ONE UNIT = INFINITE POSSIBILITIES:
the easYgen™- 3000
Proprietary Information
Current and Future Part Numbers P2
easYgen-3000 Terminal Comm. 1A CT 5A CT 1A CT 5A CT
Platform Blocks Ports P2 P2
RP-3000 2 1 No No No No
(Remote Panel)
easYgen-3100 80 4 8440-1819 8440-1817 8440-1844 8440-1845
Proprietary Information
Application
Single Unit Mains Parallel
• Engine start / stop
• Generator protection
• AMF (auto mains failure)
• Generator control
• Frequency / active power
• Voltage / power factor
• Parallel to mains
• Full Generator Breaker Control
• Full Mains Breaker Control
Proprietary Information
No external mains
breaker control module
required. Mains CT and
Application
PT will connected to all
easYgen-3000.
Redundant Multiple Unit Mains Parallel
protection/control over
the Mains Breaker.
Proprietary Information
Terminology Overview
• FlexAppTM Multiple breaker operation application setups in one unit:
No breaker, GCB o/, GCB o/c, GCB & MCB o/c*
• FlexRangeTM Allows for the control to operate on a wide range
of PT voltage inputs and CT configurations
• FlexInTM The controller analog inputs are compatible with both
resistive and mA signals permitting the use of a wide
range of sending units
• LogicsManagerTM Configurations, operating sequences, and operating
modes can be modified through the use of logical
operators, timers, internal and external status
• Analog ManagerTM Analog signals can be monitored and sent to an output
(metered values, bias signals for control purposes)
• FlexLimitsTM Free running and programmable analog limit switches
extend the quantity of trip levels or actuation triggers
• FlexCANTM Utilizes CANopen and J1939 protocols
Proprietary Information
Features – Engine Control
• Stop, Manual, Automatic modes • Crank control and
protection
• Start / stop by
discrete inputs, interface, frontpanel, • Aux. excitation for
analog inputs ... alternator via D+
• ECU J1939 CAN connection for termimal
Monitoring • Aux. services for pre-
Visualization and postrun
Control
• Counters for running
• Override mode for critical operation
hours , service
• Speed sensing/monitoring via MPU requests,...
• Redundant relay outputs for safety
considerations (breaker, gas
valves,...) via LogicsManager
Proprietary Information
Features – Engine Control
Start-Stop-Management
Proprietary Information
Features – Breaker
Breaker Synchronization Modes
No breaker, GCB, MCB Phase matching
Slip frequency synch.
Breaker modes Synch. check option
Parallel
Open transition Protection
Closed transition Synch Time Out
Interchange (Soft transfer) Close Time Out
External (No breaker ops.) Open Time Out
Field rotation monitoring
Proprietary Information
Features – Controllers
Droop can be
activated/deactivated AVR and Governor Control Signals
via LogicsManager
output status
Frequency Two setpoints for each controller
Load sharing Internal setpoints
Isochronous Interface
Droop Discrete Inputs (discrete raise/lower)
Voltage Analog inputs (by mA, by potentiometer)
Reactive (var) sharing Bias outputs (for AVR & Governor)
Isochronous Adjustable analog bias signal between
+/-20 mA or +/-10 V
Droop
PWM output
Load control
Relay outputs raise/lower (3-step-Logic)
Baseload
Analog bias and raise/lower outputs are
Export/Import separately configurable for V, var, f and
kW. (=> dual fuel capability)
Power Factor
Constant Proprietary Information
Features - LogicsManagerTM
Configuration and modification of sequences and operation modes by
using logical operators, timers, internal and external status conditions.
Proprietary Information
Discrete Inputs / Outputs
12 x Relay Outputs Expansion with external DI/DO boards
• Alarm and control • Maximum 16 DI/16 DO
• 6 single-pole contacts • Woodward IKD 1
• 6 two-pole contacts • Phoenix
• Max 2A @ 24Vdc/250Vac
12 x Discrete Inputs
• Alarm and control (isolated)
• Configurables: Timers, alarm
classes, text
Proprietary Information
Analog Inputs / Outputs
3 x Analog Inputs 1 x Battery Voltage
• 0 to 500 Ohm or 0/4 to 20 mA • Monitoring of power supply 8 to 40 Vdc
• Change between different
senders via parameter P2 External analog input module
• 1- and 2-wire senders compatibility
supported
• 11 bit resolution
• Configurables: Timers,
alarm classes, text
1 x Auxiliary Excitation D+
• Input: Sensing and monitoring of
excitation voltage
• Output: Supplying excitation
voltage (via internal shunt
resistor)
Proprietary Information
Voltage Sensing - Generator and Mains
3Ph4W (3phase, 4wire) 3Ph3W (3phase, 3wire)
1-, 2- and 3-phase CT arrangement possible & configurable for each phase
FlexRangeTM
1Ph3W (1phase, 3wire) 1Ph2W (1phase, 2wire)
only 2-phase CT possible only 1-phase CT possible
Proprietary Information
AC Generator sensing
True RMS Voltage Sensing True RMS Current Sensing
• 4-phase (L1, L2, L3, Neutral) • 3-phase
• 100 and 400 V input • Non-returning slave pointer
• Frequency measurement • 1% accuracy
• Field rotation detection
• 1% accuracy Power Sensing
• Phase-to-Phase measurement • 2% accuracy
• Phase-to-Neutral measurement • True RMS power measuring
• 3ph3w, 3ph4w, 1ph2w, or 2ph3w • Real and reactive power
Proprietary Information
DynamicsLCDTM
Multiple languages – 10 standard
English Turkish
German Portuguese
Italian Russian
French Chinese
Spanish Japanese
Proprietary Information
DynamicsLCDTM
Italian
French
Spanish
Turkish
Portuguese
Proprietary Information
DynamicsLCDTM
Chinese
Russian
Japanese
Proprietary Information
DynamicsLCDTM
The 320x240 pixel graphic interactive LC display provides soft keys with
changing functionality depending on application (see FlexAppTM) and operation.
Proprietary Information
DynamicsLCDTM
The display sections:
Last alarm
Current operation
i.e. cranking, loading,
start pause, etc.
Proprietary Information
DynamicsLCDTM
Operating modes
Automatic mode
Manual mode
Stop mode
Proprietary Information
DynamicsLCDTM
Symbols in the Single Line Diagram
Proprietary Information
DynamicsLCDTM
Proprietary Information
DynamicsLCDTM
Alarm screen Event History
• Active alarms visible • In-/ out coming events (+ / -)
• Date and time stamped • Date and time stamp
• 16 entries displayed • 300 entries (FIFO)
Proprietary Information
Alarm Classes
Alarm Classes are configurable for almost all protection functions
Class Action Result
Display Warning
Display and Horn Unload Gen. and open GCB Cool down Shut down
Display and Horn Open GCB immediate Cool down Shut down
Display and Horn Unload Gen. and open GCB Immediate Stop Shut down
Display and Horn Open GCB immediate Immediate Stop Shut down
Proprietary Information
Generator Protection
# of Trip Levels ANSI Code
• Power factor (PF) lagging 2
• PF leading – loss of excitation 2 [40Q]
• Phase rotation field CW/CCW 1
• Psetpoint Pactual mismatch 1 Controller*
• Unload mismatch (time out monitoring) 1 Controller*
• Operating range failed 1 Controller*
Proprietary Information
Engine Protection
• Maintenance days exceeded
• Maintenance hours exceeded
• Over-/Underspeed (MPU)
• Unintended Stop
• Engine Stop malfunction
• Speed/frequency mismatch
• Start failure
• Charge alternator low voltage
• Red stop lamp (J1939)
• Amber warning lamp (J1939)
• Battery over-/undervoltage
Proprietary Information
Mains Monitoring and Decoupling
# of Trip Levels ANSI Code
• Over-/undervoltage 2/2 [59/27 ]
• Over-/underfrequency 2/2 [81O/U]
• Import/Export power 2 [32]
• Power factor leading 2 [55]
• Power factor lagging 2
• Phase shift 1ph/3ph [78 ]
• Phase rotation
Proprietary Information
Miscellaneous Monitoring
• GCB / MCB fail to close
• GCB / MCB fail to open
• Synch. Time Out GCB / MCB
• Phase rotation mismatch generator / busbar / mains
• Mains decoupling
• CAN bus communications monitoring (J1939, CANopen)
• Parameter alignment (multiple units)
• Missing members (multiple units)
• EEPROM failure (internal CPU)
• Wire break analog inputs
• Discrete inputs
• FlexLimitsTM for analog values Proprietary Information
Interfaces
• ToolKit
• Load share
• Modbus
• CANopen
Serial 1
CAN 1 RS-232
Serial 2
CAN 2
RS-485
• Extension cards • Modbus
(IKD 1, Phoenix)
• J1939 ECU
Engine level
• J1939 (ECU) 2x IKD 1 Phoenix
ECU
ECU
GATEWAY
GATEWAY
P2
ENGINE GENERATOR
-Engine -Generator
Proprietary Information
Phoenix J1939
Serial Interface Overview
Serial 1
Serial RS-232
RS-232
Serial RS-485
Serial 2
PLC RS-485
Profibus
• Modbus
• Multiple units
PC
Proprietary Information
Configuration via ToolKit
RS-232 or CAN
Serial 1
RS-232
Proprietary Information
Miscellaneous
• CE marked
• UL listed
1 x CD with
Woodward ToolKit v3.0 configuration program
ToolKit *.WTOOL files (English and German)
ToolKit *.SID files (English and German)
Manuals
Proprietary Information
Remote Panel 3000
Remote Panel RP-3000
• CANopen connected panel to all easYgen-3000 controls
• Point-to-point connection
• Same look and feel as easYgen-3200
easYgen-3000 controls
CANopen
RP-3000
Proprietary Information
easYgen-3100
easYgen-3100 (1A CT and 5A CT model)
• Metal housing: no display, HMI via interfaces and DI
• Same functionality as easYgen-3200
Proprietary Information
easYgen-3000/P2 Features
Extended I/O Via External Terminals
P2
only
Proprietary Information
easYgen-3000/P2 Features
P2
only
Extended I/O Via External Terminals
• 48 x Analog Inputs
- 32 x Inputs via predefined J1939 engine messages in 10 languages
- 16 x Inputs via CANopen terminals
Proprietary Information
3rd Party Accessories
P2
Accessories easYgen-3000/P2 only
CANopen Bus Coupler
IL CAN BK-TC-PAC [#2718701] (max 3 possible)
Analog Inputs
IB IL AI 2/SF-PAC [#2861302] 2x analog (0-20 mA, 4-20 mA, ±20 mA, 0-10 V, ±10 V)
IB IL TEMP 2 UTH-PAC [#2861386] 2x thermocouples
IB IL TEMP 2 RTD-PAC [#2861328] 2x RTDs, resistive senders
Analog Outputs
IB IL AO 2/SF-PAC [#2863083] 2x analog outputs (0-20 mA, 4-20 mA, 0-10 V)
Phoenix part numbers in brackets
Proprietary Information
3rd Party Accessories
P2
Accessories easYgen-3000/P2
only
J1939 Analog Inputs
TC 4 [#AXTC4] 4x thermocouples
TC 20[#TC20] 20x thermocouples
Analog input 10 [#AX030100] freely configurable, for advanced J1939 users only
Axiomatic part numbers in brackets
Proprietary Information
Accessories
Proprietary Information
3rd Party Accessories
Accessories easYgen-3000 all types
CANopen bus coupler
IL CAN BK-TC-PAC [#2718701] (max 3 possible)
Proprietary Information
Product Documentation
Product Specification
[P/N 37258]
Proprietary Information
End of Section 1
1 Overview 6 LogicsManager
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
Proprietary Information
easYgen-3200 Training
Section 2 – Hardware and I/O
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
Introduction slide 3
Power Supply 4
MPU Input 5
FlexRangeTM 6
Discrete Inputs 20
Discrete Outputs 22
FlexInTM 25
Analog Outputs 29
Auxiliary Excitation D+ 31
Technical Data 32
Proprietary Information
Introduction
Introduction
FlexRangeTM
Power Supply
The voltage measuring inputs of the easYgen-3000 permit the user to
MPU Input
customize the controller for use with a wide range of voltage potential
FlexRangeTM
transformers and system configurations. Each control has two sets of PT
Discrete Inputs inputs (100 Vac and 400 Vac), with configurable ranges.
Discrete Outputs
The CT inputs may be configured for any combination of monitoring and
FlexInTM protection schemes to provide the highest level of flexibility possible for
Analog Outputs the user.
Aux Excitation D+
Technical Data
FlexInTM
Programming created by Woodward that permits the user to configure the
analog inputs of the easYgen-3000 series to work with a wide range of
resistive and/or current (mA) senders.
56
Proprietary Information
Power supply
Introduction
Discrete Outputs
57
Proprietary Information
Pickup Input MPU
Introduction The MPU input (Magnetic Pickup Unit) measures the engine
Power Supply
speed by counting the teeth of the flywheel.
