Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Transient Stability
Depending on the severity of the disturbance, the rotor angle
instability can be classified into two categories:
Transient instability:
In this case, the disturbance on the system is quite severe and
sudden and the machine is unable to maintain synchronism
under the impact of this disturbance.
Basic concept of ‘Synchronism’ cont…
J m (t ) Tm (t ) Te ( t ) Ta (t )
J=total moment of inertia of the rotating masses, kgm2
J m (t ) Tm (t ) Te ( t ) Ta (t )
J m (t ) Tm (t ) Te ( t ) Ta (t )
Self: Do It
Figure:
pe & pm
vs
Suppose the unit is initially
operating in steady-state at
pe = pm = pm0 and =0,
when a step change in pm
from pm0 to pm1 occurs at t =
0. Due to rotor inertia, the
rotor position cannot
change instantaneously.
That is, m(0+)= m(0-);
therefore, (0+)= (0-)=o
and pe(0+)= pe(0-).
Since pm(0+)= pm1 is greater than pe(0+), the acceleration power
pa(0+) is positive and, (d2)/(dt2)(0+) is positive. The rotor
accelerates and increases. When reaches 1, pe=pm1 and
(d2)/(dt2) becomes zero. How ever, (d)/(dt) is still positive and
continues to increase, overshooting its final steady-state
operating point. When is greater than 1, pm is less than pe, pa
is negative, and the rotor decelerates.
Find the difference between the two Figures
EXAMPLE 11.3 Generator internal voltage and real power output versus power angle
P.U.
(b)
EXAMPLE 11.4 Equal-area criterion: transient stability during a
three-phase fault The synchronous generator shown in Figure is
initially operating in the steady-state condition given in Example
11.3, when a temporary three-phase to-ground bolted short circuit
occurs on line 1–3 at bus 1, shown as point F in Figure. Three
cycles later the fault extinguishes by itself. Due to a relay
misoperation, all circuit breakers remain closed. Determine whether
stability is or is not maintained and determine the maximum power
angle. The inertia constant of the generating unit is 3.0 per unit-
seconds on the system base. Assume pm remains constant throughout
the disturbance. Also assume p.u(t)=1.0 in the swing equation.
=0.4964 radian=28.44o
Integrating,
3=2.7236 rad
Example 11.4
3=2.7236 rad
cr
Solving for cr,
cr
cr
cr
Thevenin
Eq Faulted
Network Post fault conditions
shown in Fig, and the The´venin equivalent of the faulted
network, as viewed from the generator internal voltage source,
is shown in Fig. The The´venin reactance is XTh=0.40+
0.20‖0.10=0.46666 per unit and the The´venin voltage source is
Thevenin
Eq
Faulted
Network
accelerating
area A1 and
decelerating
area A2
Where:
• is the angular position of the rotor with respect to a stationary axis in (rad)
• is time in seconds (s)
• is the mechanical torque supplied by the prime mover in N-m
• is the electrical torque output of the alternator in N-m
• is the net accelerating torque, in N-m
In order to determine the transient stability of a power system using swing equation, let us
consider a synchronous generator supplied with input shaft power PS producing mechanical
torque equal to TS as shown in the figure below. This makes the machine rotate at a speed of ω
rad/sec and the output electromagnetic torque and power generated on the receiving end are
expressed as TE and PE respectively.
When, the synchronous generator is fed with a supply from one end and a constant load is
applied to the other, there is some relative angular displacement between the rotor axis and the
stator magnetic field, known as the load angle δ which is directly proportional to the loading of
the machine. The machine at this instance is considered to be running under a stable condition.
Now if we suddenly add or remove load from the machine the rotor decelerates or accelerates
accordingly with respect to the stator magnetic field. The operating condition of the machine
now becomes unstable and the rotor is now said to be swinging w.r.t the stator field and the
equation we so obtain giving the relative motion of the load angle δ w.r.t the stator magnetic
field is known as the swing equation for transient stability of a power system.
https://www.electrical4u.com/transient-stability-and-swing-equation/
Example: A generator is operating al a load angle of 30° and transmitting power over two
parallel lines. The load angle across the lines is 25°. If all of the load is slowly shifted to
one power line. will the line and load remain stable?
An,wer; Using the 'ame power transfer equations as before. And assuming P, YL and YT all
remain constant, then sin lit. is proportional 10 XL When lit. is 25°, sin lit. = 0.423 with line
reactance of XL. When XL increases to 2XL, sin lit. will increase to 2(0.423) = 0.845.
This gives a new value ofau for the line load angle where au = arc sin 0.845 = 57.6°, this gives a
combined load angle for the generator and line of (30° + 57.6°) = 87.6°.
Under this condition the generator and line are operating at just less than 90° and will
therefore remain stable. II should be appreciated that any slight change in generator output or
other conditions will cause the system to become unstable. It would be most undesirable to
operate under these conditions.
