Electrical service cabinet will normally be mounted in a wall facing a street, and
as close as possible to the LV main which will supply it. Qatar General Electricity And
Water Corporation (KAHRAMAA) therefore reserves the right to determine the location
of the electrical service cabinet. (See also Annexures 7, 8, and 9 for additional details)
The minimum fault level for any supply position connected by means of a
KAHRAMAA cut out shall be 12KA for a duration of 3 seconds.
The method of KAHRAMAA service connection for
customer load of up to 400A capacity (for residential) and
630A capacity (for commercial or industrial) is through a
Sub-Main Board (SMB) ,and via a KAHRAMAA cut out,
located inside the customer premises.
Where switch boxes contain more than one phase for group
switching, approved barrier switch boxes may be used. The unit must
be labeled to indicate that 415V exists at the box.
Each motor starter for all three phase motor shall incorporate a phase
failure device which will automatically disconnect the supply from the motor.
This device must be manually reset.
All water pump motor installed remotely from the controlling device
shall be provided with an additional means of isolation immediately adjacent
to the motor. Where the controlling device and / or the means of isolation is
installed outside the building, it shall be of a weather proof design. Water
pumps for any installation shall be located at a minimum distance of 2 meters
from any water tank.
3.12 Electric Motors,
Circuits And Controllers
The method of starting motors shall restrict the current to limits
laid down by the Qatar General Electricity And Water Corporation
(KAHRAMAA). All motors over 1 HP shall be provided with means of
automatic disconnection from the supply in the event of excess current flow
or drop in voltage of over 15%. The limits laid down are as set out below:
Motors that fall within category (1) may be connected for direct on
line starting with over current protection.
Motors that fall within category (2) shall not in any circumstances
be connected for direct on line starting but shall be arranged for reduced
voltage starting e.g. open or closed transition Star / Delta Starting, Auto-
transformer starting, or other approved arrangement.