MPU Input • The number of teeth is adjustable
FlexRangeTM
• Switching or inductive senders may be used
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
58
Proprietary Information
Flex Range
Measuring
Introduction
True RMS measurement of the generator, mains and busbar voltage
Power Supply
measuring inputs
MPU Input
- Rated 100 Vac (max. 150 Vac) and
FlexRangeTM
- Rated 400 Vac (max. 600 Vac)
Discrete Inputs
Analog Outputs
Aux Excitation D+
Technical Data
59
Proprietary Information
Flex Range - 3Ph4W
3Ph4W (3phase, 4wire)
Introduction 1- or 3-phase voltage measurement possible
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Generator voltage measurement 3PH4W
Technical Data
Mains voltage measurement 3PH4W
“Busbar” 1PH2W voltage measurement
Phase – Phase L1 - L2 or
60 Phase – Neutral L1 - N
Proprietary Information
Flex Range - 3Ph4W
3Ph4W (3phase, 4wire)
Introduction
L1 L2 L3 N
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
G
61
Proprietary Information
Flex Range - 3Ph4W
3Ph4W (3phase, 4wire)
Introduction 1- or 3-phase current measurement possible
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Generator current measuring L1 L2 L3 or
Technical Data
L1 or L2 or L3
62
Proprietary Information
Flex Range - 3Ph4W
3Ph4W (3phase, 4wire)
Introduction Measured values in the display
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
63
Proprietary Information
Flex Range - 3Ph3W
3Ph3W (3phase, 3wire)
Introduction 1- or 3-phase voltage measurement possible
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Generator voltage measurement 3PH3W
Technical Data
Mains voltage measurement 3PH3W
“Busbar” 1PH2W voltage measurement
Phase – Phase L1 – L2
64
Proprietary Information
Flex Range - 3Ph3W
3Ph3W (3phase, 3wire)
Introduction
L1 L2 L3
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
G
65
Proprietary Information
Flex Range - 3Ph3W
3Ph3W (3phase, 3wire)
Introduction 1- or 3-phase current measurement possible
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Generator current measuring L1 L2 L3 or
Technical Data
L1 or L3
66
Proprietary Information
Flex Range - 3Ph3W
3Ph3W (3phase, 3wire)
Introduction Measured values in the display
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
67
Proprietary Information
Flex Range - 1Ph3W
1Ph3W (1phase, 3wire)
Introduction only 2-phase voltage measurement possible
Power Supply
MPU Input
FlexRangeTM
jumper
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Generator voltage measurement 1PH3W
Technical Data
Mains voltage measurement 1PH3W
“Busbar” 1PH2W voltage measurement
Phase – Neutral L1 - N
68
Proprietary Information
Flex Range - 1Ph3W
1Ph3W (1phase, 3wire)
Introduction only 1- or 2-phase current measurement possible
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Generator current measuring L1 L3 or
Technical Data
L1 or L3
69
Proprietary Information
Flex Range - 1Ph3W
1Ph3W (1phase, 3wire)
Introduction Measured values in the display
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
70
Proprietary Information
Flex Range - 1Ph2W
1Ph2W (1phase, 2wire)
Introduction only 1-phase voltage measurement possible
Power Supply
MPU Input
FlexRangeTM
jumper
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Generator voltage measurement 1PH2W
Technical Data
Mains voltage measurement 1PH2W
“Busbar” 1PH2W voltage measurement
Phase – Neutral L1 - N
71
Proprietary Information
Flex Range - 1Ph2W
1Ph2W (1phase, 2wire)
Introduction only 1-phase current measurement possible
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Generator current measuring L1
Technical Data
72
Proprietary Information
Flex Range - Ground current
Parameter: Mains current input = Ground current
Introduction
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
Examples
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
73
Proprietary Information
Discrete Inputs
Introduction
Discrete I/O
Power Supply
• 12 discrete inputs (alarm and control)
MPU Input
• Expansion with external boards
FlexRangeTM - 2x Woodward (IKD) or
Discrete Inputs - 1x Phoenix
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
74
Proprietary Information
Discrete Inputs
Common for DI 1 – 12
May use either + or – polarity
DI is energized if voltage is measured between
Introduction
the input terminal and terminal 66
Power Supply
1 Emergency Stop
MPU Input
2 Start in Auto
FlexRangeTM
3 Low oil pressure
Discrete Inputs
4 Coolant temp.
Discrete Outputs
5 Ext. acknowledge
FlexInTM
6 Release MCB
Analog Outputs 7 Reply MCB is open
Aux Excitation D+ 8 Reply GCB is open
10 Discrete input
11 Discrete input
12 Discrete input
MPU Input
FlexRangeTM
Device ok
Discrete Inputs
Horn
Discrete Outputs
Crank
FlexInTM
Analog Outputs
Fuel valve
Aux Excitation D+
Technical Data
Preglow
76
Proprietary Information
Discrete Outputs
Max 250 V AC/DC
Discrete outputs 6 through 9
Introduction
Power Supply
Max 2 A each contact
MPU Input
FlexRangeTM
FlexInTM
GCB open
Analog Outputs
Aux Excitation D+
MCB open
77
Proprietary Information
Discrete Outputs
Discrete outputs 10 through 12
Introduction
Power Supply
Lube pump
MPU Input
Warning signal
FlexRangeTM
Discrete Inputs
Shutdown signal
Discrete Outputs
FlexInTM
Analog Outputs
Max 2 A each contact
Aux Excitation D+
Technical Data
78
Proprietary Information
FlexInTM
Analog inputs
Introduction
3 analog inputs
Power Supply
• programmable as 0 to 500 Ohm or 0/4 to 20 mA
MPU Input
FlexRangeTM
VDO / resistive input (0 to 500 Ohm) 1- or 2-pole sender
Discrete Inputs
• 0 to 5 bar (0 to 75.5 psi)
Discrete Outputs • 0 to 10 bar (0 to 145 psi)
FlexInTM • 40 to 120 °C (104 to 248 °F)
Analog Outputs • 50 to 150 °C (122 to 302 °F)
Aux Excitation D+
• Linear 2-point, adjustable min/max value
• User defined – 9-point curve
Technical Data
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
80
Proprietary Information
FlexInTM
Introduction
Discrete Inputs
Discrete Outputs
FlexInTM
81
Proprietary Information
FlexInTM
Introduction
MPU Input
Numeric and graphical
FlexRangeTM
Text for input
Discrete Inputs description is
Discrete Outputs
configurable
FlexInTM Bar graph
Analog Outputs min / max value
Aux Excitation D+
Technical Data
82
Proprietary Information
Analog Outputs
Introduction
Two analog outputs
Power Supply
• +/- 20mA or
+/-20mA
MPU Input • +/- 10V or
FlexRangeTM
• PWM (500 Hz)
Discrete Inputs
Discrete Outputs
+/-10V
FlexInTM Output signals
Analog Outputs
• speed bias (governor)
Aux Excitation D+
jumper
• voltage bias (AVR)
Technical Data
• measured values
PWM
– Generator kW
– Power factor
83
Proprietary Information
Analog Outputs
11/12 bit resolution =
Signal Options:
Introduction 102.4 steps / mA or
• OFF
204.8 steps / V
Power Supply • User defined (maximum +/- 20mA and +/- 10V)
MPU Input • 0-10mA / 0-5V
• 0-20mA / 0-10V
FlexRangeTM
• 4-20mA
Discrete Inputs
• 0.5-4.5V
Discrete Outputs • 10-0mA / 5-0V
FlexInTM
• 20-0mA / 10-0V
• 20-4mA
Analog Outputs
• 4.5-0.5V
Aux Excitation D+ • +/-1 V
Technical Data • +/- 2.5 Actual output signal
• +/- 3V
% in relation to the
• +/-10mA / +/-5V
• +/-20mA +/-10V
configured range
FlexRangeTM
the engine
• Measures the D+ voltage after startup of the engine
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
85
Proprietary Information
Technical Data
Technical specifications can be found in the “Installation” manual
Introduction
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
86
Proprietary Information
Technical Data
Technical specifications can be found in the “Installation” manual
Introduction
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
87
Proprietary Information
Technical Data
Technical specifications can be found in the “Installation” manual
Introduction
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
88
Proprietary Information
Technical Data
Technical specifications can be found in the “Installation” manual
Introduction
Power Supply
MPU Input
FlexRangeTM
Discrete Inputs
Discrete Outputs
FlexInTM
Analog Outputs
Aux Excitation D+
Technical Data
89
Proprietary Information
End of Section 2
1 Overview 6 LogicsManager
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
90
Proprietary Information
easYgen-3200 Training
Section 3 - Operational Modes
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
DynamicsLCDTM slide 3
Status Menu 6
Parameter Menu 14
Password Protection 18
Operation Modes (Auto, Manual, Stop) 24
Start / Stop 27
FlexAppTM 31
FAQ 37
Proprietary Information
DynamicsLCDTM
The 320x240 pixel graphic interactive LC display provides soft keys
DynamicsLCDTM
whose functionality changes depending on application (see FlexAppTM)
and operation.
Status Menu
Parameter Menu
93
Proprietary Information
DynamicsLCDTM
The Display Topography:
DynamicsLCDTM
Password
Current operation
Operation i.e. Cranking, loading,
Start / Stop
start pause, etc.
FlexAppTM
FAQ
94
Proprietary Information
Status Menu
Screen Navigation – Measured Values
DynamicsLCDTM
Operation
Start / Stop
FlexAppTM
FAQ
Screen Name
95
Proprietary Information
Status Menu
DynamicsLCDTM
Status Menu
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ
Set Points
96
Proprietary Information
Status Menu
DynamicsLCDTM
Status Menu
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ
97
Proprietary Information
Status Menu
DynamicsLCDTM
Status Menu
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ
Measured Values
98
Proprietary Information
Status Menu
DynamicsLCDTM
Status Menu
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ Online
Diagram
Visible
99
Proprietary Information
Parameter Menu
Screen Navigation – Parameter Screens
DynamicsLCDTM
Press “Parameter” Soft key
Status Menu
Parameter Menu
Password
Select Subdirectory
Operation
Start / Stop
FlexAppTM
FAQ
Screen Name
100
Proprietary Information
Parameter Menu
Screen Navigation – Parameter Screens
DynamicsLCDTM System Overview Parameter
Status Menu
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ
Screen Name
Pathway to
this screen
101
Proprietary Information
Parameter Menu
Change a Parameter
DynamicsLCDTM
Status Menu
Move black cursor
line up and down
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ
Press “Enter” soft key to select
parameter to be changed
102
Proprietary Information
Password Protection
Three levels of password protection enable multiple users
DynamicsLCDTM with varying degrees of access
Status Menu
Parameter Menu
Password protection valid for 2 hours
Password
Level 1/End user 0001
Operation Level 2/Temporary commissioning (random number+200)*3
Start / Stop Level 3/Commissioning 0003
FlexAppTM
FAQ
103
Proprietary Information
Password Protection
DynamicsLCDTM
Status Menu
Possible ways to access a parameter:
Parameter Menu
Operation
HMI Pushbuttons Display
Start / Stop
RS-232 ToolKit No password required
104
Proprietary Information
Password Protection
Screen Navigation – Parameter Screens
DynamicsLCDTM System Overview Parameter
Status Menu
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ
Password Screen
105
Proprietary Information
Password Protection
Password protection valid for 2 hours
DynamicsLCDTM Level 1/End user 0001
Status Menu Level 2/Temporary commissioning (random number+200)*3
Parameter Menu
Level 3/Commissioning 0003
Password
Randomly generated number
Operation
Start / Stop
Current level of access
FlexAppTM
FAQ
To access to this
communication port,
enter code here
106
Proprietary Information
Password Protection
Individual parameters cannot be viewed or edited if
DynamicsLCDTM the password has not been entered or has expired.
Status Menu
Parameter Menu
FlexAppTM
FAQ
107
Proprietary Information
Password Protection
New version shows that parameters are locked Version
DynamicsLCDTM 1.12
Status Menu
Parameter Menu
FlexAppTM
FAQ
108
Proprietary Information
Operation Modes
Shutdown alarms will change the operating mode to STOP
DynamicsLCDTM
Status Menu
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ
109
Proprietary Information
Operation Modes
Parameter Menu
Password
Operation
FAQ
MANUAL
STOP
110
Proprietary Information
Start / Stop in Auto
Generator:
DynamicsLCDTM
Start conditions Stop conditions
Status Menu
LM: Start in auto is “true” LM: Start conditions are “false”
Parameter Menu may be used with load dependent start/stop function Alarm class C-F detected
LM: Start w/o load is “true” LM: Stop in auto
Password
LM: Critical mode is “true”
Operation Loss of mains {GCB/MCB} (Emergency mode) LM: Inhibit emergency mode
Mains voltage/frequency out of operating range
Start / Stop Mains rotation field wrong
FlexAppTM
“Fail to close MCB” (if parameter is enabled)
FAQ
Mains:
Close MCB: Open MCB:
Mains are within accepted limits Dependent upon breaker logic
DI7 is de-energized (MCB is open) For mains decoupling
LM: Enable MCB is “true” (default DI6)
Conditions for synchronization or
dead bus closing are met
111
Proprietary Information
Start / Stop Logic
Diesel engine
DynamicsLCDTM
- Pre-glow function
Status Menu
- Fuel or Stop solenoid activation
Parameter Menu
- Crank/start circuit control
Password
Gas engine
Operation
- Ignition
Start / Stop
FlexAppTM
- Gas valve
FAQ - Crank/start circuit control
External logic
- Fuel solenoid as a start request to external controllers
- External control must take care of start sequence – no start failure
112
Proprietary Information
FlexAppTM
Parameter Menu
Parameter name: Product spec application:
Password
Operation
[GCB/MCB] [GCB/MCB open/close {2oc}]
Start / Stop
[GCB] [GCB open/close {1oc}]
FlexAppTM
FAQ
[GCB open] [GCB open {1o}]
[none] [0-CB-Mode {0}]
113
Proprietary Information
FlexAppTM – Breaker Application – [GCB/MCB]
Two breaker mode
DynamicsLCDTM
• Mains/utility breaker (MCB) and generator breaker (GCB)
Status Menu
• Generator protection for shutdown and GCB open command
Parameter Menu
• Single or multiple genset operation
Password
Operation
• GCB & MCB open close command
Start / Stop • Automatic mains failure (AMF) / emergency mode
FlexAppTM
FAQ
FlexAppTM
FAQ
Password
FlexAppTM
FAQ
116
Proprietary Information
FlexAppTM – Breaker Application – [GCB open]
Breaker open mode
DynamicsLCDTM
• Generator breaker open only
Status Menu
• Generator protection for shutdown and GCB open command
Parameter Menu
• Single or multiple genset operation
Password
Operation
• GCB open command (shunt trip)
Start / Stop
FlexAppTM
FAQ
Operation
• All breaker control is external
Start / Stop
FlexAppTM
FAQ
Fixed Input
DI 8 reply GCB (B contact)
DI 7 reply MCB (mains parallel)
118
Proprietary Information
Frequently Asked Questions
DynamicsLCDTM
Status Menu
Parameter Menu
Operation
119
Proprietary Information
FAQ
How do I reset the maintenance counter?
