DEEPAK SHARMA VIIth Sem.,B.Tech.

(Electrical) 08EYTEE010(E-1)

INTRODUCTION
Rajasthan Rajya Vidyut Prasaran Nigam Limited (RRVPNL).A company under the Companies Act of 1956.Established on 19 July, 2000 by Govt. of Rajasthan under the provisions of the Rajasthan Power Sector Reforms Act, 1999 as the successor company of RSEB.An ISO 9001:2000 Certified Company.Registered Office at Vidyut Bhawan, Jyoti nagar Jaipur.

DUTIES & RESPONSIBILITIES OF RRVPNL


Transmission of bulk power from Intra state generating transmission of stations to inter- electricity phase point of DISCOMS.

Planning and co- ordination.


Complying with the relating to intra- directions of RLDC state and SLDC for its transmission operation.

CONTROL AND OPERATION


Control & Operation of GSS Works under the directions of RLDC and SLDC for load dispatch Load dispatch on the basis of the Hourly GSS schedule Permission from LDC for line or Transformer shutdown.
Work in synchronization with DISCOMS for scheduled maintenance.

Incoming Feeder

RATINGS OF THE INSTRUMENT AT THE INCOMING FEEDER


Instrument Rating Lightning arrester 198KV CVT 245KV, 200VA CT

800-400-200/1A, 5C, 20KA/1Sec. SF6 Circuit Breaker 245KV, 40KA/3Sec Wave Trap NA Line Isolator 800A SF6 CB Ratings Voltage 245KV Normal Current 2000A Lightning impulse withstand voltage 1050 KV Short circuit breaking current 40 KA Short circuit breaking duration 3 sec Gas Pressure SF6 (20 degree) 7 bar Air Pressure 20 bar Line Charging breaking current 125 A

220/132 KV, 100 MVA Transformer Type of Cooling ONAN ONAF

OFAF Rated Power HV(MVA) 50 70 100 LV(MVA) 16.67 23.33 33.33 Rated Voltage HV(KV) 220 IV (KV) 132 LV(KV) 11 Rated Line Current HV(A) 131.37 183.92 262.74 IV(A) 218.95 306.53 437.90 LV(A) 874.97 1225.96 1751.44 No. of Phases 3 Max. Temp. rise Top Oil 40 over an ambient of Avg. Winding 55 50 degree Celsius Frequency 50 HZ

Switchyard EQUIPMENT RATING MAIN BUS-II CVT 220KV//3/110V,200VA ISO.


MAIN BUS-II CVT 800A,245KV BUS ISOLATER 145

KV,800A C.B. 1250A,145KV C.T. 400-200-100/5A,3C WT NA It has total of 13 bays with 10 SF6 type of CB & 3 Air Blast CBs

Rating of Tranformers at 33 KV and 11KV


Switchyards Voltage Power No. of Rating Rating Transformer :-

132/33KV 40/50MVA 1
132/33KV 20/25MVA 2 132/11KV 10/12.5MVA 1 33/0.4kv 250KVA 1

At total of 18 bays with 11 Vacuum CB & 6 MOCB also 1 SF6 CB Equipment Ratings 33 KV C.T 500-250-125/1A, 2C 33 KV Isolator.
Bus 630A 33 KV Circuit Breaker 1250A, 36KV 33 KV capacitor Bank 38 KV, 7.2 MVAR LA 28KV 33 KV PT(ON BUS-I) 33KV/ /3*110V, 100VA

Equipments Ratings 11 KV Circuit Breaker 1250A,25KA/1Sec


11 KV C.T 400-200-100/5A,2C LA 11KV 11 KV PT ON BUS(3PH) 11KV/110 V, 100VA 11 KV Isolator Bus 400A 11 KV switchyard consisted of 6 bays, with all Vacuum types of CB

THE OUTGOING FEEDERS FROM

HEERAPURA ARE:1.SANGANER 220 KV 2.HEERAPURA ITSELF 11KV 3.SODALA 132KV 4.DUDU 132KV 5.BAGAD 33KV 6.VIDAYADAR NAGAR 33KV ETC.

Fault Operation,Relay trips as fault is detected in the system.


Breaker operates Alarm at control room blows up. Alarm is manually reset. Breaker is made off after 5 min. If the fault persists , Isolator is removed. Fault if at switchyard is checked if no local fault present, then fault

feeder is contacted. Supply is resumed after fault removal.

Visual checking for any hot spot Checking of air and gas leakage from the breaker Checking of air and gas pressure of breaker Checking of oil level from CT and CVT

Thermo vision scanning of conductor joints and attending to the hot spot available Breaker operation. Checking from local and remote Isolators operation from

remote and local. Measurement of specific gravity and voltage of 220 V D. C Battery cells.

Transformer Maintenance Permission from SLDC Switching Load to other Tranformer .


CB connected is operated Isolators are operated .

Earthing is provided to remove the residual charge due to induction.

Level of Members committee


Subdivision level AEN, ARO, JEN Division level XEN, AEN (Concerned) Assist Account officer Circle Level SE, XEN Accounts Officer Vig. / Audit Officer/ XEN(M&P) Chief Engineer CE, SE, Sr. AO, SE (Comml.) level Vig/Audit

Officer/SE(M&P) Corporate Level CMD, Director Finance,CE (Comm.), CE (O&M) JPr, Incharge Legal Section

Queries??

THANK YOU..