Sei sulla pagina 1di 23

Chief Engineer cum Executive Director

CPWD

Report On
MEP services
for Phase 1C

IIT Jammu
Team of Chief Engineer cum Executive Director,
CPWD for Electrical Works for Phase 1-C is as
under :
(1) Mr. M P Singh, CE cum ED, CPWD
(2) Mr. Sundar Maddali, EE cum SM (Elect.), CPWD
(3) Mr. Kuldeep Sharma, AE (E) , CPWD
(4) Mr. Saurabh Sharma, AE (E) , CPWD
(5) Mr. Yaduveer Singh, AE (E) , CPWD
The following services will be provided in Phas1C :-
1. Internal and external Electrical installations and fans
2. Vertical Transportation ( Lifts and Dumb waiter in Kitchen)
3. CCTV security surveillance system
4. LAN, WiFi and DATA networking
5. Uninterrupted power supply system (UPS)
6. Audio- Video system
7. Building management system (BMS)
8. Supervisory control and data acquisition (SCADA) system
9. Fire Fighting and sprinkler system
10. Fire detection and alarm system
11. 11/0.44 KV Electrical Sub-Stations
12. Street Lighting, Garden and Facade lighting
13. Hydro-pneumatic Water supply pumping system
14. Sewage treatment plant (STP), ETP and WTP system
15. DG set system
16. Heating ventilation and air conditioning (HVAC) system
17. Solar Water heating system
18. HVLS Fans
The following services are not in the scope of work in Phas1C :-
1. IP PBX and IP Telephone hand set
2. Solar PV generation system
1. Internal and external Electrical installations and fans

i) Copper wiring in steel conduit with modular switch/ sockets


ii) Submain, circuit and data wiring in modular PVC trunking system
in all building except residential blocks
iii) Energy efficient LED lighting
iv) Energy efficient 5 star rating AC ceiling fans
v) Light and power plugs
vi) Industrial sockets for Labs and machinery equipment
vii) Main panel at ground floor and Floor panels at each floor in all
building except hostel and residential blocks with SCADA
viii) Rising main in hostel building
ix) MCCBs, MCBs and MCB Distribution board
x) Earthing system
xi) Lightning arrestor system for multi-storey buildings
2. Vertical Transportation System( MRL Lifts and Dumb Waiter)

i) MRL Passenger and Bed lifts in all building


ii) Lifts will be compatible as per Accessible India Campaign(AIB)
iii) Automatic rescue device (ARD) in Lifts
iv) 250 Kg Capacity Dumb waiter in Dinning Block Kitchen area
3. CCTV security surveillance system

i) CCTV system will be provided in all common area (except


Washrooms), Classrooms, office areas, roads & approach
subways, and terrace as per NBC
ii) IP based cameras
iii) Recording backup will be stored on IIT’s existing server
iv) Wiring with CAT-6A
v) VMS system will be provided by IIT Jammu
4. LAN, WiFi and DATA networking

i) All Wiring with CAT-6A cable


ii) Active parts are in the scope of IIT Jammu
iii) All passive parts are in the scope of CPWD
iv) OFC layout and details will be provided by IIT however
supplying and Laying of OFC cable is in the scope of CPWD.
5. Uninterrupted power supply system (UPS)

i) For Fire alarm system, CCTV, DATA networking


ii) Audio Video system
iii) Emergency Lighting with inverter as per NBC 2016
iv) Exit illuminating signage and fire escape routes
6. Audio- Video system

Audio video system in


i) In Seminar Hall
ii) Conference Hall
iii) Interactive white board upto 40 seating capacity
iv) All Classrooms more than seating capacity of 60 student
7. Building management system (BMS)

i) Lifts
ii) Fire fighting system
iii) Fire alarm system
iv) HVAC
v) CCTV
vi) Sub-Station
vii) Water Pumping system
8. Supervisory control and data acquisition (SCADA) system

i) SCADA software system will be provided by IIT Jammu


ii) Necessary control cables is in the scope of CPWD
iii) Lifts
iv) Fire fighting system
v) Fire alarm system
vi) HVAC
vii) CCTV
viii)Sub-Station
ix) Water Pumping system
x) STP, ETP and WTP
9. Fire Fighting and sprinkler system

i) Fire fighting and sprinkler system for individual buildings as per


NBC- 2016
10. Fire detection and alarm system

i) Fire detection and alarm system for individual buildings as per


NBC- 2016
11. 11/0.44 KV Electrical Sub-Stations

i) 11/0.44 KV electrical substation as per DBR – 3 Nos of


different capacities
ii) Oil type outdoor transformer as per NBC -2016
iii) TTA HT/LT panels
iv) Space for future provision
v) HT and LT Cable
vi) APFC panel
vii) Sandwich type bus-trunking
12. Street Lighting, Facade and garden Lighting

i) Energy efficient LED street lighting


ii) Feeder pillar with astronomical time switch
iii) Bollard and garden lighting, landscape lighting
iv) 3 meter ornamental pole for compound lighting
v) Street lights on Conical single /double bracketed GI poles
along road work, day light sensor control
vi) Street Light Poles shall be suitable for CC Camera's & wifi
fixing arrangement.
vii) Facade lighting for lecture hall complex and engineering block
13. Hydro pneumatic Water supply pumping system

i) Hydro pneumatic Water supply pumping system for water


Supply
14. Sewage treatment plant (STP) DEWTAS technology & ETP

1) STP-3 of 75 KLD & ETP of 10 KLD with separate plant room


& separate inlet collection tank:- For Engineering Block-1,
Lecture Hall Complex, Work Shop
2) STP-4 of 50 KLD:- For Hostel, Dining
3) STP-5 of 50 KLD:- For Housing Type-3 & 5
4) STP-6 of 15 KLD:- For Sports Complex
15. LT DG set system

i) LT DG set for individual Substation for essential supply


ii) 100% backup for all buildings for light and power plug
iii) 2 Nos. 1000 KVA for ESS -3
iv) 1 Nos. 250 KVA for ESS-4
v) 1 Nos. 125 KVA for ESS-6
16. Heating ventilation and air conditioning (HVAC) system
AC Loads, Phase-1C, Part of this Tender

Block Name Approx AC Calculated AC


Area in SFT Load in TR
`
a) Engineering Block-1 95000 565.00
b) Lecture Hall Block 40000 265.00
c) Hostel Block 72000 365.00
d) Workshop Block 10000 065.00
e) Dining Hall Block 15000 085.00
Total 232000 1345.00

i) Demand AC Load with diversity of 45% shall be 605.00 TR and


rounded to 600.00 TR.
ii) 2x200 TR (1W+1S) + 1x400 TR (1W)
iii) Centralised Water cooled HVAC plant with screw chillers
17. Solar Water heating system

1) For Boys Hostel, 3000 Ltrs


2) For Dining Hall, 1000 Ltrs
18. HVLS Fans

1) HVLS fans of suitable sizes will be provided in


workshop area

Potrebbero piacerti anche