DynamicsLCDTM The maintenance hours counter decreases as the operation hours counter increases.
Status Menu The maintenance days counter decreases as the Internal calendar clock increases.
Parameter Menu When a count down timer reaches “0” an alarm is issued. The reset procedure is as follows:
Password
Step 1:
Operation
Start / Stop
FlexAppTM
FAQ
Status Menu
Step 2:
Parameter Menu
Password
Operation
Symbol appears only if the
required password is active
Start / Stop
FlexAppTM
FAQ
Status Menu
Step 3: Step 4:
Parameter Menu
Password
Operation
Start / Stop
FlexAppTM
FAQ
FlexAppTM
FAQ
123
Proprietary Information
End of Section 3
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
124
Proprietary Information
easYgen-3200 Training
Section 4 - Configuration via ToolKit
Proprietary Information
Contents
Introduction slide 3
Installing ToolKit 4
Connect 11
Status Menu 16
Configuration 24
Settings Menu 26
FAQ 38
Proprietary Information
Introduction
Introduction
Configuration
Settings
FAQ
127
Proprietary Information
Installing ToolKit
Introduction ToolKit 3.x
Installation The executable file for ToolKit may be found on the CD-ROM, which
Connect
comes with the control, or on the Woodward website.
Status Menu
http://www.woodward.com/software/Download/SWProductDetail.cfm?FileID=165
Configuration
Settings Menu
FAQ
128
Proprietary Information
Installing ToolKit
Introduction Install ToolKit 3.x
Installation
Follow the webpage directions for downloading ToolKit.
Connect
Install Microsoft .net Framework first!
Status Menu
Configuration
Settings Menu
FAQ
129
Proprietary Information
Installing ToolKit
Introduction Click the Next button on the ToolKit Setup Wizard dialog box
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
Connect
Status Menu
Configuration
Settings Menu
FAQ
131
Proprietary Information
Installing ToolKit
Introduction
Configure the ToolKit directories
Installation
ToolKit requires that controller specific files be installed in a separate folder
Connect
than the ToolKit folder in order to enable communications between the PC
Status Menu
and the easYgen. Refer to the configuration manual for an example.
Configuration
Settings Menu
ToolKit Files
FAQ
*.SID
5418-2752-D.SID
*.WSET
132
User defined name.WSET
Proprietary Information
Installing ToolKit
Introduction Get the config files
Installation
Load the config files from the easYgen-3000 page on the internet
Connect
http://www.woodward.com/power/easygen-3000.cfm?
Status Menu
Configuration
Copy the files to the previously defined ToolKit directories
Settings Menu
# of gensets to be displayed
Part number of the
control Language ID
US = English
133
DE = German
Proprietary Information
Installing ToolKit
Introduction Selecting a Communication Port
Installation
The default COM port settings of ToolKit may be configured by selecting
Connect Tools Options from the toolbar.
Status Menu
The options window will be displayed permitting you to select the desired default
COM port and the default path for the configuration files.
Configuration
Settings Menu
FAQ
134
Proprietary Information
Connect
Introduction
Open the *.wtool file
Installation
Connect
After the ToolKit application has been started, select what control to
communicate with. Open the proper *.wtool file.
Status Menu
Settings Menu
Or the symbol in the tool bar
FAQ
135
Proprietary Information
Connect
Introduction Serial Connection
Installation
• Connect to the serial COM port
Connect
• Use a Null Modem Cable
Status Menu
(crossover)
Configuration
Settings Menu
FAQ
RS-232
Serial 1
RS-232 ToolKit
136
Proprietary Information
Connect
Introduction Initialize communication between the PC and the controller
Installation
Device Connect
Connect
Status Menu
FAQ
137
Proprietary Information
Connect
Introduction
Installation
Check “Device -> Communications” if no measured values are displayed.
Connect
Status Menu
It should read “ToolConfigurator” for connecting via the RS-232 port.
Configuration
Settings Menu
FAQ
138
Proprietary Information
Status Menus
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
Measured values
139
Proprietary Information
Status Menus
Introduction
Installation
Connect
Status Menu
Use push buttons to
navigate between screens
Configuration
Settings Menu
FAQ
140
Proprietary Information
Status Menus
Introduction
Installation
Active alarms Can not be reset if
Connect
active flag = TRUE
Status Menu
Configuration
Settings Menu
FAQ
141
Proprietary Information
Status Menus
Introduction
Installation
Connect
Configuration
Settings Menu
FAQ
142
Proprietary Information
Status Menus
Use EXPORT to create HTML
Introduction
file of the active alarms
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
143
Proprietary Information
Configuration
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
144
Proprietary Information
Configuration
Changes are written directly to
Introduction
the controller!
Installation
Connect
Status Menu
Go to the desired screen
Configuration
145
Proprietary Information
Settings Menu
Introduction The settings menu is used to save configuration files from the
Installation controller, edit saved files offline, load a saved file into additional
Connect
controllers, and identifies differences in settings of two different files.
Status Menu
Configuration
Settings Menu
FAQ
146
Proprietary Information
Settings Menu
Introduction
Installation
Connect
• Saves the settings from an easYgen control to the computer for use
Status Menu as a historical record or to be transfered to additional controllers.
Configuration
Settings Menu
FAQ
147
Proprietary Information
Settings Menu
Introduction
Installation
Status Menu
Configuration
148
Proprietary Information
Settings Menu
Introduction
Installation
Connect
Status Menu
Edit settings file permits changing of
set points without being connected to
Configuration
a controller.
Settings Menu
FAQ
149
Proprietary Information
Settings Menu
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
150
Proprietary Information
Settings Menu
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
151
Proprietary Information
Settings Menu
Introduction
Installation
Connect
1) Warning
Status Menu
Configuration
Settings Menu
FAQ
152
Proprietary Information
Settings Menu
Introduction
Installation
Connect
2) Select file with
Status Menu Browse button
Configuration
Settings Menu
FAQ
3) Monitor
progress
153
Proprietary Information
Settings Menu
Introduction
Installation
Connect
• Select the two files to compare
Status Menu
Configuration
Settings Menu
FAQ
154
Proprietary Information
Settings Menu
Introduction
Installation
Connect
Status Menu
• Any
Configuration
differences
are displayed
Settings Menu
as a
FAQ spreadsheet
155
Proprietary Information
Settings Menu
Introduction
Installation
Connect
LogicsManager
Status Menu results
Configuration
Settings Menu
FAQ
156
Proprietary Information
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
157
Proprietary Information
FAQ
Introduction
Installation
Use the search function in ToolKit
Connect
• Starting with version V2.3
Status Menu
Configuration
Double-click on
Settings Menu
the result will
FAQ open the page
158
Proprietary Information
FAQ
Introduction
Installation
Mark any measured value with the right mouse button.
Connect
Select “Add to trend”.
Status Menu
Configuration
Settings Menu
FAQ
159
Proprietary Information
FAQ - Trend function
Introduction
Installation
Connect
Adjust trend scaling with “Properties...”
Status Menu
Configuration
Settings Menu
FAQ
160
Proprietary Information
FAQ - Trend function
Introduction Export as screenshot or *.csv file (only values in display, no storage)
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
161
Proprietary Information
FAQ
Introduction
Installation
Connect
Status Menu
Use a USB-to-CAN converter (from IXXAT)
Configuration
Settings Menu
VCI driver 3.0 or higher needed
FAQ
CAN 1
to #2, #3,....
162
Proprietary Information http://www.ixxat.com
FAQ – Multiple units on CAN #1
Introduction
Select the CAN hardware in the Network menu
Installation
Select the device with Tool Device Tool Configurator
Connect
Change the baud rate from
Status Menu “Autodetect” to 250kBd if there are
Configuration
less than 3 members on the CAN bus
Settings Menu
FAQ
163
Proprietary Information
FAQ – Multiple units on CAN #1
Introduction
Display of multiple units in the “Plant page” screen
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
164
Proprietary Information
FAQ
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
RS-232
Serial 1
RS-232
Industrial modem
ToolKit
with discrete input for dial up
165
Proprietary Information
FAQ - Modem
Introduction Select the modem from the “Network” and enter the number to
Installation
be dialed.
Connect
Status Menu
Configuration
Settings Menu
FAQ
166
Proprietary Information
FAQ
Introduction
Installation
Connect
Status Menu
FAQ
RS-232 Ethernet
Serial 1
RS-232
Anybus ToolKit
http://www.anybus.com/products/abxss.shtml
167
Proprietary Information
FAQ
Introduction
Installation
Connect
Use language specific folders
Status Menu
• The English and German *.SID files are named identically
Configuration
• The *.SID file contains language information and must not be renamed
Settings Menu
• Opening the *.WTOOL file means ToolKit looks for the *.SID file in the specified
FAQ
folder
• Assign different file paths for different languages
168
Proprietary Information
FAQ
Introduction
Installation
Connect
Status Menu
Red indicates
Configuration
an incorrect
Settings Menu
SID- selection
FAQ
169
Proprietary Information
FAQ
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
Open the Device Manager window and right click on the VCI3
170 Interface and select Update Driver.
Proprietary Information
FAQ
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
Select “Don’t search. I will choose the driver to install.” and click
172 the Next button.
Proprietary Information
FAQ
Introduction
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
Installation
Connect
Status Menu
Configuration
Settings Menu
FAQ
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
3 Operational Modes 8 Controller
5 Communication 10 Application
11 Sequencing
Note:
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
Information contained
product specs. Specificherein is intended
reliance should beforgiven
and appropriate to the purposes
only to information containedofin
this publication/presentation.
purchase Woodward
order(s), other contractual reserves the
document(s), orright to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
applications.
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
177 applications.
Proprietary Information
easYgen-3200 Training
Section 5 - Communication
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
Introduction slide 3
Communication Ports 4
Serial Port Communication 5
CAN bus Communications 13
Password Protection 25
FAQ 27
Proprietary Information
Introduction
Introduction
Comm Ports
Serial Comms
CANbus Comms The easYgen-3200 has four communication ports. The functionality of
Password these ports are varied and may be utilize multiple protocols. These
FAQ
functions range from load dependent start/stop, load-sharing, reading
ECU data, configuration, and remote monitoring and control via an HMI.
180
Proprietary Information
Communication Ports
Introduction
Comm Ports
• Load-sharing • ToolKit
Serial Comms
• CANopen • Modbus
CANbus Comms
Serial 1
Password CAN 1 RS-232
FAQ
Serial 2
CAN 2
RS-485
• Extension cards • Modbus
(IKD 1, Phoenix)
• J1939 messaging
Comm Ports
Serial RS-232 • ToolKit
Serial Comms
Ethernet
FAQ
Serial 1
Serial RS-232 RS-232
Serial RS-485
Serial 2
PLC
Profibus RS-485
• Modbus
• Multiple units
PC
182
Proprietary Information
Serial 1: ToolKit via RS-232
Introduction
RS-232
Comm Ports
Serial Comms
CANbus Comms
Serial 1
Password RS-232
FAQ
183
Proprietary Information
Serial 1: GSM Modem via RS-232
Introduction
Comm Ports
Serial Comms
CANbus Comms
Password RS-232
FAQ
INSYS ToolKit
Serial 1 GSM Modem Modbus
RS-232 http://www.insys-tec.de
184
Proprietary Information
Serial 1: Landline Modem via DPC
Introduction
Comm Ports
Serial Comms
CANbus Comms
Password RS-232
FAQ
Phoenix ToolKit
Serial 1 landline modem Modbus
RS-232
with discrete input for dial up
185
Proprietary Information
Serial 1: Ethernet to RS-232 converter
Introduction
Comm Ports
Serial Comms
CANbus Comms
Anybus ToolKit
Serial 1
Modbus
RS-232
The Anybus converter provides a virtual COM port.
The Toolkit software must connect to this port to
receive the data
http://www.anybus.com/products/abxss.shtml
186
Proprietary Information
Serial 1: Modbus on RS-232
Introduction • For point to point communications easYgen-3000 to the Master
Comm Ports
Serial Comms
CANbus Comms
Password Modbus
Serial 1
FAQ
RS-232
PLC
187
Proprietary Information
Serial 1: Modbus on RS-232
Introduction Baud rate
Comm Ports
Serial Comms
CANbus Comms
Password
FAQ
Password
FAQ
Modbus
Serial 2
RS-485
PLC
189
Proprietary Information
Serial 2: Modbus on RS-485
Introduction • Wiring of Half Duplex- communications
Comm Ports
Serial Comms
CANbus Comms
Password
FAQ
190
Proprietary Information
Serial 2: Modbus to Profibus
Introduction
Comm Ports
Profibus-Master
Anybus X-gateway
Serial 2
RS-485 Modbus Master to Profibus DP Slave converter.
