The two coils are said to be magnetically linked or coupled. As a result, a voltage is induced.
Because there is no electrical connection between the two coils (only magnetic link), so they are electrically isolated. The amount of voltage induced in the second coil depends on the mutual inductance, LM which is the inductance between the two coils.
LM
LM ! k L1 L2
L1
L2
LM
LM ! k L1 L2
L1
L2
The coefficient of coupling is a measure of how well the coils are linked; it is a number between 0 and 1. The coefficient of coupling depends on factors such as the orientation of the coils to each other, their proximity, and if they are on a common core. 7
TRANSFORMER BASICS
The basic transformer is formed from two coils that are usually wound on a common core to provide a path for the magnetic field lines. Schematic symbols indicate the type of core.
Air core
Ferrite core
THE FUNCTION
Function of a transformer: To transfer current, voltage and power from one series of windings (coils) to another.
TRANSFORMER CONSTRUCTION
The transformer consists of core, surrounded by at least two series of coils. The core is used as to aid in linking the flux from the primary coil to the secondary coil. Dots are used in diagrams of transformers to indicate the current polarities for the windings. Dotted terminals have the same polarity.
10
Dot Notation
11
Nsec = number of secondary windings Npri = number of primary windings Most transformers are not marked with turns ratio, however it is a useful parameter for understanding transformer operation.
A transformer has 800 turns on the primary and a turns ratio of 0.25. How many turns are on the secondary?
OPERATING PRINCIPLES
Transformer action: based on the laws of electromagnetic induction. There is no electrical connection between the primary and secondary. The AC power is transferred from primary to secondary through magnetic flux. If an ac voltage is applied to the primary coil, magnetic flux will be created. When the magnitude of the applied flux changed, then the generated flux changed. This changing flux will link the primary and secondary coil and induce a voltage across the secondary windings. There is no change in frequency (output power has the 13 same frequency as the input power).
(a)
(b)
The easiest way to test a transformer is to test the primary and secondary coils for continuity. Since the primary and secondary of a transformer are coils, both of them should have continuity between each end of the coil.
14
A transformer that has more turns on the primary than the secondary side of the transformer will decrease the input voltage.
This is called a step-down transformer.
15
TRANSFORMERISOLATION DEVICE
A transformer can also be used as an isolation device. The circuit on the primary side of the transformer is electrically isolated from the circuit on the secondary side of the circuit. Isolation transformers usually have the same secondary voltage as the primary. They are mainly used to isolate a piece of equipment from the AC mains for safety reasons. Television set is an example of the need for isolation transformers for diagnostic and repair work.
16
17
For an ideal transformer, the PPrimary is equal to the PSecondary, or the power input is equal to the power output.
19
Example 1: A doorbell requires 0.4 A at 6V. It is connected via a transformer whose primary coil contains 2000 turns to a 120V AC line. Calculate (a) N2 and (b) I1
20
Reflected load
A transformer changes both the voltage and current on the primary side to different values on the secondary side. This makes a load resistance appear to have a different value on the primary side. V pri V
R pri ! I pri and RL !
sec
I sec
R pri
22
IMPEDANCE MATCHING
To maximize power transfer, the load resistance must be matched with the source resistance Normally, the two resistance are not matched and fixed (e.g.: speakers resistance (source) is only a few ohms, but internal resistance of audio power amplifier (load) is several thousand ohms. To connect them, we need a transformer. Or else, more power dissipated at the source.) To match the resistance, reflect the load resistance into the primary.
23
An amplifier has an 800; internal resistance. To provide max power transfer, what turns ratio must be used in the matching transformer? Calculate the turns ratio of a transformer to match a 100; load to a source with internal impedance of 2.5k;. Find the load voltage when the source voltage is 30V
24
Determine the turn ratio n that will cause max power transfer to the load.Calculate the max power to the load
25
Find n for max power transfer. Then determine the power in the load if n=10
26
POWER LOSSES
A practical transformer differs from the ideal transformer in many respects. The practical transformer has iron or core losses and copper losses. -Iron or core losses- eddy current and hysterisis losses -copper losses- in the resistance of the windings
Iron or core losses The magnitude of these losses is quite small. This losses due to eddy current and hysteresis loss in it.
27
POWER LOSSES
(1) Eddy Current The magnetic core of a transformer consists of many laminations of a high-grade silicon steel. When the alternating flux cuts the steel core, an emf is induced in each lamination, causing a current (eddy current) to flow in the closed electrical. Due to this eddy current and resistance in each lamination, a certain amount of power will be absorbed, producing heat in each lamination and also in the core.
28
29
Example 3: A power transmission line has a resistance of 0.2 ohm. Calculate the power loss if 200 kW of power is transmitted from a power generator to a city at: (a) 240 V and (b) 4.4 kV.
31
Example 4: A transformer for home use of a portable radio reduces 120V ac to 30V ac. The secondary contains 50 turns, 10ohm resistance. Given the primary resistance is 5ohm. - The primary turns - Calculate the total transformer losses if the core losses is 50W.
32
TRANSFORMER APPLICATION
Step-up or step-down voltage and current. Isolation device
electrical isolation. Electrical isolation can be used to improve the safety of electrical equipment. DC isolation. Coupling transformers can be used to block DC signals from reaching the secondary circuit.
Lighting Ballast
Use to start the lamp by producing the necessary voltage and limits current thro the lamp.
Coupling Transformer
Isolates each section of the amplifier so individual amplifier characteristics will not interfere with others
34
THANK YOU
35