Sei sulla pagina 1di 67

Power systems in steady-state

Valentin Ilea
Department of Energy
Politecnico di Milano
Structure of an Electric Power System
EPS structure 3

Medium Voltage (MV) levels:


6 – 35 kV
EPS structure 4

Medium Voltage (MV) levels:


6 – 35 kV
EPS structure 5

High Voltage (HV) levels:


220 – 750 kV – Transmission
110 – 150 kV – Sub-transmission

Medium Voltage (MV) levels:


6 – 35 kV
EPS structure 6

High Voltage (HV) levels:


220 – 750 kV – Transmission
110 – 150 kV – Sub-transmission

Medium Voltage (MV) levels:


6 – 35 kV
EPS structure 7

High Voltage (HV) levels:


220 – 750 kV – Transmission
110 – 150 kV – Sub-transmission

Medium Voltage (MV) levels:


6 – 35 kV
EPS structure 8

MV levels: 6 – 69 kV
High Voltage (HV) levels:
220 – 750 kV – Transmission
110 – 150 kV – Sub-transmission

Medium Voltage (MV) levels:


6 – 35 kV
EPS structure 9

MV levels: 6 – 69 kV
High Voltage (HV) levels:
220 – 750 kV – Transmission
110 – 150 kV – Sub-transmission

Medium Voltage (MV) levels:


6 – 35 kV
EPS structure 10

MV levels: 6 – 69 kV
High Voltage (HV) levels:
220 – 750 kV – Transmission
110 – 150 kV – Sub-transmission

Primary Customers

Medium Voltage (MV) levels: LV levels: 380 V


6 – 35 kV
EPS structure 11

MV levels: 6 – 69 kV
High Voltage (HV) levels:
220 – 750 kV – Transmission
110 – 150 kV – Sub-transmission

Primary Customers

Medium Voltage (MV) levels: LV levels: 380 V


6 – 35 kV
EPS structure 12
Power substation (connection points in the grid)

Electric Transformer

Terminals

Isolators

Cooling system

Case
EPS structure 13
Power substation (connection points in the grid)

1. Primary power lines 10. Control building


2. Grounded wire 11. Security fence
3. Overhead lines 12. Secondary power lines
4. Lightning arrester
5. Disconnect switch
6. Circuit breaker
7. Current transformer
8. Transformer for measurement of electric voltage
9. Main transformer
EPS structure 14
Power substation (connection points in the grid)

For Symmetrical and Balanced operating conditions (no-faults normal operating conditions):

Primary power lines Main transformer Secondary power lines


EPS structure 15

How complex a power system is ???


https://www.entsoe.eu/data/map/

The power system is a very complex meshed network through which the
electrical power is transmitted from the electrical energy converter
(generator, power plant) to the demand. It can be divided into

• Transmission:
 nominal voltages above 220 kV;
 highly meshed grids;
 Installed load/generation higher than 200 MW each.
EPS structure 16

• Subtransmission (HV distribution) generally:


380kV

132 or 150 kV

0,4 kV

23/20/15/10 kV
Sub-transmission generation, customers or MV grids
EPS structure 17

How complex a power system is ???


https://www.entsoe.eu/data/map/

The power system is a very complex meshed network through which the
electrical power is transmitted from the electrical energy converter
(generator, power plant) to the demand. It can be divided into

• Subtransmission (HV distribution):


 nominal voltages 132 – 150 kV;
 poorly meshed grids: ring between two-three substations (busbars);
 installed generation 8 – 200 MW, loads larger than 4 MW;
EPS structure 18

• Subtransmission (HV distribution):


400 kV Italian Transmission network
EPS structure 19

• MV distribution grid generally:

Primary substation HV/MV 1

MV MV MV
MV/LV MV/LV MV/LV Normally open
LV substation LV substation LV substation breaker or
disconnector

Primary subtstaion HV/MV2

MV MV
MV/LV MV/LV
LV substation LV substation
EPS structure 20

How complex a power system is ???


https://www.entsoe.eu/data/map/

The power system is a very complex meshed network through which the
electrical power is transmitted from the electrical energy converter
(generator, power plant) to the demand. It can be divided into