Must be programmed separately.
http://www.anybus.de/products/prodindex.shtml
191
Proprietary Information
Serial 2: Parameters
Introduction
Comm Ports
Serial Comms
CANbus Comms
Password
FAQ
Password CAN 1
FAQ
Digital expansion modules
CAN 2
Engine level
2x IKD 1 Phoenix
• J1939 (ECU)
• Extension cards Analog expansion modules
ECU
ECU
GATEWAY
GATEWAY P2
ENGINE GENERATOR
Engine Generator
193
Proprietary Information Phoenix J1939
CAN 1: PC
Introduction
Comm Ports
CAN 1 IXXAT USB-to-CAN
Serial Comms converter ToolKit
http://www.ixxat.com
CANbus Comms CANopen
software tool
Password Connection to a PC via CAN-to-USB
interface transducer, e.g. IXXAT
FAQ
194
Proprietary Information
CAN 1: Load Sharing
Introduction
CANbus Comms
Password
FAQ
195
Proprietary Information
CAN 1: CANopen to PLC
Introduction
Password
FAQ
196
Proprietary Information
CAN 1: Parameters
Introduction
Comm Ports
For load share
Serial Comms
CANbus Comms
Password
FAQ
197
Proprietary Information
CAN 1: Parameters
Introduction
For CANopen
Comm Ports
Serial Comms
CANbus Comms
Password
FAQ
198
Proprietary Information
CAN 2: ECU and IKD
Introduction Parameters in the easYgen
Comm Ports CAN interface 2 IKD
Serial Comms
Function for RPDO 1 = 1st IKD
CANbus Comms Parameters in IKD 1 IKD2
Function for RPDO 2 = 2nd IKD
Password
FAQ
CAN 2
2x IKD 1
extension card
ECU
ECU
GATEWAY
GATEWAY
ENGINE GENERATOR
Engine Generator
199
Proprietary Information
CAN 2: ECU and Phoenix
Introduction Parameters in the easYgen
Comm Ports CAN interface 2 Phoenix
Serial Comms
Function for RPDO 1 = BK 16DIDO
CANbus Comms
Function for RPDO 2 = Off
Password
FAQ
CAN 2
Phoenix
extension card
ECU
ECU
GATEWAY
GATEWAY
ENGINE GENERATOR
Engine Generator
200
Proprietary Information
CAN 2: Visualization of a J1939 ECU
Introduction The easYgen reads & displays ECU values:
Comm Ports
Visualization
J1939
ECU
ECU
GATEWAY
GATEWAY
ENGINE GENERATOR
Engine Generator
201
Proprietary Information
CAN 2: Monitoring of a J1939 ECU
Introduction The easYgen reacts to ECU messages with an alarm:
Comm Ports
Serial Comms
J1939
ECU
ECU
GATEWAY
GATEWAY
ENGINE GENERATOR
Engine Generator
202
Proprietary Information
CAN 2: P1 J1939 ECU Values
Introduction
Comm Ports
• Throttle position (SPN91) • Air inlet temperature (SPN172)
Serial Comms
• % Load at current speed (SPN92) • Exhaust gas temperature (SPN173)
CANbus Comms • Engine oil level (SPN98) • Fuel temperature (SPN174)
Password • Engine oil pressure (SPN100) • Engine oil temperature (SPN175)
FAQ • Boost pressure (SPN102) • Fuel rate (SPN183)
• Intake manifold temperature • Engine speed (SPN190)
(SPN105)
• Total engine hours (SPN247)
• Barometric pressure (SPN108)
• Actual engine torque (SPN513)
• Engine coolant temperature
(SPN110)
• Coolant level (SPN111)
203
Proprietary Information
CAN 2: P2 J1939 ECU Values
Introduction
Comm Ports
• Engine Intercooler Temp (SPN52) • Transmission Oil Temperature
(SPN177)
Serial Comms
• Fuel Delivery Pressure (SPN94)
• Auxiliary Temperature 1 (SPN441)
CANbus Comms • Fuel Filter Differential Pressure
(SPN95) • Auxiliary Temperature 2 (SPN442)
Password
FAQ
• Crankcase Pressure (SPN101) • Actual Engine Torque (SPN513)
• Turbo Air Inlet Pressure (SPN106) • Alternator Bear. 1 Temperature
(SPN1122)
• Air Filter 1 Differential Pressure
(SPN107) • Alternator Bear. 2 Temperature
(SPN1123)
• Coolant Pressure (SPN109)
• Transmission Oil Pressure (SPN127)
• Fuel Rail Pressure (SPN157) Version
1.12
• Ambient Air Temperature (SPN171)
204
• Turbo Oil Temperature (SPN176)
Proprietary Information
CAN 2: P2 J1939 ECU Values
Introduction
Comm Ports
• Engine Intercooler Temp (SPN52) • Fuel Rail Pressure (SPN157)
Serial Comms
• Fuel Delivery Pressure (SPN94) • Ambient Air Temperature (SPN171)
CANbus Comms • Fuel Filter Differential Pressure • Turbo Oil Temperature (SPN176)
(SPN95)
Password • Transmission Oil Temperature
FAQ
• Crankcase Pressure (SPN101) (SPN177)
• Turbo Air Inlet Pressure (SPN106) • Auxiliary Temperature 1 (SPN441)
• Air Filter 1 Differential Pressure • Auxiliary Temperature 2 (SPN442)
(SPN107)
• Actual Engine Torque (SPN513)
• Coolant Pressure (SPN109)
• Transmission Oil Pressure (SPN127)
Version
1.12
205
Proprietary Information
CAN 2: P2 J1939 ECU Values
Introduction
Comm Ports
• Alternator Bearing 1 Temperature • Main Bearing 1-11 Temperatures
(SPN1122) (SPN1157-1167)
Serial Comms
• Alternator Bearing 2 Temperature • Turbo 1-4 Compressor Inlet
CANbus Comms
(SPN1123) Temperatures (SPN1172-1175)
Password
• Alternator Winding 1,2,3 Temperature • Turbo 1-4 Turbine Inlet Pressures
FAQ (SPN1124-1126) (SPN1176-1179)
• Intake Manifold 2,3,4 Temperature • Turbo 1-4 Turbine Inlet Temperatures
(SPN1131-1133) (SPN1180-1183)
• Engine Thermostat (SPN1134)
• Engine Oil Temperature 2 (SPN1135)
• Engine ECU Temperature (SPN1136)
Version
• Exhaust Gas Port 1-20 Temperatures 1.12
(SPN1137-1156)
206
Proprietary Information
CAN 2: P2 J1939 ECU Values
Introduction
Comm Ports
• Turbo 1-4 Turbine Outlet • Battery 1 Temperature (SPN1800)
Temperature (SPN1184-1187)
Serial Comms
• Battery 2 Temperature (SPN1801)
• Engine Aux. Coolant Pressure
CANbus Comms • Intake Manifold 5 Temperature
(SPN1203)
(SPN1802)
Password
• Pre-filter Oil Pressure (SPN1208)
FAQ
• Intake Manifold 6 Temperature
• Engine Aux. Coolant Temperature (SPN1803)
(SPN1212)
• Right Exhaust Gas Temperature
• Fuel Filter Differential Pressure (SPN2433)
(SPN1382)
• Left Exhaust Gas Temperature
(SPN2434)
Version
1.12
207
Proprietary Information
CAN 2: Control of a J1939 ECU
Introduction The easYgen sends commands to the ECU:
Comm Ports
ECU
ECU
GATEWAY
GATEWAY
ENGINE GENERATOR
Engine Generator
208
Proprietary Information
CAN 2: Control of a J1939 ECU
Deutz
Introduction Volvo MAN SISU
Woodward S6 EMR2/ Volvo MTU
EMS1/ MFR/ EEM2/ SAE
Comm Ports EGS Scania Volvo EMS2 ADEC
EDC3 EDC7 EEM3
EDC4
Serial Comms
15102
Device EGS S6 EMR2 EMS2 EMS2 ADEC MAN SISU Std.
CANbus Comms
type
Password Engine
No Yes No Yes Yes Yes Yes Yes No
Start
FAQ
Engine
Yes Yes No Yes Yes Yes Yes Yes Yes
Stop
Droop
Yes Yes No Yes Yes Yes Yes Yes Yes
Mode
Idle Mode No Yes No Yes Yes No No No No
50/60Hz
Yes Yes No Yes No Yes No No No
Switch
Yes Yes Yes Yes Yes Yes
Speed Bias Yes Yes Yes
offset set point offset set point set point set point
Preglow No No No Yes Yes No No No No
Override
ECU No Yes No No No Yes No No Yes
Alarms
209
Proprietary Information
CAN 2: Coupling to Woodward E3
Introduction Gas Mixer
Comm Ports
Password Knock
Detection
FAQ
Power
Management
Controls Throttle
-Integrated
Spark Engine
-ThrottleControl
Bodies
Ignition Plugs
By-pass /
Coils Waste gate
Comm Ports
211
Proprietary Information
CAN 2: Coupling to Woodward E3
The easYgen sends CAN commands to the EGS
Introduction
Comm Ports
Serial Comms
CAN Commands
CANbus Comms
Start / stop
Password Shutdown
FAQ Speed setpoint
Genset breaker status
CAN
J1939 Load setpoint
Alarm Reset
Real power
Rated speed
212
Proprietary Information
CAN 2: Control of a J1939 ECU
Introduction
CAN 2
Comm Ports ECU
GATEWAY
ECU
GATEWAY
ENGINE GENERATOR
Serial Comms
Engine Generator
CANbus Comms
CAN 2
Comm Ports ECU
GATEWAY
ECU
GATEWAY
ENGINE GENERATOR
Serial Comms
Engine Generator
CANbus Comms
Password Parameters
FAQ Setting Device type J1939 Device Engine control SPN Version Comment
ECU (ID 15102) address address (ID 15103)
(ID 15106) (ID 15107)
Woodward E3 EGS 234 0 n/a
MTU ADEC ADEC MTU 1 128 n/a Connection:
easYgen SAM via CAN2
SAM ADEC using MTU bus
Comm Ports
Serial Comms
CANbus Comms
Password
FAQ
Comm Ports
Serial Comms
CANbus Comms
Password
FAQ
-ECU
216
Proprietary Information
P2
only CAN 2: Parameters
Expansion boards – refer to applications manual for details
Introduction
Comm Ports
Serial Comms
CANbus Comms
Password
FAQ
217
Proprietary Information
Password Protection
Introduction
Password protection valid for 2 hours
Comm Ports Level 1/end user 0001
Serial Comms Level 2/temporary commissioning (random number+200)*3
CANbus Comms
Level 3/commissioning 0003
Password
Possible ways to change a parameter:
FAQ
218
Proprietary Information
Password Protection
Introduction
Password protection valid for 2 hours
Comm Ports Level 1/end user 0001
Serial Comms Level 2/temporary commissioning (random number+200)*3
CANbus Comms
Level 3/commissioning 0003
Password
Randomly generated number
FAQ
219
Proprietary Information
FAQ
Introduction
How can I make a start / stop / acknowledge via the interface?
Comm Ports
Serial Comms
220
Proprietary Information
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
Serial Comms
1) Config device
CANbus Comms
Password
FAQ
Acknowledge:
Enter input command variable “04.14 Remote acknowledge” in the
“Ext.Acknowledge” LogicsManager output.
When data bit 4 “Remote acknowledge” changes from false to true, the
“Ext.Acknowledge” LogicsManager output is enabled.
Data bit 4 “Remote acknowledge” must change back to false in order to reset the
221
Proprietary Information
“Ext.Acknowledge” LogicsManager output.
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
Serial Comms
1) Config device
CANbus Comms
Password
FAQ
Start/Stop:
Enter input command variable “04.13 Remote request ” in the “Start request in
AUTO” LogicsManager output.
When data bit 0 “Start request” changes from false to true, the “Start request
in AUTO” LogicsManager output is enabled.
When data bit 1 “Stop request” changes from false to true, “Start request in
222
Proprietary Information
AUTO” LogicsManager output is disabled.
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
Serial Comms
2) Send start bit
CANbus Comms
Password
Remote control
FAQ Parameter ID 503
223
Proprietary Information
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
2) Send start bit:
Serial Comms
All interface protocols write utilizing the same LogicsManagerTM
CANbus Comms
commands:
Password
FAQ
04.13 Remote request
RS-232 CAN bus 1
Modbus 04.14 Remote acknowledge CANopen
Modbus
RS-485
224
Proprietary Information
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
2) Send start / stop bits
Serial Comms
CANbus Comms Via interface RS-232 or RS-485, Modbus protocol address 503
Password
Start/Stop
FAQ
Engine starts when the “Remote Start” data bit is true/high
Engine stops when the “Remote Stop” data bit is true/high
225
Proprietary Information
Note: Software ModScan32 adds internally +1 to the address (504 instead of 503)
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
2) Send acknowledge bit
Serial Comms
CANbus Comms Via interface RS-232 or RS-485, Modbus protocol address 503
Password Acknowledge:
FAQ Bit must be reset by the Modbus master
226
Proprietary Information
Note: Software ModScan32 adds internally +1 to the address (504 instead of 503)
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
2) Send start / stop / acknowledge bits
Serial Comms
FAQ
227
Proprietary Information
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
2) Send start / stop bits
Serial Comms
FAQ
Start bit #0
Stop bit #1
04.13 Remote
start request
228
Proprietary Information
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
2) The acknowledge sequence requires two “rising edges”
Serial Comms
CANbus Comms
04.14 Ext.
Acknowledge
229
Proprietary Information
FAQ
Introduction How can I make a start / stop / acknowledge via interface?
Comm Ports
3) Monitor result
Serial Comms
Engine will perform a start sequence
CANbus Comms
Password
FAQ
230
Proprietary Information
End of Section 5
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
3 Operational Modes 8 Controller
4 Configuration and ToolKit 9 Synchronization and Breaker
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
231
Proprietary Information
easYgen-3200 Training
Section 6 - LogicsManager
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
Introduction slide 3
Screen Description 5
Input Command Variables 6
Signs 11
Operators 13
Time delay 17
Logical Outputs 18
Programming 24
Exercise 26
Proprietary Information
Introduction
Introduction The LogicsManagerTM permits the easYgen-3000 operating logic to
Description be customized to the individual application. The status of discrete
Input Commands
inputs, discrete outputs, internal conditions, alarms, and measured
values may be combined into logical functions. These logical
Signs
functions may be used to initiate numerous operational functions,
Operators
such as starting the generator in the automatic mode.
