ELECTRICAL SYSTEM

1x15 MW CFB POWER PLANT


ELECTRICAL SYSTEM
Overview
• The electrical system is designed as single bus
• The generator parallel in 34.5 kV bus
• 4.16 kV station service bus
• Operation section
• Standby section
ELECTRICAL SYSTEM
Overview
• 460 V station service bus
• Low voltage station service bus
• Coal conveying bus
• Chemical water treatment bus
• Low voltage station standby bus
• Coal conveying standby bus
• Coal water treatment standby bus
• Emergency section bus
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
Generator
• Model: QFW-15-4
• Brushless Turbogenerator
• Output power 15 MW / 18.75 MVA
• 4 poles
• Rotating Direction: CCW viewing from Turbine to
Generator
• Rated Voltage: 13.8 kV
• Rated Current: 784 A
ELECTRICAL SYSTEM
Generator
• Rated Speed: 1800 rpm
• Armature winding is wye-connected
• Cooling Type: Air Cooled
ELECTRICAL SYSTEM
Components of Generator
• Field
• Consists of coils of conductors within the generator that
receive a voltage from a source and produce a magnetic
flux
• Armature
• Part of a generator in which voltage is produced
• Carry the full load current of generator
ELECTRICAL SYSTEM
• Prime Mover
• Used to drive the generator
• Type of rotating machine such as a diesel engine, a
steam turbine
• Rotor
• Rotating component of the generator
• Driven by prime mover
• The rotor will be armature if the voltage output is
generated there, the rotor will be the field if the field
excitation is applied there
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
Parallel Operation Conditions of Generator
• Same phase sequence with system
• Equal voltage with system
• Same frequency with system
• Same phase position with system
ELECTRICAL SYSTEM
Main Transformer
• Model: S20000/34.5
• Rated Power: 20,000 kVA
• Rated Voltage: (34.5±2x2.5%)/13.8 kV
• Rated Current: 334.7/836.7 A
• Vector Group: YnD5
• Cooling Type: ONAN
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
High Voltage Auxiliary Transformer
• Model: S11-3150/13.8
• Rated Power: 3150 kVA
• Rated Voltage: (13800±2x2.5%)/4160 V
• Rated Current: 131.8/437.2 A
• Vector Group:DYn5
• Cooling Type: ONAN
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
Start-up/Standby Transformer
• Model: S11-3150/34.5
• Rated Power: 3150 kVA
• Rated Voltage: (34500±2x2.5%)/4160 V
• Rated Current: 52.7/437.2 A
• Vector Group: YnYn10+D
• Cooling Type: ONAN
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
ELECTRICAL SYSTEM
Parallel Operation Conditions of Transformer
• Same vector group
• Same ratio of transformation
• Equal Impedance Voltage
• Same phase sequence