Outline
• Introduction
• Need for Innovative Cooling Solutions
• Objective
• Scope of this Presentation
• Cooling Solutions – Air-based Cooling Systems
– Water-based Cooling Systems
– Refrigerant-based Cooling Systems
• Comparative Analysis
• Conclusion
• Vendor Contacts
3
Introduction - Power Density and Heat Load Trends
• Electrical Power = Waste Heat
• Increase in power densities from the CPU-level to the System-level
5
Objective
• Cooling of equipment in rack using airflow and impact of minor design
changes for better cooling
• Cooling of high density equipment using water-based cooling techniques
• Cooling of high density equipment using refrigeration-based cooling
techniques
• Provide vendor data for the above mentioned products
6
Scope of this Presentation
• Limited to discussion of cooling solutions only at the rack level
• Closed racks and commercially available products
• Discussion on Component-level, Board-level and Room-level cooling can
be personally consulted
7
Airflow-based Cooling Techniques
8
Cooling of Racks with Conditioned Air
• Most easy to implement and maintain
• Limitation based on cooling capacity, acoustics and power consumption
• Detailed analysis could improve efficiency of air cooling
9
Cooling of Racks with Conditioned Air
10
Sample Case Study 1
11
Sample Case Study 1 (Contd …)
Higher
temperatures
at the inlet
sides
13
Sample Case Study 1 (Contd …)
• Added blockage above the topmost unit of the rack
Top of 2U server
14
Sample Case Study 1 (Contd …)
15
Sample Case Study 1 (Contd …)
Comparison of
Inlet Temperatures
17
Sample Case Study 2 Container wall
18
Sample Case Study 2
Testing
Testing to collect
data for modeling 19
Cooling of Racks with Conditioned Air
20
Airflow Enhancers – Cabinet Powered Fans Ceiling
Front or
Footprint Inlet
26
Water-based Cooling
• Basis: QLOAD = mCp DT = rVCp DT
(Water has 3000 times higher heat carrying capacity than air)
• Chilled water from building supply
• Cooling high density servers up to 70 kilowatts per rack
• Lower energy cost as some of the CRAC units can be removed
• Avoid hotspots due to high power-density equipment
• Possible to have redundant systems (Chillers, pumps, piping, and power supply)
to avoid downtime
• Importance of CDU
• Electrically conductive, corrosiveness and high flow rates
27
Water-based Cooling
Combination of Air and Water Cooling Pure Water-based Cooling
Heat Exchanger
28
Water-based Cooling
• Cooling system design by Naissus Thermal
Management Solutions
• Heat removal of 20+ kilowatts
• Closed liquid loop with bottom mounted fin
and tube heat exchanger
•Thermal test done with 5 blade servers Heated Air
Performance Table - North American units SI units
Inputs Heat Load 24.0 kW 24.0 kW
Water Temp 12.8 degC 12.8 degC
Water Flow 0.76 l/sec 0.76 l/sec
Thermal Core
Results Cold Air Supply 22.8 degC 22.8 degC
Hot Air Disch 49.8 degC 49.8 degC
Air DT 27.0 degC 27.0 degC
Water Rise 7.1 degC 7.1 degC
Water Disch 19.9 degC 19.9 degC
Water P.D. 48.3 kPa 48.3 kPa
Background Server Fans 1680 CFM Varies by manufacturer Water from Chiller Water sent to Chiller
Fan Power 700 watts
29
Water-based Cooling
30
Water-based Cooling
•Cooling system design by Vette Corp.
•Heat removal of up to 30 kilowatts
•Rear door closed loop liquid heat exchanger
designed by IBM
•Currently available only for IBM Enterprise Rack
•Available from Rittal for retro-fit designs
Pressure drop across the heat exchanger for a typical 1U fan setup 31
Water-based Cooling
•Cooling system design by
APC.
•Heat removal of up to 70
kilowatts
•Controlled in-row cooling
•Row air containment
•Modularity
•Similar designs from HP (35
kilowatts)
•Similar concepts available
from Rittal (30 kilowatts)
•Similar concepts available
from Liebert (8 kilowatts
and 17 kilowatts)
Heat Exchanger and Front View Rear View
Fan Assembly 32
Images: www.apc.com
Refrigerant-based Cooling Techniques
33
Refrigerant-based Cooling
34
Refrigerant-based Cooling
•Cooling system design by Liebert
•XDF- Cooling capacity of 14 kilowatts
•Stand-alone unit
35
Refrigerant-based Cooling
•Cooling system design by APC.
•Heat removal of up to 43 kilowatts
•Modularity
•Rack air containment
Liebert Roof Mount Cooling Liebert In-Row Cooling Rittal Rear Door Hx
Images: www.liebert.com 37
Liquid Based Touch Cooling
38
Water/Refrigerant-based Touch Cooling
Available from:
Clustered Systems
Rittal (Power electronics)
SprayCool (20 to 30KW)
Spray Cooling
Images: www.spraycool.com
39
Refrigerant-based Touch Cooling
•Cooling system design by Thermal
Form and Function
•Pumped liquid multiphase cooling
•Heat removal of up to 10 kilowatts
per evaporator (Modular)
•Designed for retro-fit applications
•Air/Water cooled condenser unit can
be used
Images: http://www.thermalformandfunction.com/
41
Comparative Analysis
43
Vendor Contacts
44
References
• Product websites and communication with vendors
• Hannemann, R and Chu, H., (2007), “Analysis of Alternative Data Center
Cooling Approaches”, ASME Interpack 1176, Vancouver, BC.