Time Delay
Logical Outputs
234
Proprietary Information
Introduction - LogicsManagerTM
Introduction
Description
Input Commands
Digital Signals Relay Outputs
Discrete inputs Assignment Operate freely configurable
Signs Relay status outputs
External discrete inputs With timer ON-delay and OFF-delay
Operators
External relays
Control via interface 16 additional/internal flags or logical
Time Delay operations
Logical Outputs
Internal Conditions Internal Conditions
Programming Conditions Start/stop engine
- CB status
Exercise Change operation mode
- operating mode
- engine status Acknowledge of alarms
Alarms Inhibit emergency mode
- warning alarm
Creating internal flags for
- shutdown alarm
cascading logic with
Time / Date multiple variables
235
Proprietary Information
Screen Description
Introduction Components of a Boolean Logic equation:
Description
Time Delay
Command
Logical Outputs
Programming Operator 01
Exercise
Operator 02
236
Proprietary Information
Input Command Variables
Introduction The following groups are available:
Description
Input Commands
00 Flags condition 08 System related alarms
(results of LogicsManager outputs)
Signs 09 Discrete inputs
01 Alarm system
Operators (active alarm classes) 10 Analog inputs
(wire break)
Time Delay 02 System condition
11 Clock and timer
Logical Outputs
03 Engine control
Programming
12 External DIs
04 Applications condition
Exercise
13 Discrete outputs
05 Engine related alarms
14 External DOs
06 Generator related alarms
15 Flexible limits
07 Mains related alarms
18 Transistor outputs
(external excitation 12V/24V)
237
Proprietary Information
Input Command Variables
Introduction Viewing the state of the inputs in ToolKit:
Description
Input Commands
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
238
Proprietary Information
Input Command Variables
Introduction Viewing the state of the inputs in the HMI:
Description
Input Commands
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
239
Proprietary Information
Input Command Variables
Introduction Internal clock and timer functions:
Description
Input Commands
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
240
Proprietary Information
Input Command Variables
Introduction If a discrete input or alarm threshold is to
Description
be used as an input command to the
LogicsManager, the alarm class must be
Input Commands
configured as “Control”.
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
241
Proprietary Information
Signs
Introduction The sign defines if the input is enable and how it will be used
Description
Direct Command value
Input Commands - The command variable input is
passed directly to the operator.
Signs
Operators
Hard True
- The command variable input is
ignored and this logic path is
always TRUE.
242
Proprietary Information
Signs
Introduction
Description
Input Commands
Command input:
Grey if sign = TRUE or FALSE
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
243
Proprietary Information
Operators
Introduction Operator 01 and 02
Description
Input Commands
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
244
Proprietary Information
Operators
Introduction Truth Tables
Description
AND OR NAND
Input Commands
x1 x1
Signs
x1 x2
Operators x2
x2
Time Delay
Logical Outputs
Programming
Exercise
x1 x2 y x1 x2 y x1 x2 y
0 0 0 0 0 0 0 0 1
0 1 0 0 1 1 0 1 1
1 0 0 1 0 1 1 0 1
1 1 1 1 1 1 1 1 0
245
Proprietary Information
Operators
Introduction Truth Tables
Description
NOR NXOR XOR
Input Commands
x1 x1
OFF OFF
ON ON
Signs
x1 x2
x2 x2
Operators OFF ON
ON OFF
Time Delay
Logical Outputs
Programming
Exercise
x1 x2 y x1 x2 y x1 x2 y
0 0 1 0 0 1 0 0 0
0 1 0 0 1 0 0 1 1
1 0 0 1 0 0 1 0 1
1 1 0 1 1 1 1 1 0
246
Proprietary Information
Operators
Introduction The “Help” screen gives a description of the logical outputs.
Description
Input Commands
Signs
Press soft key
Operators
Time Delay
Logical Outputs
Programming
Exercise
247
Proprietary Information
Time Delay
Introduction Delay ON Delay OFF
Description The amount of time that the logical The amount of time that the logical
output state is delayed before changing output state is delayed before changing
Input Commands
to true to false
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
248
Proprietary Information
Logical Outputs
Introduction There are three types available:
Description
Input Commands
Signs Relay outputs Any discrete output that are freely configurable
Operators
Time Delay
Exercise
249
Proprietary Information
Logical Outputs
Relay output 1 Ready for operation OFF
Introduction
Relay outputs
Description
Relays 2 to 12 Depending on configuration
Input Commands
External relays 1-16 via expansion board
Signs May be used as additional flags if not utilized
Operators
Time Delay
Logical Outputs
Programming
Exercise
250
Proprietary Information
Logical Outputs
Introduction
Internal Flags Internal flags 1 through 16
Description
Flag 1: used as placeholder – use caution when
Input Commands
employing it for other purposes
Signs
Internal flag 8:
Flag 8: Timer function
Operators Timer1: 08:00.00
Time Delay Timer2: 17:00.00
Logical Outputs Active weekday:
Programming Monday: Yes
Exercise
…..
Friday: Yes
Saturday: No
Sunday: No
251
Proprietary Information
Logical Outputs
Introduction
Logical Functions
Description
Input Commands
Start request in AUTO
Signs Stop request in AUTO
Operators Load dependent (LD) start stop
Time Delay Start w/o load
Logical Outputs Critical mode
Programming
Inhibit emergency
Exercise
External acknowledge
Undelayed close GCB
External mains decoupling requested
Enable MCB
Firing speed reached
252
Proprietary Information
Logical Outputs
Introduction
Logical Functions
Description
Setpoint 2 power
Input Commands
Setpoint 2 power factor
Signs
Setpoint 2 frequency
Operators
Setpoint 2 voltage
Time Delay
Frequency droop active
Logical Outputs
Voltage droop active
Programming
Discrete f/P + (raise)
Exercise
Discrete f/P – (lower)
Discrete V/PF + (raise)
Discrete V/PF – (lower)
RUN synchronization mode
CHECK synchronization mode
PERMISSIVE synchronization mode
253
Proprietary Information
Logical Outputs
Introduction
Logical Functions
Description
Input Commands
254
Proprietary Information
Programming
Introduction Select component to change with arrows
Description
Input Commands
Operators
Time Delay
Go to next input command group
Logical Outputs
Programming
Exercise
255
Proprietary Information
Programming
Introduction Remote start:
Description
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
257
Proprietary Information
Exercise
Introduction
Your customer needs a relay output to cause a
Description
warning light to flash if the operator puts an
Input Commands
easYgen-3200 into the MANUAL operation mode.
Signs
Operators
Time Delay
Logical Outputs
Programming
Exercise
258
Proprietary Information
Exercise
Introduction Create pulsing relays output
Description
Use as many flags as necessary
Input Commands
The relay shall only pulse in operating mode MANUAL
Signs
Use relay 11 as pulse relay
Operators
Logical Outputs
Programming
Exercise
259
Proprietary Information
Exercise
Introduction Solution: Create pulsing relay output.
Description
Can be used as a simple process controller if combined with Flexible Limits
Input Commands (alarm class = control). Only digital PID possible with multiple Flexible Limits
Signs and different pulse / pause ratios.
Operators
Pause time Pulse time
Time Delay
Logical Outputs
Programming
Exercise
260
Proprietary Information
End of Section 6
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
3 Operational Modes 8 Controller
4 Configuration and ToolKit 9 Synchronization and Breaker
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
261
Proprietary Information
easYgen-3200 Training
Section 7 – Analog Manager
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
Introduction slide 3
Data Sources 6
Flexible Limits 13
Source Format 18
Analog Output 21
Exercises 29
Proprietary Information
Introduction
Introduction
Analog ManagerTM
Data Sources
The Analog Manager permits measured or internal analog values, such as
Flexible Limits
speed or voltage bias signals, to be utilized for the following
Source Format functionalities:
Analog Outputs
• Monitoring via FlexLimitsTM for alarm and control purposes
Exercises
• Sources for the analog bias signals output
• Sources for the set point references to external controllers
264
Proprietary Information
Introduction
Introduction
The easYgen offers the ability to measure multiple values:
Data Sources
• Voltage • Active Power
Flexible Limits
• Current • Reactive Power
Source Format
Analog Outputs
• Speed / Frequency • Apparent Power
Exercises • Analog Input
265
Proprietary Information
Data Sources
Introduction Possible data sources
Data Sources
00 Internal values
Flexible Limits
01 Generator values
Source Format 02 Mains values
Analog Outputs 03 Busbar
Exercises
05 Controller set points
06 Analog inputs
08 External analog inputs
Flexible Limits
Source Format
Analog Outputs
Exercises
267
Proprietary Information
Data Sources
Introduction Group 01 Generator values
Data Sources
Analog Analog variable Reference value
Flexible Limits
input #
Source Format
01.01 Gen. aver.ph-n volt Generator rated voltage
Analog Outputs
01.02 Gen voltage L1-N Generator rated voltage
Exercises
268
And many more detailed values
Proprietary Information
Data Sources
Group 02 Mains values
Introduction
Data Sources
Flexible Limits
Source Format
Analog Outputs
Exercises
269
Proprietary Information
Data Sources
Introduction Group 05 Controller setpoints
Data Sources
Flexible Limits
Source Format
Analog Outputs
Exercises
Flexible Limits
Source Format
Analog Outputs
Exercises
271
Proprietary Information
Data Sources
Group 07 ECU Engine values (J1939) Version
1.12
Introduction
Number # Datenquelle
Data Sources
272
And many more detailed values
Proprietary Information
Flexible Limits
Introduction
Data Sources
Flexible Limits
Description of the
Source Format parameters
Analog Outputs
Exercises
273
Proprietary Information
Flexible Limits
Introduction Description of the parameters
Data Sources
Analog Outputs
Exercises
275
Proprietary Information
Flexible Limits
Introduction Description of the parameters
Data Sources
Flexible Limits
Source Format
Analog Outputs
Exercises
276
Proprietary Information
Flexible Limits
Introduction Description of the parameters
Data Sources
Flexible Limits
Select monitored data
Source Format source from list
Analog Outputs
Exercises
277
Proprietary Information
Source Format
Introduction
Format of the values:
Data Sources
Flexible Limits
The data range of these values is +/- 32000 (+/- 320.00%)
Source Format
There are two types of values
Analog Outputs
• with reference i.e. voltages, refer to rated voltage, entered as 000.00%
Exercises
• without reference i.e. analog inputs entered in the displayed format without a
decimal
278
Proprietary Information
Voltage Analog input
Source Format
Introduction
The format is needed for the following parameters:
Data Sources
Flexible Limits
Flexible limits Parameter: Limit
Hysteresis
Source Format
279
Proprietary Information
Source Format
Introduction Examples:
Data Sources
Flexible Limits
Source Format
Analog Outputs
Exercises
280
Proprietary Information
Analog Output
Introduction Description of the
Data Sources parameters
Flexible Limits
Source Format
Analog Outputs
Exercises
281
Proprietary Information
Analog Output
Introduction Description of the analog output parameters
Data Sources
Flexible Limits
Source Format
Analog Outputs
Data source:
Exercises
select from list
282
Proprietary Information
Analog Output
Introduction Description of the analog output parameters
Data Sources
Flexible Limits
Source Format
Analog Outputs
Exercises
283
Proprietary Information
Analog Output
Introduction Description of the analog output parameters
Data Sources
Flexible Limits
284
Proprietary Information
Analog Output
Introduction Description of the analog output parameters
Data Sources
Flexible Limits
Source Format
Analog Outputs
Only for hardware type:
Exercises
User defined
285
Proprietary Information
Analog Output
Introduction Description of the analog output parameters
Data Sources
Flexible Limits
Source Format
Ensure hardware is configured
for +/-10V or 0-10V if using
Analog Outputs PWM signal
Exercises
286
Proprietary Information
Analog Output
Introduction Examples for analog output parameters from the Configuration manual
Data Sources
Flexible Limits
Source Format
Analog Outputs
Exercises
287
Proprietary Information
Analog Outputs: Status Screen
Introduction Signal Options: Analog outputs
Data Sources • OFF • 2 analog outputs
• User defined (max. +/- 20mA and +/- 10V)
Flexible Limits Configurable as a
• 0-10mA / 0-5V
Source Format
• 0-20mA / 0-10V
voltage, current, or
Analog Outputs • 4-20mA Actual output PWM signal
• 0.5-4.5V • Preconfigured for speed and
Exercises signal
• 10-0mA / 5-0V voltage bias
• 20-0mA / 10-0V % in relation to
• 20-4mA the configured
• 4.5-0.5V range
• +/-1 V
• +/- 2.5
• +/- 3V
• +/-10mA / +/-5V
• +/-20mA +/-10V
288
Proprietary Information
Exercises
Introduction A: 1) Configure the analog input 1 for a VDO fuel tank level sender.
Data Sources 2) Additional task: What would you have to change to view the tank
Flexible Limits
level in liters?
Source Format
B: Configure the analog output manager:
Analog Outputs
Generator real power for an analog meter (rated power 200 KW).
Exercises
D: Use the flexible limits and activate a fuel transfer pump with the fuel
tank levels from the analog input (refer to section 2, exercise A).
289
Proprietary Information
Exercises: Task A
Introduction 1) Configure the Analog input 1 for a VDO fuel tank level sensor.
Data Sources
Sender Type:
Flexible Limits
Source Format
Resistive range: 0 to 180 Ohm linear= 0 to 100% Fuel
level, 2-wire / two-pole sender
Analog Outputs
Exercises
2) Additional task: What would you have to change to see the fuel
tank level in liters?
290
Proprietary Information
Exercises: Task A
Introduction 1) Configure the Analog input 1 for a VDO fuel tank level sensor.
Data Sources
Change parameters in the analog input screen
Flexible Limits
Source Format
Analog Outputs
Exercises
291
Proprietary Information
Exercises: Solution A
Introduction 1) Configure the Analog input 1 for a VDO fuel tank level sensor.
Data Sources
Flexible Limits
Source Format
Analog Outputs
Exercises
292
Proprietary Information
Exercises: Solution A
Introduction 1) Configure the Analog input 1 for a VDO fuel tank level sensor.
Data Sources
Select Type “linear” from list
Flexible Limits
Source Format
Analog Outputs
Exercises
293
Proprietary Information
Exercises: Solution A
Introduction 1) Configure the Analog input 1 for a VDO fuel tank level sensor.
Data Sources
Flexible Limits
Source Format
Analog Outputs
Exercises
294
Proprietary Information
Exercises: Solution A
Introduction 1) Configure the Analog input 1 for a VDO fuel tank level sensor.
Data Sources
Flexible Limits
Enter value to be displayed
Source Format
Analog Outputs
Exercises
296
Proprietary Information
Exercises: Solution A
Introduction 1) Configure the Analog input 1 for a VDO fuel tank level sensor.
Data Sources
Flexible Limits
Check result in the display
Source Format
Analog Outputs
Exercises
297
Proprietary Information
Exercises: Solution A
Introduction 2) Additional task: What would you have to change to view the fuel
Data Sources tank level in liters?