• MV distribution:
 nominal voltages 10-24 kV or even higher, up to 60 kV;
 Radial grids or ring topology (normally open);
 Installed capacity: loads/generators each in the range 4-8 MW;

• Secondary distribution:
 nominal voltages 400 V;
 Radial grids;
 Installed capacity: loads/generators each up to some hundreds of kW;
EPS structure 21

• MV distribution grid example:

sorce: https://pandapower.readthedocs.io/en/v1.5.1/_images/plotting_tutorial1.png
Power system’s components models
Power systems components models 23

Let us remember the main steps we took to solve Exercise 5 of the Synchronous
Machines applications:
V, I, Ploss, Qloss
VG

PG QG PD QD

• first, knowing the characteristics of the demand, calculations have been


performed to obtain the required real and reactive power from the grid;

• second, we made computations in the electrical grid to determine the nodal


voltages. power losses and currents in the network;

• finally, knowing the voltage at generator’s terminals and the power it needs to
inject into the network to suply the motor, the emf (therefore, the excitation
current) and the mechanical power at the shaft of the generator have been
determined;
Power systems components models 24

Let us remember the main steps we took to solve Exercise 5 of the Synchronous
Machines applications:
V, I, Ploss, Qloss
VG

PG QG PD QD

• it is clear that, from the network point of view, the generator and the motor
(demand) are seen as inputs so simplified models can be adopted, while the
network components (electric lines and transformers) need to be modeled in
details.
Generator Models 25

• Engineering models depend upon application


• Large generators are usually synchronous machines
• we have studied a detailed model for the synchronous generator:

Ig
R+jXS
Ef V

– a simplified model, treating the generator as a constant power source operating at


a fixed voltage will be used for power flow and economic analysis:
Pg

V = const.

– neglecting the losses in the machine: the real power is given by the turbine
mechanical power while the voltage is kept constant through the control of the
excitation current
Load Models 26

• Electrical characteristics of individual loads can usually only be estimated:


aggregate models are typically used

– actual loads are continuously changing, being an aggregation of a large number


of individual devices
– only limited observability of load

• It is important to know how the load changes with variations of bus voltage: three
(static) models can be adopted

– constant power (power flow studies): 𝐴´


  𝐷 = 𝑃𝐷 + 𝑗 ∙ 𝑄 𝐷= 𝑐𝑜𝑛𝑠𝑡 .

– constant impedance:
2
V V
Z 
I P  jQ

– constant current:

𝑃 − 𝑗𝑄
¯𝐼  = =𝐼 ∠ ( 𝛿 − 𝜑 )     where   𝛿   is   the   voltage  angle
´𝑉
Electric line Models 27

Electric lines can be made with bare air conductors (HV and MV), or in
underground cables (MV and LV).

The isolators support and isolate the conductors with respect to the sustaining
pillars.
The insulation between the conductors and the ground is guaranteed by the air.

Electric Power Systems


Electric line Models 28
Distributed parameters model
Looking at an elementary length of line(ΔL) one can distinguish the
longitudinal parameters which are representative for the joule losses in the
conductors (the resistance) and the electromagnetic couplings between
conductors and between conductors and ground (the reactance):

𝟐
𝑷
  𝑱 =𝚫 𝑹 𝑳 ∙ 𝑰

´𝑰
 
´𝑰
 
´𝑰
 
  ´ 𝑳 =− 𝒋 ∙ 𝚫 𝑿 𝑳 ∙ ´𝑰
𝑬

Electric Power Systems


Electric line Models 29
Distributed parameters model
The transverse parameters are representative of the capacitive effects
between the conductors and between the conductors and the ground
(susceptance), and of the conductive effects (dispersion currents) on the
isolators, which cause the re-closing to the ground of a part of the current
through the support pillars (conductance).

Electric Power Systems


Electric line Models 30
Distributed parameters model

The equivalent circuit for an elementary length of line (ΔL) can be


represented as follows:

Distributed parameter circuit.

ΔRl, ΔXl and ΔBc, ΔG are the


longitudinal and shunt
parameters of the line,
respectively.

To represent the entire line it would be neccessary to connect in series


as many bipoles as elementary lengths have been considered.