11.16 Two-Axis Synchronous Machine Model
The classical model for a synchronous machine provides a
useful mechanism for introducing transient stability concepts, it is
only appropriate for the most basic of system studies. Also, it
cannot be coupled with the exciter and governor models that will
be introduced in the next chapter. The analysis of more detailed
and more realistic synchronous machine models requires that
each machine model be expressed in a frame of reference that
rotates at the same speed as its rotor. The standard approach is
to use a d-q reference frame in which the major ‘‘direct’’ (d) axis
is aligned with the rotor poles, and the quadrature (q) axis leads
the direct axis by 90o. The rotor angle is then defined as the
angle by which the q-axis leads the network reference frame see
Figure. The equation for transforming the network quantities to
the d-q reference frame is given
Reference frame
transformations
A non salient
two-pole rotor
for a
synchronous
machine. A salient six-pole rotor for
a synchronous Machine.
Nonsalient pole Salient Pole
Synchronous Machine
The damper winding consists of short circuited
copper bars embedded in the face of the rotor
poles When there is change in load, excitation or
change in other conditions of the systems, rotor
of the synchronous motor/generator will oscillate
to and fro about an equilibrium position.
Field Field
Winding Winding
Two Pole Cylindrical Rotor Machine Four Pole Salient Rotor Machine
Synchronous Machines
Stator of a salient pole hydro generator; the insulated conductors and spacers.
Synchronous Machines
Slip
rings
Pole
DC excitation
winding
Fan
Rotor of a four-pole salient pole generator.
FIGURE 5-3 A brushless exciter circuit. A small three-phase current is rectified and used to
supply the field circuit of the exciter, which is located on the stator. The output of the armature
circuit of the exciter (on the rotor) is then rectified and used to supply the field current of the
main machine.
FIGURE 5-4: Photograph of a synchronous machine rotor with a brush less exciter mounted on
the same shaft. Notice the rectifying electronics visible next to the armature of the exciter.
(Courtesy of Westinghouse Electric Company.)
FIGURE 5-5: A brushless excitation scheme that includes a pilot exciter. The permanent magnets
of the pilot exciter produce the field current of the exciter. which in turn produces the field
current of the main machine.
Fig 5-3 (Page 253) Brushless exciter
Slip
rings
Pole
DC excitation
winding
Fan
ROTOR
Red
Yellow
Three-Phase output
Blue
If,
ϕd is the direct axis flux
Φq is the quadrature axis flux
Rd is the reluctance of the direct axis flux path
BY APPLYING PARK’S
TRANSFORMATION, THE TIME
VARYING INDUCTANCES
BECOME CONSTANTS
The rotor flux BR is shown vertically upwards as shown in the figure below. The rotor flux
induces a voltage Ef in the stator. The stator armature current Ia will flow through the
synchronous motor when a lagging power factor load is connected it. This stator armature
current Ia lags behind the generated voltage Ef by an angle Ψ.
The armature current produces stator magnetomotive force Fs. This MMF lags behind Ia by
angle 90 degrees. The MMF FS produces stator magnetic field BS long the direction of Fs. The
stator MMF is resolved into two components, namely the direct axis component Fd and the
quadrature axis component Fq.
Salient Pole Synchronous Machine Two Rection
Theory
The axis along the axis of the rotor is called the direct or the d axis. The axis perpendicular to d
axis is known as the quadrature or q axis. The direct axis flux path involves two small air gaps
and is the path of the minimum reluctance. The path shown in the above figure by ϕq has two
large air gaps and is the path of the maximum reluctance.
FlGURE 4- 19
A simplified synchronous
machine showing its rotor
and stator magnetic fields.
TIle net magnetic field in this machine is the vector sum of the rotor and stator fields
B net , = BR + Bs
B net = BR+ Bs
net = kBR x Bs
But from Equation (4- 59), Bs = BDe, - BR,
so
"Tind = kBR x (BDe, - BR)
= k(BR x B"",) - k(BR x BR)
Since the cross product of any vector with
itself is zero, this reduces to
Over−Excited Under−Excited
Generator Operation, Under-and Over-Excited
POWER SYSTEM STABILITY
Introduction:
Stability of a power system is its ability to return to normal or
stable operating conditions after having been subjected to
some form of disturbance. Conversely, instability means a
condition denoting loss of synchronism or falling out of step.
Though stability of a power system is a single phenomenon,
for the purpose of analysis, it is classified as Steady State
Analysis and Transient Stability. Increase in load is a kind of
disturbance. If increase in loading takes place gradually and in
small steps and the system withstands this change and
performs satisfactorily, then the system is said to be in STADY
STATE STABILITY. Thus the study of steady state stability is
basically concerned with the determination of upper limit of
machine’s loading before losing synchronism, provided the
loading is increased gradually at a slow rate.
