ABB RELAYS

NEUTRAL

AC
IMMUNISED
INTERLOCKED
ECRs
CONTACT RATING :
 Steady Current Load : AS PER IRS S 46
3 Amp continuously and 5 Amp for 30 seconds
AS PER IHC
6 AMP continuously
 Breaking Capacity : AS PER IRS S 46 2 Amp
AS PER IHC 2 Amp at 220 V 50 Hz
 CONTACT WIPING : >/= 0.1 mm
 LIFE EXPECTENCY : 1 Million Switching Cycle or 10
Years which ever earlier.
o All Relays are Type Tested by RDSO as per
IRS : S46, IRS : S34 and IRS : S23 ( as applicable)
TYPE TMA NEUTRAL LINE RELAY 60 V DC ( Non AC Immunised )
1 SPECIFICATION
1.1 RELAY TYPE : TMA 1144/111 - GUM
TMA 1153/111 - GUM
TMA 1162/111 - GUM
TMA 1126/111 - GUM
TMA 1124/111 - GUM
TMA 1122/111 - GUM
1.2 RELAY RATINGS : 60 V DC + OR - 20%.
1.3 CONTACT CONFIGURATION : 4F/4B ; 5F/3B ; 6F/2B ; 2F/6B ; 2F/4B ; 2F2B &
any other contact combination of 8 contacts.
1.4 RELAY MOUNTING : With or without plug-in-base & with socket
2 ELECTRICAL PARAMETERS
2.1 COIL RESISTANCE : 1550 Ω + OR - 10% AT 20° C.C.
2.2 PICK UP VALUE : < OR = 48 V DC & > OR = 16 mA.
2.3 DROP OFF VALUE : > OR = 12 V DC & 5 mA.
2.4 HIGH VOLTAGE TEST : 2 KV for sixty seconds (subsequent HV test,
Voltage to be 60% of 2 KV, i.e. 1.2 KV for 1-2
sec.)
2.5 INSULATION RESISTANCE : > OR = 50 M Ω at 500 V DC and during rainy
days it shall be > OR = 10 M Ω (as per clause
14.3.2.2 & 3 of IRS S23 (Part-II).
2.6 CONTACT RESISTANCE : < OR = 50 mΩ measured between contact
knives.
3 MECHANICAL PARAMETERS
3.1 CONTACT PRESSURE : Make contact in full operating and break
contact
in full release position to be checked. For
parameter ref. General Specification for Relays.
3.2 CONTACT CLEARANCE : > OR = 1.5 mm.
TYPE NEUTRAL LINE RELAY 60 V DC (AC Immunised)
1 SPECIFICATION
1.1 RELAY TYPE : TMA 1144/111 IM - GUM
TMA 1153/111 IM - GUM
TMA1162/111 IM - GUM
1.2 RELAY RATINGS : 60 V DC + OR - 20%.
1.3 CONTACT CONFIGURATION : 4F/4B ; 5F/3B & 6F/2B.
1.4 RELAY MOUNTING : With or without plug-in-base & with socket.
2 ELECTRICAL PARAMETERS
2.1 COIL RESISTANCE : 1720 Ω + OR - 10% AT 20° C.C.
2.2 PICK UP VALUE : < OR = 48 V DC & > OR = 20 mA.
2.3 DROP OFF VALUE : > OR = 12 V DC & 5 mA.
2.4 HIGH VOLTAGE TEST : 2 KV for sixty seconds (subsequent HV test,
Voltage to be 60% of 2 KV, i.e. 1.2 KV for 1-2sec.)
2.5 INSULATION RESISTANCE : > OR = 50 M Ω at 500 V DC and during rainy
days it shall be > OR = 10 M Ω (as per clause
14.3.2.2 & 3 of IRS S23 (Part-II).
2.6 CONTACT RESISTANCE : < OR = 50 mΩ measured between contact knives.
2.7 AC IMMUNITY LEVEL :
(1) Back contact will not break at 300 V AC applied across the coil.
(2) Front contact will not make at 750 V AC applied across the coil.
3 MECHANICAL PARAMETERS
3.1 CONTACT PRESSURE : Make contact in full operating and break contact
in full release position to be checked. For
parameter ref. General Specification for Relays.
3.2 CONTACT CLEARANCE : > OR = 1.5 mm.
Types of Relays

• NEUTRAL LINE RELAY 60 V DC (Non AC Immunised)

• NEUTRAL LINE RELAY 60 V DC (AC Immunised)

• NEUTRAL LINE RELAY 24 V DC (Non AC Immunised)

• MECHANICALLY INTERLOCKED RELAY 60 V DC

• MECHANICALLY INTERLOCKED RELAY 24 V DC

• AC LAMP PROVING RELAY FOR ‘ON’ASPECT WITH


INTERPOSING CURRENT TRANSFORMER
Types of Relays
• AC LAMP PROVING RELAY FOR ROUTE
INDICATOR WITH INTERPOSING
CURRENT TRANSFORMER
• AC LAMP PROVING RELAY FOR SHUNT SIGNAL
• WKR2 RELAY FOR POINT GROUP
• N/R RELAY FOR POINT CONTACTORUNIT
• KEY LOCK RELAY UNIT 60 V DC (AC Immunised)
• KEY LOCK RELAY UNIT 60V DC (Non AC
Immunised)
ACI Relay
 Lamp Proving Relay
• Interlocked Relay