Distributed parameters model requires an excessively complicated and


poorly practical equivalent circuit.
Electric Power Systems
Electric line Models 31
Concentrated parameters model
To reduce the complexity, we switch to the concentrated parameter
representation: the electrical parameters of the line are combined in a
single point (or a limited number of points).

Concentrated
Rl  rl L X l  xl L Bc  bc L G  gL parameters

Rl Xl Bc G Per length (1 km)


rl  xl  bc  g
L L L L parameters of the line

Electric Power Systems


Electric line Models 32
Concentrated parameters model

In order to study the electrical power systems, the most used model is the
so-called «p-model»:

2 2 2
2

This choice is motivated by a better representation of the distributive


nature of the transversal parameters and by the need to limit the number
of variables to be managed.
For example, using a «T-model» for the representation of power lines will
increase the number of electrical nodes in the system:
The admittance matrix
The Power Flow problem: 34
Goal

An electrical network is represented as a set of interconnected electrical


nodes (the substations) through electrical branches (the electric lines and
the transformers).

Goal: Given a generic network, calculate the equilibrium condition of the


whole system, that is the steady-state values of the electrical variables in
all the nodes and in all the branches of the system.

In order to calculate this equilibrium, if we know the


parameters of the various branches, the problem is
reduced to the calculation of the nodal voltages.
Indeed, knowing the nodal voltages is possible to express
the currents (and therefore the powers) circulating on a
generic branch as:
𝑣´𝑖𝑗 = 𝑉´ 𝑖 − 𝑉´ 𝑗 = 𝑧´𝑖𝑗 ∙ 𝑖´𝑖𝑗
 

i   𝑧´𝑖𝑗 j 𝑉´ 𝑖 − 𝑉´ 𝑗
iij 𝑖´𝑖𝑗 =
𝑧´𝑖𝑗
The pu system 35

• Power transmission lines are operated at voltage levels where the kV is the most
convienent unit to express voltage. Because of the large amount of power transmitted,
kW or MW and kVA or MVA are the common terms. However, these quantities as well as
A and W are often expressed in per unit of a base or reference value.

• The per-unit value (pu) of any quantity is defined as the ratio of the quantity divided to its
base expressed as a decimal.

• The per-unit calculations are simpler and often more informative than the use of actual A,
W, V etc.

• Voltage, current, powers and impedance are so related that a selection of base values for
any two of them determines the base values of the remaining two.
The pu system 36

• Since balanced three-phase circuits are solved as a single line with a neutral return, the
bases for quantities are kVA (or MVA) per phase and kV from line to neutral. However,
data are ussually given as total three-phase kVA (or MVA) and line-to-line kV:

Actual circuit
Computations circuit

𝑉 𝐿𝐿, 𝑎
𝑉  𝑓 ,𝑎 =
√3
The pu system 37

 • Although a line voltage may be specified as base, the voltage in the single phase voltage
(computation circuit) required for the solution is still the voltage to neutral. The base
voltage to neutral is the base voltage from line-to-line divided by :
𝑟𝑒𝑓
  𝑉 𝐿𝐿
𝑉 𝑟𝑒𝑓
𝑓 =
√3
• But in a balanced three-phase systems this is also the ratio between line-to-line and line-
to-neutral voltages:
𝑉 𝐿𝐿, 𝑎
𝑉  𝑓 ,𝑎 =
√3

• It follows that a per-unit value of a line-to-neutral voltage on the line-to-neutral voltage


base is equal to the per-unit value of the line-to-line voltage at the same point on the line-
to-line voltage base if the system is balanced:

𝑉 𝐿𝐿 ,𝑎   𝑝𝑢 𝑉 𝑓 ,𝑎 𝑉 𝐿𝐿 ,𝑎 √ 3 = 𝑉 𝐿𝐿, 𝑎 =𝑣 𝑝𝑢
𝑣  𝐿𝐿 ,𝑎 = 𝑟𝑒𝑓 𝑣 𝑓 , 𝑎= ∙
𝑝𝑢
and 𝑟𝑒𝑓
= 𝐿𝐿 ,𝑎
𝑉 𝐿𝐿 𝑉𝑓 √3 𝑉 𝑟𝑒𝑓𝐿𝐿 𝑟𝑒𝑓
𝑉 𝐿𝐿
The pu system 38