In practice, load change may not be gradual. Further, there may
be sudden disturbances due to
i) Sudden change of load
ii) Switching operation
iii) Loss of generation
iv) Fault Following such sudden disturbances in the power
system, rotor angular differences, rotor speeds, and power
transfer undergo fast changes whose magnitudes are
dependent upon the severity of disturbances. For a large
disturbance, changes in angular differences may be so large as
to cause the machine to fall out of step. This type of instability is
known as TRANSIENT INSTABILITY. Transient stability is a fast
phenomenon, usually occurring within one second for a
generator close to the cause of disturbance.
Short circuit is a severe type of disturbance. During a fault,
electrical powers from the nearby generators are reduced
drastically, while powers from remote generators are scarily
affected. In some cases, the system may be stable even with
sustained fault; whereas in other cases system will be stable
only if the fault is cleared with sufficient rapidity. Whether the
system is stable on the occurrence of a fault depends not only
on the system itself, but also on the type of fault, location of
fault, clearing time and the method of clearing. Transient stability
limit is almost always lower than the steady state limit and hence
it is much important. Transient stability limit depends on the type
of disturbance, location and magnitude of disturbance. Review
of mechanics Transient stability analysis involves some
mechanical properties of the machines in the system. After every
disturbance, the machines must adjust the relative angles of
their rotors to meet the condition of the power transfer involved.
The problem is mechanical as well as electrical.
Importance of Reactive Power
•Reactive power balance is achieved by adjusting voltage magnitudes.
–Too high reactive power causes overvoltage.
–Too low reactive power causes undervoltage.
•Helps to minimize voltage drops along the line and therefore the
transmission system is effectively used.
•Unlike real power production that is supplied by only generators,
reactive power production can come from several sources.
•Unlike real power, reactive power cannot be transported to a long
distance because X>>R for transmission lines.
Source and Sink of Reactive Power
Source Sink
•Synchronous generator operated
•Synchronous generator
in ‘overexcited’ mode. operated in ‘underexcited’
•Capacitor banks. mode.
•Capacitance of overhead lines and •Shunt reactors.
cables. •Inductance of overhead
•Compensating devices such as lines, cables, and
FACTS (flexible AC transmission transformers.
systems). •Inductive loads, motors.
•FACTS devices
Examples of Compensation Techniques
Series compensation
Shunt compensation
•Series capacitor
•Shunt reactor
•Use during heavy load condition to
•Use during light load condition to dampen
boost up the voltage magnitude.
the voltage magnitude.
Reactive Power and Voltage Control
•To supply electricity to field winding circuit so that the main flux
of the rotor is generated.
•The terminal voltage magnitude is controlled by the excitation
system.
•Contain several control, protection, and supervisory functions.
–Ensure physical and thermal limits are not exceeded.
–Current limiters, over-excitation protection, under-excitation
protection.
–Basically, make sure that the reactive power supply is within the
generator capability.
Different Types of Excitation Systems
•At full load, the sending end voltage is too high compared to
receiving end voltage.
•We can connect the capacitor in series to the load to help reduce the
sending end voltage in the heavy load condition.
Shunt Compensation Technique
•At no load, the receiving end voltage is higher than the usual full
load case because the sending end voltage remains constant.
•We can connect the inductor in parallel to the load to help reduce the
receiving end voltage in the light load condition.
Transformer Tap Changer Control
swing curve
•Generator-Voltage control
–Reactive power control
•Turbine-Governor control
–Real power control
•Load-Frequency control
–Bring frequency back to the nominal value.
Schematic Diagram of a Steam-Turbine Generator
Basic Generator Control Loops
Reactive Power and Voltage Control
to nominal value.
Automatic Generation Control (AGC)
Purpose of AGC
•To maintain power balance in the system.
•Make sure that operating limits are not exceeded:-
–Generators limit
–Tie-lines limit
•Make sure that system frequency is constant (not change by load).
3 Components of AGC
•Primary control “Turbine-Governor Control”
–Immediate (automatic) action to sudden change of load.
–For example, reaction to frequency change.
•Secondary control “Load-Frequency Control”
–To bring tie-line flows to scheduled.
–Corrective actions are done by operators.
•Economic dispatch
–Make sure that the scheduled of units are done in the
most economical way.
•This presentation covers only primary and secondary
control of AGC.
Basic Control Theory
•Analysis and design of a control
system requires the mathematical
modeling of the system.
–Transfer function method
–State variable method
•In this lecture, we will use
transfer function method.
•See the lecture note on basic
control and MATLAB simulink.
Basic Frequency Control Loops
Real Power Control: Block Diagram
11.2 simplified synchronous machine model - classical model used in transient stability
By transposing the line, we can reduce (or eliminate) the coupling effect between phases
from both magnetic field and electric field.