1.Cable Selection Guide


2. Load Schedule
3. Cable Voltage Drop
 CABLE SELECTION GUIDE

 Cable Ampacity

 3.10.1.15(b) -Ampacities of conductor rated 0 -2000V


shall be as specified in the allowable Table 3.10.1.16 -60
to 90 degC, not more than three conductor in raceway
based at 30 degC.

 2.10.2.1 -Conductor minimum ampacity allowed for


branch circuit shall not be less than the non-continuous
load plus 125% of the continuous load

 3.10.1.5 -Minimum size of conductor shall be as shown


Table 3.10.1.5 1-2000V 2.0mm2 Copper, 8001 -15000V
30mm2 28,001V -35,000V -50mm2 copper

 Table 3.10.1.15(b)(2)a –Adjustment Factor for more than


three conductor in a raceway.

 4 –6 conductor -80%

 7 –9 conductor -70%

 Note : Correction Factors as per PEC

 1. Ambient Temperature Correction Factor

 2. Cable Laying Factor

 Ex. A 3 -250mm2 THHN Cable in raceway

 Table 3.10.1.15 = 400A

 Ambient Temperature 36 to 40 deg. = 0.91

 Cable Laying Factor = 100%

 250mm2 Ampacity = 400 x 0.91 x 1

 = 364 A
CABLE SELECTION GUIDELINES:
Cable Tray Article 3.92
3.91.1.3 Single conductor cable shall me
50mm2 or larger
Single conductor use as grounding shall
be 22mm2 or larger
3.92.1.11(b) (1) Single-Conductor Cable
allowable ampacity use Table 3.10.1.17 (
Free Air )
3.91.1.11(a) Multi Conductor Cable
allowable ampacity use Table 3.10.1.16
( commonly called royal cord, RC, use TW
column )
Cable Location
3.10.1.8 –Type of Location,
Dry -use any type on the code
Dry and Damp –use THHN, THW, THWN,
THHW-2, THWN-2, TW
Wet Location –use TW, THW, THHW, THHW-
2, THWN
Load Calculation Parameters for Lighting Panelboard :

Use Table 2.20.2.3 – General Lighting Loads by Occupancy

For Dwelling Units use 0.024kVA per sq.m ,for Industrial, commercial building use
0.016kVA per sq.m.

Use actual manufacturer’s data for very large area.

Use 0.18kVA for duplex outlet, PEC 2017,2.20.2.5(i), 0.090kVA per four or more
receptacle in one yoke or 0.011kVA persq.m,PEC1,20092.20.2.5(k).

For Branch Circuit, use 20A maximum over-current circuit protection for lighting and
receptacle.

For Feeder Current, consider load as continuous load:

I3Ø=√3(Highest I1ØLOAD) + I3ØLOAD

Ifeeder=125% x I3Ø PEC 2017 2.10.2.1(a1)

The tables were derived for PEC 2017,Table 3.10.1.16 and Table 3.10.1.17 with
applied derating factor.

For grounding conductor use Table 2.50.6.13 from PEC 2017

For over-current protection use Inverse Time Molded Case Circuit Breaker.

MCCB=I3Ø x 125%
Load calculation parameters for Air-Conditioning and
Motor Loads :

Use the nameplate rating supplied by manufacturer as


reference for air-conditioning rated current.
For motor loads, PEC 2017, Table4.30.14.4. was used .for
the IFLC of the motor.
For over-current protection for individual hermitic
refrigerant motor-compressor , PEC 2017 4.40.2.2(a)1

I Overload = I3Ø FLA x 115%

For short circuit and ground fault protection

IMCCB = I3Ø FLA x (175%-225%)

For Feeder Current, consider load as continuous load

Ifeeder = 125% x I3Ø PEC 20172 .10.2.1(a1)

For grounding conductor useT able 2.50.6.13 from PEC


2017
PEC 2009, Article 4.30 –Motors,
Motor Circuits, and Controllers

LIST OF PEC PROVISIONS :


OVERCURRENT PROTECTION

CABLE SIZE
DESIGN OF MOTOR CONTROL BASED ON PEC
2017
Given :
1 –1HP / 0.75kW Induction Motor, 230V 3P
1 –7.5HP / 5.5kW Induction Motor, 230V 3P
1 –3HP / 2.2kW Induction Motor, 230V 3P
Voltage Drop Calculation
a) Voltage Drop Calculation 3ø

VD3ø = √3 x I x L/305 x S ( Rcos ø + X sin cos-1 ø )


Where :
R is in Ω/305 m PEC 2017, Table 9.1.1.9
X is in Ω/305 m PEC 2017, Table 9.1.1.9
Cos ø = 0.80
S is the number of parallel cable
b.)VoltageDropCalculation1ø
VD1ø = 2 x I x L/305 x S ( Rcos ø + X sin cos-1 ø )
Where :
R is in Ω/305 m PEC 2009, Table 9.1.1.9
X is in Ω/305 m PEC 2009, Table 9.1.1.9
Cos ø = 0.80
S is the number of parallel cable

PEC 2017 2.10.2.1 (a1) FTN NO. 4, Conductor for branch circuit
must be sizes to preventvoltage drop exceeding 3% to the
farthest load and the voltage drop for the feeder and branch
circuit does not exceed 5%
Voltage Drop Calculation

c.)Voltage Drop Calculation

R Ω/305= 0.0350 Ω/305 ;

X Ω/305m= 0.0400 Ω/305

Length (m)= 62 m;

I = 841.99 A

S = 3 per phase

VD = √3 x I101 x L/305 x S ( R cos ø + X sin cos-1 ø )

= √3 x 841.99 x 62/305 x 3 ( 0.0350 (0.8) +

0.0400 sin cos-1 0.8 )

= 5.14 V

%VD = VD / 220 x 100 = 2.33% <3%