• Similarly, the three-phase kVA (or MVA) is three times the kVA (or MVA) per-phase, and
three-phase kVA (or MVA) base is three times the base kVA (or MVA) per phase.
Therefore, the per-unit value of the three-phase kVA (or MVA) base is identical to the per-
unit value of the kVA ( or MVA) per phase on the kVA (or MVA) per-phase base:

𝑟𝑒𝑓 𝑟𝑒𝑓
 𝐴3 𝑓 =3 ∙ 𝐴 1 𝑓

and
𝐴1𝑓 𝐴3 𝑓 3 𝐴3𝑓
𝐴3𝑓 𝑎  1 𝑓 =
𝑝𝑢 𝑝𝑢
 
𝑎 =
𝑝𝑢 and 𝑟𝑒𝑓
= ∙ 𝑟𝑒𝑓 = 𝑟𝑒𝑓 =𝑎3 𝑓
3𝑓 𝑟𝑒𝑓 𝐴1𝑓 3 𝐴3𝑓 𝐴3𝑓
𝐴 3𝑓

• For this reason in network computations the line-to-line voltage base and the three-phase
base powers are used.
The pu system 39

• Base impedance and base current can be computed directly from three-phase values of
base kV and base kVA (or MVA). If we interpret base kVA and base voltage in kV to mean
base kVA for the total of the three-phases and base voltage from line-to-line, we find

  𝑟𝑒𝑓 𝐴 𝑟𝑒𝑓
3 𝑓 ( 𝑘𝑉𝐴 )
𝐼 = =𝐼 𝑟𝑒𝑓 ( 𝐴)
√ 3 ∙𝑉 𝑟𝑒𝑓
𝐿𝐿 (𝑘𝑉 )

𝑟𝑒𝑓 2
  𝑉 𝐿𝐿
𝑟𝑒𝑓
𝑍1𝑓 =
𝑉
𝑟𝑒𝑓 2
𝑓
2
∙1000 (𝑘 𝑉 ∙ 1000)
=
(√ ) 3
2
∙ 1000 ( 𝑘 𝑉 ∙1000 )

𝐴 𝑟𝑒𝑓 ( 𝑘𝑉𝐴 ) 𝑟𝑒𝑓


𝐴3𝑓
1𝑓
( ) 3
(𝑘𝑉𝐴 )

𝑟𝑒𝑓 2 2 𝑟𝑒𝑓 2 2
  𝑟𝑒𝑓 𝑉 𝐿𝐿 ∙1000 ( 𝑘 𝑉 ∙ 1000 ) 𝑉 𝐿𝐿 ( 𝑘 𝑉 )
𝑍 = 1𝑓 𝑟𝑒𝑓
= 𝑟𝑒𝑓
𝐴 (𝑘𝑉𝐴 )
3𝑓 𝐴 3 𝑓 ( 𝑀𝑉𝐴 )
The admittance matrix 40

• Let’s study this system


The admittance matrix 41

• Let’s study this system

1
2

L
The admittance matrix 42

• Let’s study this system

1 2

3
• Assume that losses in the
L
transformers can be neglected
for the sake of simplicity
• Then, 3 busses are
highlighted and the
corresponding graph is
represented

Electric Power Systems


The admittance matrix 43

The electric model of the network is thus:

120 120
2 2
nodo (V, y12 nodo (P,V)
1 2
G1 G2

y130 y230
2 2
y13 y23

y130 y230
2 3 2

L
C nodo (P,Q)
The admittance matrix 44

Since the generation/demand is seen as external input to the network:

120 120
2 2
nodo (V, y12 nodo (P,V)
1 2
G1 G2

y130 y230
2 2
y13 y23

y130 y230
2 3 2

C nodo (P,Q)
The admittance matrix 45
Circuit theory method

• N buses interconnected by L branches can be represented through


the GRAPH of the network:

I1 I2
In the graph:
• One node is considered as refference for
the electrical potential (ground bus 0);
V2
V1 I3 • let Vp be the nodal electrical potential;
V3
• let Ip be the externally injected nodal
currents;
• finally, a convention for the orientation of
the currents circulating on the various
branches is adopted;

 In this way, an ORIENTATED GRAPH is obtained.


