Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Approved Materials
All materials and methods for
installation are to conform to
Chapter 6 of NFPA 13- 2007 or
the individual product listings
and approvals. When in
doubt……..
…Make the installing
contractor prove it to
your satisfaction!!!!
• If it looks incorrect, it probably is
• Be wary of new products, have
contractor provide cut sheets when in
doubt
• Good review with thorough walk
through at hydro at end of job
• Your interpretation of the codes
and standards is to be met or
proven incorrect- codes/
standards are in writing- not
inferred
• Sometimes corners are cut by
unscrupulous contractors
• Some poor installs are mistakes
or “human error” - BUT….
Report repeat
offenders to the
State Fire
Marshal’s office!!!
REMEMBER…
• You are the last line of defense to
ensure the end user gets what they
expect and paid for!!! These are your
customers, you are their expert!
• Poor installs fail annual inspections
and cost the owner money later for
repairs
Shall
3.2.4 “Indicates a mandatory
requirement.”
Should
3.2.5 “Indicates a recommendation
or that which advised but not
required.”
System Acceptance
For Environmentally
Sensitive Areas
Computer Rooms
Surgical Suites
Tele-Data Switch Rooms
Fine Art Storage Rooms
Pre Action System
Preaction Requirements
-24.2.3.3
• Hydrostatic and Cover
• Walkthrough and Final
– Operational (Alarms, Tamper, Main
Drain Test)
– Confirm Code compliance
– Ensure correct number of spare heads
are left on site per NFPA 13-2007
Section 6.2.9- Dry heads not required.
Sprinkler Wrench is.
Preaction Systems Also
Require
• Test the preaction valve operation in accordance with the
manufacturer’s instructions- ask for literature if there is any
questions on operation
• Test manual and remote control activation- this can be
electric, pneumatic or a combination
• Is the piping supervised? Sec.
7.3.2.4 requires supervision to
ensure system integrity.
• If supervisory air or nitrogen is
used- it needs to conform to 7.2.6
for dry systems…
– 30 minute refill requirement.
• Also needs to maintain a
minimum supervisory pressure of
7 psi.
Preaction Riser Reqt’s
• New systems to have White Tag and
Blue ITM Tag
• All additions over 20 heads are to have
a new white tag added
• Hydraulic Placard and General
Information Sign
• PRV test tags on each PRV
• Backflow certification and Inspection
by Plumbing Dept
Deluge System
For Highly
Flammable Areas
Aircraft Hangers
Solvent Processing
Dynamite Plants
Deluge System
Deluge System
Requirements -24.2.3.3
• Hydrostatic and Cover
• Walkthrough and Final
– Operational (Alarms, Tamper, Main
Drain Test)
– Confirm Code compliance
– Ensure correct number of spare heads
are left on site per NFPA 13-2007
Section 6.2.9- Dry heads not required.
Sprinkler Wrench is.
Deluge Systems Also
Require
• Test the deluge valve operation in accordance with the
manufacturer’s instructions- ask for literature if there is any
questions on operation
• Test manual and remote control activation- this can be
electric, pneumatic or hydraulic
• Flow Testing of the system to
ensure hydraulic performance.
Calibrated gauges are to be used
at different points on the system
• These gauge readings are to be
compared to the hydraulic
calculations
• Detection devices are to be
automatically supervised
Deluge Riser Reqt’s
• New systems to have White Tag and
Blue ITM Tag
• All additions over 20 heads are to have
a new white tag added
• Hydraulic Placard and General
Information Sign
• PRV test tags on each prv
• Backflow certification and Inspection
by Plumbing Dept
Standpipe System
For Multi-level
Buildings
Per AHJ
Stand Pipe System
Standpipe System Tests
•
and Requirements
Hydrostatic and Cover
• Walkthrough and Final
– Operational (Alarms, Tamper, Main
Drain Test)
– Confirm Code compliance and hose
thread compatibility
– Flow test through roof manifold testing
approved water source- fire pump, FD
pumper truck, etc.
• PRV tests. Ask for test log
• Main Drain flow tests- record on
material test certificate
• Dry and semi automatic shall be
trip tested to deliver 250 GPM at
the hydraulically most remote
hose connection within 3 minutes
• Air testing applies per dry
systems in NFPA 13
• Open and close each valve
manually- make sure hose caps
are on prior to testing
• Check for proper signage
Fire Pump
Fire Pump Tests and
Requirements
• Per NFPA 20- 2007 Edition
Chapter 14
• Piping to be hydrostatically
tested per NFPA 13 req’s
• All piping sizes to be verified per
table 5.25 (a) by rated pump flow
• All factory supplier
representatives are to be in
attendance during field
acceptance tests- AHJ should
be notified
• As a minimum, proof of the initial
startup and field acceptance test
report should be provided at Fire
Marshal final
• A copy of the certified pump test
characteristic curve shall be
available for comparison of the
field acceptance test.
• Compare the curves to ensure
the pump meets it’s factory
specs.
• Pump shall be run at minimum, rated
and peak loads
• How is this determined??
• Minimum is 0 GPM or churn
• Rated is the rating of the pump
– i.e.. 1000 GPM pump needs to be tested
at 1000 GPM
• Maximum is 150 % of pump rating- a
1000 GPM rated pump is capable of
1500 GPM flow
• Per NFPA 14- 2007, Section
6.2.1- Pumps shall furnish not
less than 150 percent of rated
capacity at not less than 65
percent of total rated head.
• 6.2.2- The shutoff head shall not
exceed 140 percent of rated
head for any type of pump.
Example 1- Pump is rated for 750
GPM @ 100 psi
150 percent of load-
1.5 X 750 =1125
65 percent of total rated head-
.65 X 100= 65 psi
Pump should provide 65 psi
MINIMUM at 1125 GPM
Example 2- Maximum Shutoff
100 psi Fire pump
• NFPA Codes: 13, 13R, 13D, 14, 20, 22, 24, 25 & 101
• UBC
• IBC
• IFC
• Local AHJ’s
• Other Jurisdictions – Architect, Engineer & Owner
• Insurance Underwriter
Post Construction Inspections and Maintenance