Enter the value to be displayed
Flexible Limits
100% = 6000 liters
Source Format
at 100% = 6000l
Analog Outputs
Exercises
298
Proprietary Information
Exercises: Task B
Introduction Configure the analog output manager to operate
Data Sources an analog meter that will display the generator real power.
Flexible Limits
The generator is rated at 200 kW.
The range on the meter display is from –62.5 kW to 250 kW.
Source Format
Analog Outputs
-62.5
299
Proprietary Information
Exercises: Solution B
Introduction Configure the analog output manager
Data Sources Generator real power for an analog meter (rated power 200 KW)
Flexible Limits
0mA -62.5 KW -31.25% from rated power
Source Format
4mA 0 KW
Analog Outputs
20mA 250 KW 125.00% from rated power
Exercises
300
Proprietary Information
Exercises: Task C
Introduction Configure the analog output manager
Data Sources Speed bias signal for analog output 1 range: 3 – 7 V.
Flexible Limits
Source Format
Analog Outputs
Exercises
301
Proprietary Information
Exercises: Solution C
Introduction Configure the analog output manager
Data Sources Speed bias signal for analog output 1 range: 3 – 7 V.
Flexible Limits
Hardware type “user defined” with min. / max. configuration
complete output range is +/- 20mA (+/- 10V)
Source Format
3V 65.00% min. value
Analog Outputs
7V 85.00% max. value -10V 0V 3 7 10V
Exercises
302
Proprietary Information
Exercises: Task D
Introduction Fuel Transfer Pump Operation
Data Sources The flexible limits are to be used to activate a fuel pump when the fuel level
in the day tank falls below 20% capacity and shut off the fuel pump when
Flexible Limits
the fuel level in the day tank exceeds 90% capacity. The flexible limits
Source Format interpret the fuel level from an analog input. (refer to section 2, exercise A)
Analog Outputs
100% = 6000 l 90% = 5400 l 20% = 1200 l
Exercises
Fuel
Fuel pump OFF
90%
Analog Outputs
Exercises
304
Proprietary Information
Exercises: Solution D
Introduction Fuel Transfer Pump Operation
Data Sources The LogicsManager for a single discrete output is used to operate the fuel
transfer pump for the day tank.
Flexible Limits
Source Format
Analog Outputs
Exercises
Flexible limit 5 (20% capacity) activates the fuel pump and the relay
remains energized until flexible limit 6 is reached (90% capacity).
Discrete Output 10 (13.10) is used as self-holding contact for turning the
305 fuel pump on and off.
Proprietary Information
End of Section 7
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
3 Operational Modes 8 Controller
4 Configuration and ToolKit 9 Synchronization and Breaker
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
306
Proprietary Information
easYgen-3200 Training
Section 8 - Controller
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
slide 3
Introduction
4
Controller
13
Set Points
17
Load Sharing
24
FAQ
30
Exercises
Proprietary Information
Introduction
Introduction The easYgen-3200 provides the user with a selection of bias signals
Controller to operate numerous speed controls and voltage regulators. The
easYgen-3200 may be configured to use analog voltage and/or
Set Points
current signals, PWM signals, or raise/lower contacts to increase or
Load Sharing
decrease the speed and voltage reference point.
FAQ
Exercises
309
Proprietary Information
What does “control” mean?
Introduction
• Measure the actual state
-
Controller
310
Proprietary Information
Controller
Introduction
Analog / PWM Controller
Controller Proportional Gain
Set Points Integral Gain
Load Sharing Derivative ratio
FAQ
-10V -3 7 10V
311
Proprietary Information
Controller
Introduction
P (Proportional Gain)
Controller
The proportional gain indicates the closed-loop control system gain.
Set Points By increasing the gain, the response is increased to permit larger
corrections to the variable to be controlled. The further out of tolerance
Load Sharing
the process is the larger the response action to return the process to
FAQ the control set point. If the gain is configured too high, the result is
Exercises excessive overshoot/undershoot of the desired value.
312
Proprietary Information
Controller
Introduction
I (Integral Gain)
Controller
The integral gain represents the I-component of the PID controller. The
Set Points integral corrects for any offset (between set point and process variable)
automatically over time by shifting the proportioning band. Integral gain
Load Sharing
automatically changes the output requirements until the process
FAQ variable and the set point are the same. This parameter permits the
Exercises user to adjust how quickly the integral attempts to correct for any
offset.
313
Proprietary Information
Controller
Introduction
D (Derivative Ratio)
Controller
The derivative represents the D-component of the PID controller. By
Set Points increasing this parameter, the stability of the system is increased. The
controller will attempt to slow down the action of the throttle in an
Load Sharing
attempt to prevent excessive overshoot or undershoot. Essentially,
FAQ derivative acts as the brake for the process.
Exercises
314
Proprietary Information
Controller
Introduction
63
FREQUENCY
Controller
62
Set Points 61
Load Sharing
60
59
FAQ
58
Exercises 57
TIME
315
Proprietary Information
Controller
Analog / PWM Controller Bias Signal
Introduction
Exercises
316
Proprietary Information
Controller
Introduction
Three Step Controller (Raise/Lower/Off)
Controller
- Time pulse (minimum energize time)
Set Points
- Gain factor
Load Sharing
FAQ
- Dead-band adjustment
Exercises - Expand dead-band function
317
Proprietary Information
Controller
Introduction
Three Step Controller
Controller
The time interval between the raise / lower pulse depends on the actual
Set Points difference between set point and actual value.
Load Sharing
Raise/lower pulse
FAQ
Time delay
Exercises
Difference between setpoint and real value
1 2 3 4 5 6 7 8
318
Proprietary Information
Controller
Introduction
Controller Tuning
Controller
The analog and three-step controllers should ramp in a similar manner as
Set Points shown below when properly tuned.
Load Sharing
FAQ
-120 Volts
Exercises
-90 Volts
-Ramp of Voltage
Controller is
determined by the
-30 Volts Gain
-Point at which
Controller takes
control
-0
Volts
319
Proprietary Information
Set Points
Introduction “AUTOMATIC” operation mode
Controller External Set points
Set Points Frequency set point
Load Sharing
Voltage set point
FAQ
Exercises
Power set point
Power factor set point
Analog inputs
0/4 to 20 mA or 0 to 500 Ohm
Discrete inputs
Raise/lower set point via momentary switch
Interface
320 CANopen or Modbus
Proprietary Information
Set Points
Introduction
Analog Inputs
Controller
Set Points
Load Sharing
FAQ
Exercises
321
Proprietary Information
Set Points
Introduction
Discrete Input for Raise/Lower
Controller
Set Points
Load Sharing
FAQ
Exercises
The power ramp always starts at the current measured value. If the
breaker is opened this set point automatically resets to 0 kW.
322
Proprietary Information
Set Points
Interface Power Set Point
Introduction
Controller
Set Points
Load Sharing
FAQ
Exercises
323
Proprietary Information
Load Sharing
Introduction
Load sharing over the CAN bus
Controller
Real load sharing is performed as a utilization factor.
Set Points (Generators compare measured load:generator rating)
Load Sharing
Reactive load sharing is performed as a utilization factor.
FAQ
(Generators compare measured reactive load:generator rating)
Exercises
Maximum of 32 units can load-share
Split bus applications are possible with up to four bus bars
(different segment numbers)
324
Proprietary Information
Load Sharing
Introduction
Interconnection of Units via CAN 1
Controller
Set Points
Load Sharing
The units require unique
device numbers
FAQ
CAN 1
Exercises
Generator 1
CAN 1
325
More units
Proprietary Information Generator 2
Load Sharing
Introduction
Active Power Load Sharing
Controller
Maintain frequency / maintain power utilization factor
Set Points
Weighting factor may be applied to load sharing
Load Sharing
FAQ
(> 50% more frequency, < 50% more power utilization)
Exercises
326
Proprietary Information
Load Sharing
Segment numbering for multiple common busses
Introduction
General segment definition
Controller
Load Sharing Only the generator connected to the same segment number may load
FAQ
share with each other
Exercises
327
Proprietary Information
Load Sharing
Introduction
Controller
Segment 1
FAQ
Exercises
Segment 2
Load
Segment 3
328 Load
Proprietary Information
Load Sharing
Introduction
Controller
Segment 1
Exercises
Segment 2
Load
Segment 3
329 Load
Proprietary Information
Load Sharing
Introduction
Controller
Segment 1
FAQ
Exercises
Segment 2
Load
Segment #2 TRUE
Segment 3
330 Load
Proprietary Information
FAQ
Introduction
• How can I configure my controller bias signal output?
Controller
Set Points
Load Sharing
FAQ • How can I limit the generator load when the cooling water
Exercises temperature is below a desired threshold?
331
Proprietary Information
FAQ
Introduction
How can I configure my controller bias signal output?
Controller
Set Points
There are two possible types:
Load Sharing
FAQ
- Three step controller (raise / lower outputs)
Exercises
Relays via LogicsManager
332
Proprietary Information
FAQ
Introduction
How can I configure my controller bias signal output?
Controller
Three step controller (raise / lower outputs) LogicsManager
Set Points
Parameters for frequency control
Load Sharing
FAQ
Exercises
Select freely configurable relay
FAQ
Exercises
Data source:
00.02 Voltage bias
00.03 Speed bias
Set Points Use the “warm up limit” of the active load controller
The easYgen controls the warm up load limit (in % of rated power)
Load Sharing
whenever the measured value of the analog
FAQ input drops below the
Exercises threshold.
335
Proprietary Information
FAQ
How can I limit the generator load when the cooling water
Introduction
temperature is below a desired threshold?
Controller
Set Points
The warm up load limit permits a partial load warm up with a lower set point
whenever the generator runs parallel to mains.
Load Sharing
FAQ
Exercises
336
Proprietary Information
Exercise:
Introduction Configure the analog output manager (FlexOut)
Load Sharing
FAQ
Exercises
337
Proprietary Information
End of Section 8
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
3 Operational Modes 8 Controller
4 Configuration and ToolKit 9 Synchronization and Breaker
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
338
Proprietary Information
easYgen-3200 Training
Section 9 - Synchronization and Breaker Logic
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
Introduction Slide 3
Synchronization 4
Breaker Logic 9
FAQ 31
Exercises 32
Proprietary Information
Introduction
Introduction The easYgen-3200 is able to perform synchronization of the generator
Synchronization across the generator circuit breaker to a common bus as well as
Breaker Logic
synchronizing the common bus to a utility across the mains circuit
breaker. It is possible to configure the easYgen-3200 for either slip or
FAQ
phase matching synchronization and the acceptable breaker closure
Exercise
window.
341
Proprietary Information
Synchronization
Introduction The easYgen-3200 has a synchroscope in the HMI
Synchronization
Breaker Logic
Bus/mains Bus/mains
FAQ voltages frequencies
Exercise
Voltage/
frequency Phase
differential angle L1
342
Proprietary Information
Synchronization
Introduction
Slip Synchronization
o
-90 +90
FAQ Configurable synch. frequency differential
Exercise Configurable breaker closing time o
180
Example:
Phase angle = 360o * (0.3 Hz) * (0.2 sec) = 21.6°
343
Proprietary Information
Synchronization
Introduction
Slip Synchronization
o
Synchronization 0
-90 +90
FAQ Define stable timer [3415 Generator stable time]
Exercise Define maximum voltage differential o
180
344
Proprietary Information
Synchronization
Introduction
Phase Matching
Synchronization
-90 +90
FAQ
Exercise
• Define voltage differential window
• Define positive and negative phase angle window limits
o
180
345
Proprietary Information
Synchronization
Introduction
Multiple Synchronization Modes
Synchronization
+90
o
FAQ
governor and voltage regulator are active and breaker
Exercise close commands are issued. o
180
PERMISSIVE
Passive synchronization performed. Bias signals to the
governor and voltage regulator are not active but breaker
close commands are issued.
CHECK
Active synchronization is simulated. Bias signals to the
governor and voltage regulator are active but breaker
close commands are not issued.
OFF
The synchronization can be disabled
346
Proprietary Information
The synchronization modes can be changed via a LogicsManager output
Breaker Logic
Introduction The following MCB/GCB transition modes are available:
Synchronization
5 External
External breaker control (PLC)
347 Only “open” commands issued
Proprietary Information
Breaker Logic
Introduction
Synchronization
Breaker Logic
FAQ
Exercise
348
Proprietary Information
Breaker Logic
Introduction
1. Parallel {2oc} {1oc} {1o} {external}
Synchronization
Parallel breaker logic must be selected for the following operation modes:
Breaker Logic • Isolated operation
FAQ
• Mains parallel operation
349
Proprietary Information
Breaker Logic
2. Interchange {2oc}
Introduction
For this breaker logic to function correctly, the mains power measurement must be
Synchronization connected properly. The following applies for the power display:
• Positive mains power = export power
Breaker Logic
• Negative mains power = import power
FAQ
Exercise
In the event of a start request, a change is made from mains to generator supply.
The following occurs:
• The GCB is synchronized and closed
• The generator assumes load until the imported mains interchange
real power has reached 3 % of the "Generator rated active power”
• The MCB is opened
When a stop request has been issued, a change is made from generator to
mains supply. The following occurs:
• The MCB is synchronized and closed
• The generator sheds load until real power has reached the "Unload
limit" (parameter 3125)
• The generator power factor is controlled to "1.00" (unity)
350 • The GCB is opened
Proprietary Information
Breaker Logic
Introduction
3. CLOSED TRANSIT {2oc}
Synchronization
Exercise In the event of an engine start request, a change is made from mains to
generator supply. The following occurs:
• The GCB is synchronized and closed
• The MCB is opened and the generator assumes all loads
After the engine stop request has been issued, a change is made from generator
to mains supply. The following occurs:
• The MCB is synchronized and closed
• The GCB is opened and the mains assume all loads
351
Proprietary Information
Breaker Logic
Introduction
4. OPEN TRANSIT {2oc}
Synchronization
In the event of an engine start request, a change is made from mains to
Breaker Logic generator supply. The following occurs:
FAQ • The MCB is opened
• The GCB is closed after the time configured in "Transfer
Exercise
time GCB<->MCB" (parameter 3400) has expired
After the engine stop request has been issued, a change is made from generator
to mains supply. The following occurs:
• The GCB is opened
• The MCB is closed after the time configured in "Transfer
time GCB<->MCB“ has expired
352
Proprietary Information
Breaker Logic
Introduction
5. External
Synchronization
Breaker Logic
All breaker control must be carried out via master controller (i.e. PLC).
