Sei sulla pagina 1di 63

BELIN – OHNTAW LINE2

# Line Differential relay ( OPGW )

# Distance relay (Tele-prtoection via PLC )

# Single Phase Reclose

2.8.2018 AUNG KO HTAY ( EE )


Step Distance Protection

Z1 Z1
Z2 1 1 Z2
T2 T2
Z1 Z2
Z3 T3 T3 Z3
A B

Z1- 80% of Transmission Line ( T1- zero second )

Z2- 120% of Transmission Line ( T2- 400 ms )

Z3- 225% of Transmission Line ( T3- 1.67 s )


2
EXISTING DESIGN

3
EXISTING DESIGN

4
SINGLE POLE RECLOSE

5
SINGLE POLE RECLOSE

Dead time = 1.0 second


A
No Voltage Check / Synchro-Check
B

6
SINGLE POLE RECLOSE

7
SINGLE POLE RECLOSE

PERMANENT FAULT

8
SINGLE POLE RECLOSE

9
SINGLE POLE RECLOSE

10
SINGLE POLE RECLOSE

One Trial

11
SINGLE POLE RECLOSE

Lockout

12
SINGLE POLE RECLOSE

# One trial

# Single pole Circuit Breaker

# Aided Both Sides trip ( Tele-protection / Line Differential )

13
LINE DIFFERENTIAL RELAY

A B

TX RX
87L 87L
RX TX
ALSTOM P543

14
P543 CT wiring

15
P543 Tripping wiring

16
P543 Logic

17
P543 Communication Setting

18
P543 Protection Setting

19
P543 test

20
P543 Specification

Maximum Distance – 130 km


21
TELE-PROTECTION
Permissive Underreach Transfer Trip ( PUTT )

# Distance relay P442

# PLCC communication

22
Step Distance Protection

Z1 Z1
Z2 1 1 Z2
T2 T2
Z1 Z2
Z3 T3 T3 Z3
A B

Z1- 80% of Transmission Line ( T1- zero second )

Z2- 120% of Transmission Line ( T2- 400 ms )

Z3- 225% of Transmission Line ( T3- 1.67 s )


23
PUTT
SEND LOGIC : Z1
TRIP LOGIC : Rx + Z2

TX TX
RX RX
0 0
100 100
& &

Z1 Z1
Z2 1 1 Z2
T2 T2
Z1 Z2
Z3 T3 A B T3 Z3

24
PUTT

A G H J

INTERNAL FAULT

25
PUTT

Z2 G

A G Z2+RX H J

Z1 H

INTERNAL FAULT

26
PUTT

Z2 G

A G Z2+RX H J

Z1 H

INTERNAL FAULT

27
PUTT

Z2 G

A G H J

EXTERNAL FAULT

28
PUTT

Z2 G

A G H J

EXTERNAL FAULT

29
P442 Specification

30
Relay DI

CT

DI

PT

BUS PT
31
P442 DO

DO

32
P442 DO

33
P442 DI
P442 CRP CC

Selector Switch

CB open Switch

34
P442 PUTT Logic

35
P442 DO Logic - Tripping

36
P442 Led- Distance Trip

37
P442 DI Logic – P543 initiate

38
P442 DO Logic – Auto reclosing

Annunciator / buzzer : to alert operator

39
P442 DO Logic – Auto reclosing

AR successful

AR fail

40
P442 DI Logic – CB status

41
P442 DI Logic – Block AR

Selector Switch Contact

42
P442 DI Logic – CB manual open & Block AR

CB opening Switch Contact

Further study used for CB open or CB close

43
P442 DI Logic – CB Healthy
( spring charged / discharged )

44
P442 DI Logic – 1pole or 3pole AR

45
P442 DI Lables

46
P442 DI - DC Vtg

47
P442 DO - Lables

48
P442 Function Keys

49
P442 DO – AR setting

50
P442 Tele-Protection setting

51
P442 test

52
P442 PLCC

1 2

4 3

# Can use 48 Vdc field Vtg from P442 relay


53
P442 PLCC- signal send

54
P442 PLCC- signal received / carrier out of service
alarm

55
NCC

Z2 G
F-829519

A G H J

F-829519

Z1 H

LOOP NETWORK

56
NCC

Z2 G
F-829519

A G H J

F-829519

Z1 H

LOOP NETWORK

57
NCC

Z2 G

A G H J

F-829519

TR3-TPW

RADIAL LINE

58
NCC

Z2 G

A G H J

F-829519

TR3-TPW

# if 1pole Auto Reclose


RADIAL LINE
# Two phase energized in Transformer 1 second

Hint : 3 pole trip & AR block 59


To successful AR

# Earth fault Setting of OC/EF relay

# Pole dis-harmony timer ( 2 seconds )

60
Relay Leds

61
Relay Leds

62
THANKS

63