Sei sulla pagina 1di 16

Cadangan Projek Naiktaraf Hospital

Tawau,Tawau, Sabah (Reka & Bina)


“PLANT/RO WATER SYSTEM”
29th June 2019
ULTRAPURE REVERSE OSMOSIS WATER
SYSTEM
RAW WATER TANK

Model RB 122 H
Capacity 2000 Litre (440 gal)
Dimension 2337mm (H) X 1220mm (D)

Cover Stainless Steel (304)

Air Ventilation Stainless Steel (304)


Material
Come out with medium and
Accessory
low level sensor
MEDICAL WATER PRETREATMENT

Model MW 1865 (DPRO 10 SR) MW 1865 (DPRO 30 SR)


Dimensions 457.2 mm(D) x 1651mm(H) 457.2 mm(D) x 1651mm(H)
Manufacturer
Puregen Puregen
(filter)

Country Origin USA USA

FRP made and ABS FRP made and ABS


Material
laminated (USA) laminated (USA)
DPRO SR
Model DPRO 10 SR DPRO 30 SR
Manufacturer Puremeditech Sdn. Bhd. Puremeditech Sdn. Bhd.
Rated Capacity 4400 GPD 13200 GPD

1st Pass Permeate Out 20 LPM 40 LPM

2nd Pass Permeate Out 10 LPM 30 LPM

Membrane 4040 6 units 14 units


Heat Disinfection
Model HX 200 SR
Height: 1549 mm
Dimensions Width : 889 mm
Depth : 508 mm
Weight ±300 kg
Power 415 VAC, 50 Hz
12 kW running / 55 W
Consumption
standby
Capacity 200 Liters
R.O Water Tank
(only for DPRO 30 SR)
Model ROT 500 SR
Height: 1530 mm
Dimensions Width : 1080 mm
Depth : 705 mm
Weight ±118 kg
200-240 VAC, 50 Hz
Power

800 W running / 55 W
Consumption
standby
Capacity 500 Liters
DISTRIBUTION LOOP SYSTEM
DISTRIBUTION LOOP SYSTEM
Brand RAUTITAN HIS 311
Model PN 20
Material Cross – Linked Polyethylene (PEX)
Working pressure Max 300 psi
Rating 20, 25, 32 mm
RO Valve 316 Stainless Steel RO Valve
R. O. SYSTEM LAYOUT
(DPRO 10 SR)

0
SCHEMATIC DIAGRAM
(DPRO 10 SR)
R. O. SYSTEM LAYOUT
(DPRO 30 SR)

0
SCHEMATIC DIAGRAM
(DPRO 30 SR)
M & E REQUIREMENTS / PRE-INSTALLATIONS REQUIREMENTS
Electrical Requirement 3 - Phase , 415VAC 50Hz
Total current requirement 1 Ampere
3 Phase Isolator (32 Amp) , 4 ( 2 each
Supply outlet type & quantity required
location)
Water Supply Requirements Cold Water
Supply-in pipe size (diameter) 25 mm
Flow Rate 10LPM
Average consumption per hour 600 Litre
Pressure required 2.5 bars
Drainage Requirement (Flow rate per
5 LPM with gully trap
minute)
Floor trap in R.O Plant Room Min 100mm (2 each)
Drainage pipe size(diameter) Min 50 mm (heat resistant)
Type of discharge mineralised pipe water
Other special requirement (drainage) Drainage for reject / waste water output
Finished Room Condition Requirement
84 % R.H
(Relative Humidity)
Temperature Room Temperature
Thank You
JKR / KKM TENDER FOR
GOVERNMENT HOSPITAL / INSTITUITION
Contract
Bil Jenis Kontrak/Perkhidmatan Nama Jabatan/Agensi/Syarikat Swasta
Duration
• Reverse Osmosis Water System & RO Water
1 Hospital Shah Alam, Selangor (2013) 2 years
Storage Tank
• Ultrapure Reverse Osmosis Water System
2 • RO Water Storage Tank Hospital Raja Perempuan Zainab II, Kota Bharu, Kelantan. (2014) 2 years
• Heat Disinfection Module
• Ultrapure Reverse Osmosis Water System,
3 • RO Water Storage Tank Hospital Rembau, Negeri Sembilan (2018) 2 years
• Heat Disinfection Module
• Ultrapure Reverse Osmosis Water System,
4 • RO Water Storage Tank Hospital Seri Aman Sarawak (2018) 2 years
• Heat Disinfection Module
5 • Reverse Osmosis Water System Hospital Sultanah Nur Zahirah (HSNZ), Terengganu (2018) 1 year
• Ultrapure Reverse Osmosis Water System,
6 • RO Water Storage Tank Hospital Pengajar UiTM Puncak Alam (2019) 3 years
• Heat Disinfection Module
• Ultrapure Reverse Osmosis Water System
7 • RO Water Storage Tank Hospital Seberang Jaya, Pulau Pinang (2019) 2 System 2 years
• Heat Disinfection Module
• Ultrapure Reverse Osmosis Water System
• RO Water Storage Tank
8 Hospital IUN HKL, Kuala Lumpur (2019) 2 system 2 years
• Heat Disinfection Module

Potrebbero piacerti anche