FAQ
Exercise The easYgen controller always issues the breaker open command
under fault conditions and in the breaker unloading states (Unloading
GCB) if the stop request is active.
353
Proprietary Information
Breaker Logic
Introduction
The MCB operates only if “Enable MCB = TRUE”
Synchronization
The default configuration is as follows:
Breaker Logic
FAQ
Exercise
Closure prevented if
alarm occurs
Closure prevented if
field rotation is wrong
354
Proprietary Information
FAQ
Introduction
How do I define the operating ranges for synchronization ?
Synchronization
The operating ranges are utilized for permitting breaker closures and defining when
Breaker Logic an emergency mode should be initiated.
FAQ
Exercise
- Generator Mains
355
Proprietary Information
Exercise
Introduction
Configure the following application:
Synchronization
1. You are commissioning an emergency standby generator for a manufacturing
Breaker Logic plant. Select a “breaker logic” for the test run where the generator assumes
FAQ
the entire plant load and then separates from the utility. The test mode must
be initiated via a discrete input.
Exercise
2. A second “breaker logic” mode is desired where the generator assumes the
entire plant load but still remains paralleled with the utility.
Load
356
Proprietary Information
Solution
Introduction
1) Test mode with the generator running isolated from mains
Synchronization
FAQ
Exercise
357
Proprietary Information
Solution
Introduction
1) Test mode with the generator running isolated from mains
Synchronization
Select transition mode “Interchange” to open the breaker at zero power
Breaker Logic
FAQ
Exercise
Mains CT required!
358
Proprietary Information
Solution
Introduction 1) Test mode with the generator running isolated from mains
Synchronization
Use discrete input 10 also as start command via “Start in Auto”
Breaker Logic
FAQ
Exercise
359
Proprietary Information
Solution
Introduction
2) Test mode with the generator running parallel to mains
Synchronization
Select “Parallel” transition mode and configure the “Load set point” to Import 0 kW
Breaker Logic
FAQ
Exercise
360
Proprietary Information
Solution
Introduction
2) Test mode with the generator running parallel to mains
Synchronization
Use discrete input 10 also as start command via “Start in Auto”
Breaker Logic
FAQ
Exercise
361
Proprietary Information
End of Section 9
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
3 Operational Modes 8 Controller
4 Configuration and ToolKit 9 Synchronization and Breaker
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
362
Proprietary Information
easYgen-3200 Training
Section 10 - Application
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
Introduction Slide 3
Start / Stop in Auto 4
Logical Outputs 6
Start / Stop 10
Alarm Classes 14
Protection 15
FAQ 23
Proprietary Information
Introduction
Introduction
Logical Outputs
This section is a quick review of
previous sections as well as a more
Start / Stop
detailed description of software
Alarm Classes
ehancements.
Protection
FAQ
365
Proprietary Information
Start / Stop in Auto
Introduction Generator:
Logical Outputs
Start / Stop
Alarm Classes
Protection
FAQ
367
Proprietary Information
Logical Outputs
Introduction
Hierarchy of Logical Outputs:
Start /Stop Auto
Logical Outputs
Start
Start / Stop
Start, breaker depending
Alarm Classes
on parameter
Protection
No start
FAQ
Open breaker
Close breaker
Close breaker with pause
No start
Open breaker
368
Proprietary Information
Logical Outputs
Introduction
Alarm Classes
Protection
FAQ
369
Proprietary Information
Start / Stop Logic
Introduction
Diesel Engine
Start /Stop Auto
- Pre-glow function
Logical Outputs
- Fuel or Stop solenoid activation
Start / Stop
- Crank/start circuit control
Alarm Classes
Protection
Gas Engine
FAQ - Ignition
- Gas valve
- Crank/start circuit control
External Logic
- Fuel solenoid as a start request to external controllers
- External control must take care of start sequence – no start failure
370
Proprietary Information
Start / Stop Sequence
Introduction Diesel Engine
Start /Stop Auto
Logical Outputs
Start / Stop
Alarm Classes
Protection
FAQ
371
Proprietary Information
Start / Stop Sequence
Introduction Gas Engine
Start /Stop Auto
Logical Outputs
Start / Stop
Alarm Classes
Protection
FAQ
372
Proprietary Information
Alarm Classes
Class Action Result
Introduction
Display Warning
Logical Outputs
Start / Stop
Display and Horn Warning
Alarm Classes
Protection
Display and Horn Unlaod Gen. And open GCB Cool down Shut down
FAQ
Display and Horn Open GCB immediate Cool down Shut down
Display and Horn Unlaod Gen. And open GCB Immediate Stop Shut down
Display and Horn Open GCB immediate Immediate Stop Shut down
373
Proprietary Information
Generator Protection
Introduction # of Trip Levels ANSI Code
Over-/undervoltage 2/2 [59/27]
Start /Stop Auto
Voltage asymmetry 1 [47]
Logical Outputs
Over-/underfrequency 2/2 [81O/U]
Start / Stop Overload (IOP/MOP) 2 [32]
Alarm Classes
Reverse/reduced power 2 [32R/F]
Unbalanced load 2 [46 measured]
Protection
Definite time-overcurrent 3 [50/51]
FAQ
Inverse time-overcurrent 1 [IEC 255]
Overspeed (MPU) 2 [12]
Measured ground current 2 [50G]
Calculated ground current 2
374
Proprietary Information
Generator Protection
Introduction
# of Trip Levels ANSI Code
Start /Stop Auto
Power factor (PF) lagging 2
Logical Outputs PF leading – loss of excitation 2 [40Q]
Start / Stop
Phase rotation field CW/CCW 1
Alarm Classes
Psetpoint Pactual mismatch 1 Controller*
Unload mismatch (time out monitoring) 1 Controller*
Protection
Operating range failed 1 Controller*
FAQ
375
Proprietary Information
Engine Protection
Introduction
Maintenance days exceeded
Start /Stop Auto
Start / Stop
Over-/Underspeed (MPU)
Alarm Classes Unintended Stop
Protection
Engine Stop malfunction
FAQ
Speed/frequency mismatch
Start failure
Charge alternator low voltage
Red stop lamp (J1939)
Amber warning lamp (J1939)
Battery over-/undervoltage
376
Proprietary Information
Mains Monitoring and Decoupling
# of Trip Levels ANSI Code
Introduction
Over-/undervoltage 2/2 [59/27 ]
Start /Stop Auto
Over-/underfrequency 2/2 [81O/U]
Logical Outputs Import/Export power 2 [32]
Start / Stop
Power factor leading 2
Power factor lagging 2
Alarm Classes
Phase shift 1ph/3ph [78 ]
Protection
Field rotation
FAQ
377
Proprietary Information
Miscellaneous Monitoring
Introduction
GCB / MCB fail to close
FAQ
CAN bus communications monitoring (J1939, CANopen)
Parameter alignment (multiple units)
Missing members (multiple units)
EEPROM failure (internal CPU)
Wire break analog inputs
Discrete inputs
378
FlexLimitsTM for analog values
Proprietary Information
Software Enhancements Version
1.12
Introduction Password for ToolKit required
Start /Stop Auto
Display hibernation / backlight shutdown
Logical Outputs
Start / Stop
Daylight saving time implemented, fully adjustable
Alarm Classes
Protection
LogicsManager: Status display of input command
FAQ variables
379
Proprietary Information
Software Enhancements Version
1.12
Introduction
FAQ
• New MAN MFR/EDC7 ECU (J1939) coupling
• ECU alarm messages now in event list
• HMI populates only with J1939 messages
broadcast by ECU
• Alarm reset message (DM 11) is sent to J1939
members
380
Proprietary Information
Software Enhancements Version
1.12
Introduction
Start / Stop • Multiple set points now available via Analog Manager
Alarm Classes (ramped values, without ramp) for external use
Protection
FAQ
• Import / export power control set point performed via
ramp
• Droop tracking: frequency does not drop off when
droop is being activated
• LM “Discrete +/-” of set points now also active in
MANUAL mode
381
Proprietary Information
FAQ Version
1.12
Introduction How can I adjust the daylight saving time?
Start /Stop Auto
Each region has its specific parameters. Possible options are:
Logical Outputs
382
2009 March 08, 2009 November 01, 2009
Proprietary Information
FAQ Version
1.12
Introduction How can I adjust the daylight saving time?
Start /Stop Auto
Available parameters, example for Germany:
Logical Outputs
Start / Stop
Alarm Classes
Protection
FAQ
383
Proprietary Information
End of Section 10
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
3 Operational Modes 8 Controller
4 Configuration and ToolKit 9 Synchronization and Breaker
5 Communication 10 Application
11 Sequencing
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to
update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward
product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and
applications.
384
Proprietary Information
easYgen-3200 Training
Section 11 - Sequencing
marked
CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies
Proprietary Information
Contents
Introduction slide 3
Getting Started 5
Start/Stop 10
Calculation 17
Exercises 40
Proprietary Information
Introduction
Introduction Multiple easYgen-3000s may be configured to sequence generators
Getting started on- and offline in order to supply the power required while operating
Start/Stop
the power plant with a high degree of efficiency. This sequencing is
performed automatically through a Load Dependant Start/Stop
Calculation
(LDSS) calculation in the easYgen software according to the
Exercises
thresholds configured by the user.
387
Proprietary Information
Introduction
Introduction
Isolated and mains parallel operations
Getting Started
Start/Stop
388
Proprietary Information
Getting Started
Introduction
Connection between the units via CAN 1
Getting Started
Start/Stop CAN 1
Calculation
Exercises
389
Proprietary Information
Getting Started
Introduction
Enable LDSS Sequencing
Getting Started
Start/Stop
Calculation
Exercises
390
Proprietary Information
Getting started
Introduction
Enable LDSS Sequencing
Getting Started
Only generators on the same bus segment can be sequenced.
Start/Stop
Calculation
Exercises
bus 1 Load
bus 2
391 Load
Proprietary Information
Getting Started
Introduction
Status Screen
Getting Started
- Operation mode and breaker feedback status
Start/Stop
- Add on/off condition
Calculation
- Measured values
Exercises
392
Proprietary Information
Getting Started
Introduction
Status Screen
Getting Started
Start/Stop
Calculation
Exercises
393
Proprietary Information
Start/Stop Mode
Load-dependent start/stop may either be performed according to a system
Introduction
reserve power or the generator load depending on the configuration of the
Getting Started "Start stop mode“.
Start/Stop Reserve power
Load-dependent start/stop is performed so a configured minimum reserve power
Calculation
is maintained in the system. This provides enough reserve power for load swings
Exercises regardless of the generator load. The actual reserve power in the system is the
total rated power of all gensets minus the actual total generator real power. This
provides high system reliability and is intended for applications that require a
dedicated reserve power on the load bus, independent of the number of gensets.
Generator load
Load-dependent start/stop is performed so the next genset will be started if all
gensets in operation reach the maximum generator load percentage of the rated
power. A generator will be stopped when the load of all gensets in operation fall
below the configured minimum generator percentage of the rated power.
An additional Dynamic parameter prevents the gensets from being started and
stopped continusously if only a few gensets are in operation. The Dynamic is only
394 considered for the start sequence if "Fit size of engines" is enabled.
Proprietary Information
Dead Bus Start Mode
Introduction (Loss of Mains Condition)
Getting Started
Start/Stop
All
Calculation
All available engines will start and supply the load. If the minimum
Exercises
running time is expired the LDSS sequencing calculates how many
engines will be required to supply power to the load and sequences
generators offline.
LDSS
Only one generator is started and closed to the busbar. The LDSS
sequencing calculates if additional units are required and additional
generators are sequenced online accordingly. Load sequencing
schemes are typically used with this type of dead bus starting to
prevent overloading the generator.
395
Proprietary Information
Start/Stop Priority
Multiple Start/Stop Priority Selections are Available
Introduction
Getting Started
1 Assigned generator priority
If a genset is to be started, the genset with the highest priority configured will be
Start/Stop
started. If a genset is to be stopped, the genset with the lowest priority configured
Calculation will be stopped.
Exercises 2 Efficiency, fit size of engine
If all gensets have the same priority, the next genset is selected according to the
size of engine, i.e. the genset combination, which allows an optimum efficiency will
be used.
3Service Hours, based on maintenance hours or change of
engines according to run time
If all gensets have the same rated load or this parameter is disabled, the remaining
hours until the next maintenance are considered.
4 Assigned generator number (device number)
If all else are equal, the genset with the lowest generator number will be started first
or stopped last.
396
Proprietary Information
Start/Stop Priority
Introduction
11. Base or Alternative Priority Sequencing
Getting Started
- Lowest number has the highest priority
Start/Stop
- Generator assigned priority
Calculation
397
Proprietary Information
Start/Stop Priority
Introduction
22. Fit Size of Engine Sequencing
Getting Started
- For use with multiple engine sizes
Start/Stop
- Calculation for optimal efficiency
Calculation
398
Proprietary Information
Start/Stop Priority
Introduction
33. Fit Service Hours Sequencing
Getting Started
Equal – maintenance at the same time
Start/Stop
Start unit with the highest service hours remaining
Calculation
Works only if the Base or LogicsManager Priority and Fit of Engine are
equal
399
Proprietary Information
Start/Stop Priority
Introduction
34. Change of Engines when Fit Service Hours is Equal
Getting Started
The easYgen-3000 divides the time remaining on the maintenance hours
Start/Stop
counter by the service hours group (32/64/128h) to determine the
Calculation individual unit’s time group.
