HANDS ON TESTING OF
TRANSFORMER
PROTECTION RELAY
Slope 1 =40%
Id Pick up .
• Also non directional High Set Value (110% of Max. Flt Current) with DT characteristic is
used as Back up
• Earth Fault :-
• 20% of Full Load Current is the Pick up value with TMS suitable to trip beyond Zone 3
timing of Downstream Lines.
• Here also Non Directional High Set function is used.
Testing of Over current and Earth Fault Relays
• For Over Current Inverse Characteristics is checked by Appling 2 time, 5 times and 10
times the set current and the Time delay is measured against the calculated value.
• Example :-
• Suppose PMS is 1.5 A Current Setting and TMS = 0.5
• OC and E /Fault Relays are tested for Pick up value and time delay set in EF relays is about
• Current Value Calculated Time Formula
• 2times 3A 5.01 sec t= TMS x (0.14/ (((1/Is)^0.02)-1))
• 5 times 7.5A 2.14 sec
• 10 times 15A 1.49 sec.
OVER FLUXING PROTECTION
Over Fluxing Protection- ?
• As per transformer design practice, flux density is kept about 1.7 to 1.8 Tesla,
while the saturation flux density is of the order of 1.9 to 2 Tesla which
corresponds to about 1.1 times the rated value.
• Above this design limit the eddy currents in the core and nearby conductive
components cause overheating which within a very short time may cause severe
damage.
• The flux in the core increases with either increasing voltage or decreasing
frequency.
2000
• Functions
• Basically Secondary Injection test set with various functions . Voltage &
Current Injection , Binary Inputs , Binary Outputs , Auxilliary DC /AC
Sources.
• Many Function Template is available with user settings- rio/Xrio file import
function.
• Capable for Fault replaying functions.
• Inbuilt automatic Protection for kit- overloading , short circuit etc.
• Portable and User friendly operation.