Electric Power Systems
The admittance matrix 46
Circuit theory method

•  Let us define:

 the column vector of nodal voltages with refference to bus 0


 the column vector of voltages across branches
 the diagonal matrix of branch admittances

For the given network: Let us define the set of nodes and branches of the network:

  { 1,2,3,0 }
ℵ=
ℬ=
  { (1,2 ) , ( 1 ,3 ) , ( 2 , 3 ) , ( 0 ,1 ) , ( 0 , 2 ) , ( 0 ,3 ) }

The order of the elements in the sets MUST be


V2 maintained when defining the matrices:
V1
  𝑉1
V3
[ 𝑉´ ] = 𝑉 2
𝑉3
0
[] it is an NX1 vector

Electric Power Systems


The admittance matrix 47
Circuit theory method

•  Let us define:

 the column vector of nodal voltages with refference to bus 0


 the column vector of voltages across branches
 the diagonal matrix of branch admittances

For the given network:

ℬ=
  { (1,2 ) , ( 1 ,3 ) , ( 2 , 3 ) , ( 0 ,1 ) , ( 0 , 2 ) , ( 0 ,3 ) }

  𝑣 21 𝑉 2−𝑉

[ ][ ]
1
𝑣31 𝑉 3 −𝑉 1
𝑣 𝑉 3 −𝑉 it is an LX1 vector
´ ] = 32 =
[𝑣 2
𝑣 01 −𝑉 1
it is defined
𝑣 02 −𝑉 2
according to the
𝑣 30 𝑉3 orientation of the
graph
Electric Power Systems
The admittance matrix 48
Circuit theory method
120 120
2 2
nodo (V, y12 nodo (P,V)
1 2
G1 G2

y130 y230
2 2
y13 y23

y130 y230
2 3 2

C nodo (P,Q)

ℬ=
  { (1,2 ) , ( 1 ,3 ) , ( 2 , 3 ) , ( 0 ,1 ) , ( 0 , 2 ) , ( 0 ,3 ) }

 
´𝑦 12 ¿ ¿ ¿ ´𝑦 13 ¿ ¿

[ ´𝑦 ]=
[ ¿ ´𝑦23

¿
Electric Power Systems
¿
¿
´𝑦 230 ´𝑦 120
2 2
+ ¿ ¿
¿ ¿
´𝑦 130 ´𝑦 120
2 2
¿
+ ¿
´𝑦 130 ´𝑦 23 0
2 2
+ ] it is an LXL matrix
The admittance matrix 49
Circuit theory method
120 120
2 2
nodo (V, y12 nodo (P,V)
1 2
G1 G2

y130 y230
2 2
y13 y23

y130 y230
2 3 2

C nodo (P,Q)

ℬ=
  { (1,2 ) , ( 1 ,3 ) , ( 2 , 3 ) , ( 0 ,1 ) , ( 0 , 2 ) , ( 0 ,3 ) }

 
´𝑦 12 ¿ ¿ ¿ ´𝑦 13 ¿ ¿

[ ´𝑦 ]=
[ ¿ ´𝑦23

¿
Electric Power Systems
¿
¿
´𝑦 230 ´𝑦 120
2 2
+ ¿ ¿
¿ ¿
´𝑦 130 ´𝑦 120
2 2
¿
+ ¿
´𝑦 130 ´𝑦 23 0
2 2
+ ] it is an LXL matrix
The admittance matrix 50
Circuit theory method
120 120
2 2
nodo (V, y12 nodo (P,V)
1 2
G1 G2

y130 y230
2 2
y13 y23

y130 y230
2 3 2

C nodo (P,Q)