Exercises
Example:
Unit 1: 254 h 254 / 64 = 3.96 Time group 3
Unit 2: 325 h 325 / 64 = 5.07 Time group
Unit 3: 284 h 284/ 64 = 4.44 Time group 4
The unit 2 is the next unit to start
Higher calculated time group
400
Proprietary Information
Start/Stop Priority
Introduction
3 Change of Engines when Fit Service Hours is Staggered
Getting Started
The easYgen-3000 divides the time remaining on the maintenance hours
Start/Stop
counter by the service hours group (32/64/128h) to determine the
Calculation individual unit’s time group.
Exercises
Example:
Unit 1: 254 h 254 / 64 = 3.96 Time group 3
Unit 2: 325 h 325 / 64 = 5.07 Time group 5
Unit 3: 284 h 284/ 64 = 4.44 Time group 4
The unit 1 is the next unit to start
Lower calculated time group
401
Proprietary Information
Start/Stop Priority
Introduction
42. Generator Number
Getting Started
Lowest device number -> highest priority
Start/Stop
Calculation
Exercises
402
Proprietary Information
Calculation
Introduction
System Reserve Power
Getting Started
Generators are sequenced on and off to maintain a spinning reserve for
Start/Stop
the plant. This reserve power threshold is used to calculate when
Calculation additional generators are required to be started or shutdown.
Exercises
403
Proprietary Information
Calculation
Introduction
System Reserve Power – Mains Parallel
Getting Started
Start/Stop
Start/Stop
30 kW
Calculation 170 kW Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Reserve power 30 kW
Hysteresis 10 kW
Start/Stop
15 kW 185 kW
Calculation Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Reserve power 30 kW
15 kW
185 kW Hysteresis 10 kW
Getting Started
Start/Stop
Calculation
Exercises
600
500
Start/Stop
15 kW+5 kW 120 kW
Calculation Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Reserve power 30 kW
15 kW+5 kW 120 kW Hysteresis 10 kW
Start/Stop
30 kW+10 kW
Calculation 80 kW Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Reserve power 30 kW
80 kW Hysteresis 10 kW
409
Load
Proprietary Information
Calculation
Introduction
System Reserve Power – Mains Parallel
Getting Started
Start/Stop
Getting Started
Start/Stop
Calculation
Exercises
410 kW 210 kW 60 kW
Third engine stops Second engine stops Last engine stops
600
500
Exercises The following unit uses the same formula like mains parallel
Actual total generator power > total rated power – reserve power
Stop condition
The same formula like mains parallel
Actual total generator power < total rated power (n-1) –
reserve power - hysteresis
Last unit keeps running
412
Proprietary Information
Calculation
Introduction
Generator Load Capacity
Getting Started
Generators are sequenced on and off based on configured values for
Start/Stop
minimum and maximum percent of rated load. This permits online
Calculation generators to be loaded to the maximum limit before the next generator is
Exercises started. When connected load reduces to the minimum load limit, then a
generator is removed and shutdown.
Start/Stop
Start/Stop
40 kW
Calculation 160 kW Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Hysteresis 5 kW
Start/Stop
40 kW 160 kW
Calculation Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Hysteresis 5 kW
40 kW 160 kW Max. load 80%
Min. load 40%
Getting Started
Start/Stop
Calculation
Exercises
600
500
Start/Stop
Calculation
120 kW 80 kW Power set point Import 50 kW
Minimum power 20 kW
Exercises
50 kW Hysteresis 5 kW
120 kW 80 kW Max. load 80%
Min. load 40%
Start/Stop
120 kW
Calculation 80 kW Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Hysteresis 5 kW
80 kW Max. load 80%
Min. load 40% !!!
Start/Stop
185 kW
Calculation 15 kW Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Hysteresis 5 kW
Max. load 80%
Min. load 40%
420
Load
Proprietary Information
Calculation
Introduction
Generator Load – Mains Parallel
Getting Started
Start/Stop
Mains load
421
Load
Proprietary Information
Calculation
Introduction
Getting Started
Start/Stop
Calculation
Exercises
290 kW 210 kW 65 kW
Third engine stops Second engine stops Last engine stops
600
500
Exercises Constants:
80%
Low dynamic = 25% MAX
75%
Moderate dynamic = 50% HIGH
High dynamic = 75% 50%
MOD
423
Proprietary Information
Calculation
Introduction
Generator Load (differing sizes) – Mains Parallel
Getting Started
Start/Stop
Calculation
100 kW genset: Min 100 kW * 0.40 = 40 kW, Max 100 kW * 0.70 = 70 kW
Exercises 200 kW genset: Min 200 kW * 0.40 = 80 kW, Max 200 kW * 0.70 = 140 kW
425
Proprietary Information
Calculation
Introduction
Generator Load – Mains Parallel
Getting Started
Start/Stop
426
Load
Proprietary Information
Calculation
Introduction Generator Load (differing sizes) – Mains Parallel
Getting Started
50 kW genset: Min 50 kW * 0.40 = 20 kW, Max 50 kW * 0.70 = 35 kW
Start/Stop
Calculation
100 kW genset: Min 100 kW * 0.40 = 40 kW, Max 100 kW * 0.70 = 70 kW
Exercises 200 kW genset: Min 200 kW * 0.40 = 80 kW, Max 200 kW * 0.70 = 140 kW
427
Proprietary Information
Calculation
Introduction
Generator Load (differing sizes) – Mains Parallel
All Gensets connected and load drops to 190 kW.
Getting Started
Start/Stop
Calculation
120 kW 80 kW Power set point Import 50 kW
Minimum power 20 kW
Exercises
50 kW Hysteresis 5 kW
70 kW 40 kW Max. load 70%
Min. load 40%
Calculation
100 kW genset: Min 100 kW * 0.40 = 40 kW, Max 100 kW * 0.70 = 70 kW
Exercises 200 kW genset: Min 200 kW * 0.40 = 80 kW, Max 200 kW * 0.70 = 140 kW
429
Proprietary Information
Calculation
Introduction
Generator Load (differing sizes) – Mains Parallel
Getting Started
Start/Stop
107 kW
Calculation 93 kW Power set point Import 50 kW
Exercises Minimum power 20 kW
50 kW Hysteresis 5 kW
53 kW 47 kW Max. load 70%
Min. load 40%
430
Load
Proprietary Information
Calculation
Introduction
Generator Load (differing sizes) – Mains Parallel
Getting Started
Start/Stop
431
Load
Proprietary Information
Exercise: Reserve Power
Configure the load dependent start/stop for a mains parallel application with
Introduction two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started
sees common load shift of 10-15 kW with occasional 20 kW pump operation.
Start/Stop
Calculations and configurations:
Calculation 1. Mains interchange power set point Import 50 kW
Exercises 2. Determine an acceptable hysteresis
3. Set minimum running load for generators at 25 kW
4. Determine at what import power will the first generator
initiate start
5. Determine an acceptable reserve power value
6. Determine at what facility power will the second
generator initiate start
7. Determine at what facility power will the second
generator shut down
8. Determine at what facility power will the first generator
432
Proprietary Information
shut down
Exercise: Solution 1
Configure the load dependent start/stop for a mains parallel application with
Introduction
two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started sees common load shift of 10-15 kW with occasional 20 kW pump operation.
Start/Stop Mains interchange power set point Import 50 kW
Calculation Parameter
Exercises
Configuration
Configure application
Configure controller
Configure load control
Load set point 1 or 2 source (5539) Internal pwr. setp.1
Load set point 1 or 2 (5526) Import
Int. load control set point 1 or 2 (5520) 50 kW
433
Proprietary Information
Exercise: Solution 2
Configure the load dependent start/stop for a mains parallel application with
Introduction two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started
sees common load shift of 10-15 kW with occasional 20 kW pump operation.
Start/Stop
Determine an acceptable hysteresis
Calculation Parameter
Exercises Configuration
Configure application
Configure automatic run
Load dependent start/stop
Mains parallel operation
Determine hysteresis based on facility loads. Hysteresis needs to be larger than the
common load swings. At 15 kW shifts, assume a hysteresis of 20 kW.
MOP Hysteresis [5769] 20 kW
434
Proprietary Information
Exercise: Solution 3
Configure the load dependent start/stop for a mains parallel application with
Introduction
two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started sees common load shift of 10-15 kW with occasional 20 kW pump operation.
Start/Stop
Set minimum running load for generators at 25 kW
Calculation Parameter
Exercises Configuration
Configure application
Configure automatic run
Load dependent start/stop
Mains parallel operation
Minimum running load = MOP min (starting) load [5767] – MOP Hysteresis [5769]
25 kW= MOP Min Load – 20 kW, MOP Min Load = 25 kW + 20 kW
MOP Minimum load [5767] 45 kW
435
Proprietary Information
Exercise: Solution 4
Configure the load dependent start/stop for a mains parallel application with
Introduction two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started
sees common load shift of 10-15 kW with occasional 20 kW pump operation.
Start/Stop Determine at what inport power will the first generator initiate start
Calculation Parameter
Exercises
Configuration
Configure application
Configure automatic run
Load dependent start/stop
Mains parallel operation
Import load set point + MOP min load = Import power level
50 kW + 45 kW = 95 kW
436
Proprietary Information
Exercise: Solution 5
Configure the load dependent start/stop for a mains parallel application with
Introduction
two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started sees common load shift of 10-15 kW with occasional 20 kW pump operation
Start/Stop
Determine an acceptable reserve power value
Calculation Parameter
Exercises Configuration
Configure application
Configure automatic run
Load dependent start/stop
Mains parallel operation
MOP Reserve Power [5768] = Value greater than maximum anticipated added load
above normal operation (20 kW pump). Assume reserve of 25 kW
MOP Reserve Power [5768] 25 kW
437
Proprietary Information
Exercise: Solution 6
Configure the load dependent start/stop for a mains parallel application with
Introduction
two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started sees common load shift of 10-15 kW with occasional 20 kW pump operation
Start/Stop Determine at what facility power will the second generator initiate start
Calculation Parameter
Exercises
Configuration
Configure application
Configure automatic run
Load dependent start/stop
Mains parallel operation
Import load set point + (Gen 1 rated – reserve) = facility power level
50 kW + (100 kW – 25 kW) = 125 kW
438
Proprietary Information
Exercise: Solution 7
Configure the load dependent start/stop for a mains parallel application with
Introduction
two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started sees common load shift of 10-15 kW with occasional 20 kW pump operation
Start/Stop
Determine at what facility power will the second generator shut down
Calculation
Parameter
Exercises
Configuration
Configure application
Configure automatic run
Load dependent start/stop
Mains parallel operation
Import load set point + Gen 1 MOP Min Load + Gen 2 MOP Min load – MOP
Hysteresis = facility power level for Gen 2 shut down
50 kW + 45 kW + 45 kW – 20 kW = 120 kW
439
Proprietary Information
Exercise: Solution 8
Configure the load dependent start/stop for a mains parallel application with
Introduction
two 100kW peak shaving generators with reserve power sequencing. Facility
Getting Started sees common load shift of 10-15 kW with occasional 20 kW pump operation
Start/Stop
Determine at what facility power will the first generator shut down
Calculation
Parameter
Exercises
Configuration
Configure application
Configure automatic run
Load dependent start/stop
Mains parallel operation
Import load set point + Gen 1 MOP Min Load – MOP Hysteresis = facility power
level for Gen 1 shut down
50 kW + 45 kW– 20 kW = 75 kW
440
Proprietary Information
Exercise: Generator Load
Configure the load dependent start/stop for an isolated plant with three
Introduction generators (1-100kW, 1-200kW, 1-300kW) with generator load sequencing.
Getting Started
The 100kW gen is the first on the bus. Assume a Moderate (50%) dynamic,
equal priority, best fit selected
Start/Stop
Exercises
1. Set maximum generator operating load
2. Set minimum generator load
3. Determine at what power level does the next generator start
4. Determine which generator(s) is on line with 100 kW facility load
5. Determine at what power level does the third generator start
6. Given exercise 5, which generators would be left connected
with a High Dynamic
441
Proprietary Information
Exercise: Solution 1
Configure the load dependent start/stop for an isolated plant with three
Introduction
generators (1-100kW, 1-200kW, 1-300kW) with generator load sequencing.
Getting Started The 100kW gen is the first on the bus. Assume a Moderate (50%) dynamic,
equal priority, best fit selected
Start/Stop
442
Proprietary Information
Exercise: Solution 2
Configure the load dependent start/stop for an isolated plant with three
Introduction
generators (1-100kW, 1-200kW, 1-300kW) with generator load sequencing.
Getting Started The 100kW gen is the first on the bus. Assume a Moderate (50%) dynamic,
equal priority, best fit selected
Start/Stop
Calculation
Determine at what power level does the next generator start
Exercises
In General, the next start occurs when:
Plant load > Sum of rated powers of the generators online * IOP max
generator load [5762]
100 kW * 0.85 = 85 kW for Next to start
444
Proprietary Information
Exercise: Solution 4
Configure the load dependent start/stop for an isolated plant with three
Introduction
generators (1-100kW, 1-200kW, 1-300kW) with generator load sequencing.
Getting Started The 100kW gen is the first on the bus. Assume a Moderate (50%) dynamic,
equal priority, best fit selected
Start/Stop
Calculation
Determine at what power level does the third (200kW) generator start
Exercises
In General, the next start occurs when:
Plant load > Sum of rated powers of the generators online * IOP max
generator load [5762]
(100 kW + 300 kW) * 0.85 = 340 kW for third to start
446
Proprietary Information
Exercise: Solution 6
Configure the load dependent start/stop for an isolated plant with three
Introduction
generators (1-100kW, 1-200kW, 1-300kW) with generator load sequencing.
Getting Started The 100kW and 300kW gensets are on the bus. Assume a High (75%)
dynamic, equal priority, best fit selected
Start/Stop
Calculation
Determine at what power level does the third (200kW) generator start
Exercises
In General, the next start occurs when:
Plant load > Sum of rated powers of the generators online * IOP max
generator load [5762]
(100 kW + 300 kW) * 0.85 = 340 kW for third to start
447
Proprietary Information
End of Presentation
1 Overview 6 LogicsManager
2 Hardware and I/O 7 Analog Manager
3 Operational Modes 8 Controller
4 Configuration and ToolKit 9 Synchronization and Breaker
5 Communication 10 Application
11 Sequencing