• General requirements
• Ventilation
requirements
• Construction and O/M
requirements
• Questions
62-2001
•Prescriptive
62-1999 •Commissioning
• IAQ-Health disclaimers •O&M
62-1981 • Smoking disclaimers •Combustion air
•Alternative • Clarified CO2 for use as •Filtration
Indoor Air Quality a ventilation metric
Procedure
62.1-2007
…updates
every 3 yrs 62.1-2013
62.1-2010
62-1989
• Removed Thermal 62.1-2004
Comfort •Commercial and high-rise residential
62-1973 • Ventilation Rate •Enforceable code language
…first issued Procedure •ETS ventilation rates not covered
• IAQ Procedure •Ventilation Rate Procedure modified
•Occupant and area ventilation rates
• Standard 62.1-2013 is the most current
version.
• IMC and UMC have adopted
methodology and rates.
• Several educational
courses are available
from ASHRAE.
§ 1.1 - Specify minimum ventilation rates
and other measures intended to provide
IAQ that is acceptable to human
occupants and that minimizes adverse
health effects.
§ 1.2 - Intended for regulatory application
to new buildings and additions.
§ 1.3 - Guide the improvement of IAQ in
existing buildings.
§ 2.1 - All spaces intended for human
occupancy excluding low-rise residential
(covered under Standard 62.2).
§ 2.2 - Defines requirements for ventilation,
air-cleaning design, commissioning,
installation and O&M.
§ 2.3 - Additional requirements and other
standards may apply (labs, healthcare,
industrial, etc.).
§ 2.4 - May be applied to both new and
existing buildings, not intended to be
used retroactively.
§ 2.5 - Does not prescribe specific
ventilation rates for smoking spaces.
§ 2.6 - Ventilation requirements based
on chemical, physical, & biological
contaminants.
§ 2.7 - Consideration or control of
thermal comfort is not included.
§ 2.8 - In addition to ventilation,
contains requirements related to
certain sources.
§ 2.9 - Acceptable IAQ may not be
achieved in all buildings meeting
these requirements because of:
– Diversity of sources and contaminants,
– Air temperature, humidity, noise,
lighting, and psychological/social
factors,
– Varied susceptibility in the occupants,
– Introduction of outdoor contaminants.
§ 4.1 - Regional Air Quality
– Must determine NAAQS
attainment status www.epa.gov.
– Air cleaning is required in some
cases in non-attainment areas.
§ 4.2 - Local Air Quality
– Conduct observational site
survey to identify local sources
of air contaminants.
§ 4.3 - Documentation
– Regional air quality compliance status.
– Local survey
information.
– Conclusions regarding
acceptability of
outdoor air quality.
§ 5.1 - Ventilation Air Distribution
– Must provide means to adjust the system.
– Ventilation air must be provided to terminal
units in plenum systems such that each space
receives the required minimum ventilation.
§ 5.2 Exhaust Duct Location
– Operate exhaust ducts with harmful
contaminants at negative pressure.
§ 5.3 Ventilation System Controls
– Control to assure proper ventilation under
any operating condition.
§ 5.4 Airstream Surfaces
– Use materials that have documented
resistance to microbial growth and erosion.
§ 5.5 - Outdoor Air Intakes
– Separate OA intake from outdoor
contaminant sources.
– Must comply with default minimum
separation distances in Table 5-1.
– Examples:
• Loading dock 25 ft
• Dumpster 15 ft
• Surface below intake 1 ft
• Cooling tower exhaust 25 ft
§ 5.5 - Outdoor Air Intakes (cont.)
– Must limit moisture penetration (using
hood, proper velocity, etc.) or manage
water that penetrates.
– Prevent moisture intrusion into
equipment mounted outdoors.
– Must use bird screens and prevent
bird nesting.
§ 5.6 - Local Capture of Contaminants
– Discharge air from non-combustion
equipment that captures contaminants shall
be exhausted to the outdoors.
§ 5.7 - Combustion Air
– Follow manufacturer’s instructions to provide
sufficient combustion air and exhaust air for
indoor fuel-fired appliances.
– Products of combustion from vented
appliances shall be vented directly outdoors.
§ 5.8 - Particulate Matter Removal
– Use a filter with a rating of MERV 8 (or
greater) upstream of cooling coils and
other wetted-surface devices in supply
stream.
§ 5.9 - Dehumidification Systems
– Must limit indoor RH to 65% or less at
design dew point condition.
• Exception to RH limit - where occupancy
requirements or processes dictate higher
RH conditions .
62°F DP
§ 5.10 - Drain Pans
– Assure drainage without flooding or
carryover.
– Slope: 0.125” (⅛”) per foot toward outlet.
– Drain: located at lowest point, with
sufficient diameter to prevent overflow.
§ 5.10 - Drain Pans (cont.)
– Drain seal: Shall include P-trap or other
seal for negatively pressurized drain
pans to prevent ingestion of air while
allowing complete drainage (fan on or
off).
– Pan size: length at least 1/2 coil height
or as necessary to limit water droplet
carryover.
§ 5.11 - Finned Tube Coils and Heat
Exchangers
– Provide drain pan beneath all dehumidifying
cooling coil assemblies and all condensate
producing heat exchangers.
– Select to limit coil pressure drop to 0.75”
w.c.@ 500 fpm face velocity.
• Exception - higher pressure drop can be
accommodated by providing access on both sides
and providing clear and completed instructions for
maintenance
§ 5.12 - Humidifiers and Water Spray
Systems
– Use potable water (or better).
– No downstream devices within
absorption distance.
• Exception - devices or obstructions
provided with appropriate drain pan.
§ 5.13 - Access for Inspection,
Cleaning and Maintenance.
– Install equipment with sufficient working
space for access and maintenance
– Provide access doors, panels or other
means to allow convenient and
unobstructed access for maintenance
of the HVAC system
§ 5.14 - Building Envelope and
Interior Surfaces
– Weather barrier to prevent water
penetration into envelope.
– Vapor retarder or other means to
prevent condensation on cold
surfaces within envelope.
§ 5.14 - Building Envelope and Interior
Surfaces (cont.)
– Seal all exterior seams, joints,
penetrations to limit infiltration.
– Insulate pipes, ducts expected to have
surface temperature below surrounding
dew point.
§ 5.15 - Buildings with Attached
Parking Garages
– Limit infiltration of vehicular exhaust:
• Maintain garage pressure at or below
adjacent occupied space,
• OR, use a vestibule,
• OR, otherwise design to minimize air
migration from garage to occupied space.
§ 5.16 - Air Classification and Recirculation.
– Designate expected air quality classification
for all return transfer or exhaust air (refer to
table 5.2, 6.1 and 6.4 for examples of air
classes):
• Class 1: Low contaminant concentration
• Class 2: Moderate concentration
• Class 3: Significant concentration
• Class 4: Highly objectionable or potentially
harmful concentration.
• Recirculation limitations:
– Class 1 to anywhere,
– Class 2 to self, similar Class 2 or Class
3 or Class 4,
– Class 3 to self,
– Class 4 to outdoors.
• Re-designation of air classes:
– Air Cleaning - may allow re-designation of
the air to a cleaner classification.
– Transfer - a mixture of air with different
classes shall be re-designated with the
highest class of classification among the air
classes mixed.
– Energy Recovery - energy recovery from
class 2 (exhaust) airstreams must have ≤10%
leakage into a class 1 airstream.
§ 5.17 - Requirements for buildings
containing ETS areas and ETS-free
areas.
Note: Does not purport to achieve acceptable IAQ in ETS
areas.