ℬ=
  { (1,2 ) , ( 1 ,3 ) , ( 2 , 3 ) , ( 0 ,1 ) , ( 0 , 2 ) , ( 0 ,3 ) }

 
´𝑦 12 ¿ ¿ ¿ ´𝑦 13 ¿ ¿

[ ´𝑦 ]=
[ ¿ ´𝑦23

¿
Electric Power Systems
¿
¿
´𝑦 230 ´𝑦 120
2 2
+ ¿ ¿
¿ ¿
´𝑦 130 ´𝑦 120
2 2
¿
+ ¿
´𝑦 130 ´𝑦 23 0
2 2
+ ] it is an LXL matrix
The admittance matrix 51
Circuit theory method
120 120
2 2
nodo (V, y12 nodo (P,V)
1 2
G1 G2

y130 y230
2 2
y13 y23

y130 y230
2 3 2

C nodo (P,Q)

ℬ=
  { (1,2 ) , ( 1 ,3 ) , ( 2 , 3 ) , ( 0 ,1 ) , ( 0 , 2 ) , ( 0 ,3 ) }

 
´𝑦 12 ¿ ¿ ¿ ´𝑦 13 ¿ ¿

[ ´𝑦 ]=
[ ¿ ´𝑦23

¿
Electric Power Systems
¿
¿
´𝑦 230 ´𝑦 120
2 2
+ ¿ ¿
¿ ¿
´𝑦 130 ´𝑦 120
2 2
¿
+ ¿
´𝑦 130 ´𝑦 23 0
2 2
+ ] it is an LXL matrix
The admittance matrix 52
Circuit theory method
120 120
2 2
nodo (V, y12 nodo (P,V)
1 2
G1 G2

y130 y230
2 2
y13 y23

y130 y230
2 3 2

C nodo (P,Q)

ℬ=
  { (1,2 ) , ( 1 ,3 ) , ( 2 , 3 ) , ( 0 ,1 ) , ( 0 , 2 ) , ( 0 ,3 ) }

 
´𝑦 12 ¿ ¿ ¿ ´𝑦 13 ¿ ¿

[ ´𝑦 ]=
[ ¿ ´𝑦23

¿
Electric Power Systems
¿
¿
´𝑦 230 ´𝑦 120
2 2
+ ¿ ¿
¿ ¿
´𝑦 130 ´𝑦 120
2 2
¿
+ ¿
´𝑦 130 ´𝑦 23 0
2 2
+ ] it is an LXL matrix
The admittance matrix 53
Circuit theory method
120 120
2 2
nodo (V, y12 nodo (P,V)
1 2
G1 G2

y130 y230
2 2
y13 y23

y130 y230
2 3 2

C nodo (P,Q)

ℬ=
  { (1,2 ) , ( 1 ,3 ) , ( 2 , 3 ) , ( 0 ,1 ) , ( 0 , 2 ) , ( 0 ,3 ) }

 
´𝑦 12 ¿ ¿ ¿ ´𝑦 13 ¿ ¿

[ ´𝑦 ]=
[ ¿ ´𝑦23

¿
Electric Power Systems
¿
¿
´𝑦 230 ´𝑦 120
2 2
+ ¿ ¿
¿ ¿
´𝑦 130 ´𝑦 120
2 2
¿
+ ¿
´𝑦 130 ´𝑦 23 0
2 2
+ ] it is an LXL matrix
The admittance matrix 54
Circuit theory method

Moreover, let us define the incidence matrix [A]NxL

• For oriented graphs, it describes the topology of the network


• Matrix [A] has N rows an L columns

• It is built according to the following rule: its element aij is

 0 if branch j is not connected to bus i


 +1 if branch j exits bus i (the orientation of the branch, and hence of
the branch current, is “outwards” the bus)
 -1 if branch j enters bus i (the orientation of the branch, and hence of
the branch current, is “inwards” the bus)

Electric Power Systems


The admittance matrix 55
Circuit theory method

• For the considered example:

ℵ 

  → ( 1,2 ) ( 1,3 ) ( 2 , 3 ) ( 0,1 ) ( 0,2 ) ( 0,3 )

  −1 −1 0 −1 0 0 1

[
[ 𝐴 ]= 1
0
0
0
1
0
−1
1
0
0
0
1
−1
0
1
0
1
−1
] 2

• The last row is relevant to the reference bus and will not be
considered: it is a linear combination of the other rows.
Electric Power Systems
The admittance matrix 56
Circuit theory method

 Let us define the column vector


𝑇
[ ´𝑖 ] =[ 𝑖 21 𝑖 31 𝑖 32 𝑖 01 𝑖 02 𝑖 30 ]

as the vector of the branch currents


(according to the orientation of the graph)

The KCL can thus be written in matrix form as:

  𝑖2 1

[]
−1 −1 0 −1 0 0 𝑖3 1

[
[ 𝐴 ] ∙ [ ´𝑖 ] = 1
0
0
0
1
0
−1
1
0
0
0
1
−1
0
1
0
1
−1
𝑖
𝑖 01
𝑖 02
𝑖 30
]
∙ 32 =0

 Note that if the complete incidence matrix is used, the last


equation is linearly dependent on the other equations

Electric Power Systems


The admittance matrix 57
Circuit theory method

 Let us define the column vector


𝑇
[ ´𝑖 ] =[ 𝑖 21 𝑖 31 𝑖 32 𝑖 01 𝑖 02 𝑖 30 ]

as the vector of the branch currents


(according to the orientation of the graph)

Therefore, the reduced matrix will be used


instead:

  𝑖2 1

[]
𝑖3 1
−1 −1 0 −1 0 0

[
[ 𝐴 ] ∙ [ ´𝑖 ] = 1
0
0
1
−1
1
0
0
−1
0 1 ]𝑖
0 ∙ 32 =0
𝑖 01
𝑖 02
𝑖 30

Electric Power Systems


The admittance matrix 58
Circuit theory method
•  
• and vectors can now be linked:

[ 𝑣´ ] =[ 𝐴 ]𝑇 ∙ [ 𝑉´ ] = ¿

  −1 1 0 0 𝑉 2− 𝑉 1 𝑣 21 V2

[ ][ ] [ ] [ ]
𝑉1 𝑉 3− 𝑉 1 𝑣 31 V1
−1 0 1 0
𝑉2 𝑉 3− 𝑉 2 𝑣
¿ 0 −1 1 0 = = 32 V3
−1 0 0 1 𝑉3 −𝑉1 𝑣 01
0 −1 0 1 0 −𝑉2 𝑣 02
0 0 1 −1 𝑉3 𝑣 30

• Note that the last column does not influence the results as the electric
potential of the refference bus is 0.

Electric Power Systems


The admittance matrix 59
Circuit theory method

• Therefore, the previous expression can be written using the reduced A:

[ 𝑣´ ] =[ 𝐴 ]𝑇 ∙ [ 𝑉´ ] = ¿

  −1 1 0 𝑉 2−𝑉 1 𝑣 21 V2

[ ] [ ][ ]
𝑉 3− 𝑉 1 𝑣 31 V1
−1 0 1
𝑉1
¿ 0
−1
0
0
−1
0
−1
0
1
0
0
1
[]𝑉2
𝑉3
=
𝑉 3− 𝑉 2
−𝑉 1
−𝑉 2
𝑣
= 32
𝑣 01
𝑣 02
V3

𝑉3 𝑣 30

Electric Power Systems


The admittance matrix 60
Circuit theory method
•  Putting it all together
  𝐼1

[]
[ ´𝐼 ] = 𝐼 2 = [ 𝐴 ] ∙ [ ´𝑖 ]
𝐼3
I1 I2

where is the column vector of external


nodal current injections; its size is (N-1)X1 V2
V1
if the reduced matrix is used. I3

V3
• moreover

[ ´𝑖 ] =[ ´𝑦 ] ∙ [ 𝑣 ] =[ ´𝑦 ] ∙ [ 𝐴 ] 𝑇 ∙ [ 𝑉´ ]
• thus

[  ´𝐼 ] =[ 𝐴 ] ∙ [ ´𝑖 ] =[ 𝐴 ] ∙ [ ´𝑦 ] ∙ [ 𝐴 ] 𝑇 ∙ [ 𝑉´ ]

Electric Power Systems


The admittance matrix 61
Circuit theory method
• We
  have found a liniar relationship between
the vector of nodal voltages and the vector of
nodal current injections into the buses I1 I2

𝐼
 [ ´ ] =[ 𝐴 ] ∙ [ ´𝑦 ] ∙ [ 𝐴 ]𝑇 ∙ [ 𝑉´ ]
• we define the nodal admittance matrix as
V2
V1 I3
𝑇
 [ 𝑌
´ ] ≜ [ 𝐴 ] ∙ [ ´𝑦 ] ∙ [ 𝐴 ]
V3
• it’s a square matrix of size (N-1)X(N-1)

 [ 𝑌
´ ] ≜ [ 𝐴 ] ∙ [ ´𝑦 ] ∙ [ 𝐴 ]𝑇
[(N-1)XL] [LXL] [LX(N-1)]

• therefore

 ´
[ ] =[ 𝑌´ ] ∙ [ 𝑉´ ]
𝐼
Electric Power Systems
The admittance matrix 62
Circuit theory method
• For our example:

  −1 1 0
−1
[ 𝑌´ ] ≜ 1
[
0
−1
0
1
0
−1
1
−1
0
0
0
−1
0
0

1][
´𝑦 1
0 ∙ ¿
¿
¿
´𝑦 3
¿
¿
¿
´𝑦5
¿
¿
¿
´𝑦2
¿
¿
¿
´𝑦 4
¿
¿

]
¿ ∙
´𝑦 6
[ ]
−1
0
−1
0
0
0
−1
0
−1
0
1
1
0
0
1

 
´𝑦12 ¿ ¿ ¿ ´𝑦 13 ¿ ¿

[
´𝑦 1 ¿ ¿ ¿ ´𝑦 2 ¿ ¿
[ ´𝑦 ]= ¿ ´𝑦 3 ¿ ¿ ¿ ´𝑦 4 ¿ = ¿ ´𝑦 23
¿ ¿ ´𝑦 5 ¿ ¿ ¿ ´𝑦 6

Electric Power Systems


¿ ¿
] [
¿
𝑦´ 130 ´𝑦120
2 2
+
¿ ¿

¿ ¿
´𝑦 130 ´𝑦 120
2 2
+

¿
¿
´𝑦 130 ´𝑦 120
2 2
+ ]
The admittance matrix 63
Circuit theory method
• For our example:
1
1 2
2 3
 
3
4 6
5

• no matter the orientation of the graph branches, the result will be the
same
• for a system with N buses (N+1 buses with the ground bus), [Y] is an N
by N symmetric, sparse matrix: nonzero elements are in the position ij
only if bus i and bus j are directly connected

Electric Power Systems


The admittance matrix 64
Circuit theory method
• Another example example:

We can get similar relationships for buses 3 and 4


The results can then be expressed in matrix form
I  Y  V 
 I1  YA  YB YA YB 0  V1 
I   Y YA  YC  YD YC YD  V2 
 2   A  
 I3    Y B YC YB  YC 0  V3 
I   0 YD 0 YD  V4 
 4 

• no matter the orientation of the graph branches, the result will be the
same
• for a system with N buses (N+1 buses with the ground bus), [Y] is an N
by N symmetric, sparse matrix: nonzero elements are in the position ij
only if bus i and bus j are directly connected

Electric Power Systems


General Form of [Y] 65
Graph Inspection method

• The diagonal terms, Yii, are the self-admittance terms, equal to the
sum of the admittances of all branches incident to bus i

• The off-diagonal terms, Yij, are equal to the negative of the sum of
the admittances of the branches directly connecting the two buses i
and j

• With large systems, the fact that [Y] is a sparse matrix (that is, most
entries are zero) is a major advantage, from both the storage and
the computation time point of view

• Shunt terms, such as with the p line model, only affect the diagonal
terms

Electric Power Systems


Bus Admittance Matrix 66

• First step in solving the power flow is to create what is known as the
bus admittance matrix, often called the Y 

• It gives the relationships between all the bus current injections and
 I   Y  V 
bus voltages

• If all busses are considered, including the reference bus, Y  is


singular and its inverse does not exist

Electric Power Systems


Bus Admittance Matrix 67

If the voltages were known then we could immediately


find current injections:
 Y  V    I 
If current injections were known then we could
solve the linear system for voltages:
1
 Y   I   V    Z   I 
where  Z  is the bus impedance matrix

However the models we have assumed for the generators/demand


are constant power models; we cannot use this formulation
directly
Electric Power Systems

Potrebbero piacerti anche