Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Objectives:
What is a control valve? What is a centrifugal
What is an actuator? pump?
What is a positioner? What is pump head?
What is Cv? Why do we use pump head
and not psi?
What are valve characteristics?
What is a pump curve?
What is valve deadband?
What is a system curve?
What is stiction?
What is the system
What are the types of valves operating point?
What is a positive
displacement pump?
How does a PD pump differ
from a centrifugal pump?
sg
CV Q
P
Where :Q Fluid Flow in GPM
sg Specific Gravity of the Fluid
P Pressure Drop in PSI
0 0
20 20 1.0
40 40 1.0
60 60 1.0
80 80 1.0
100 100 1.0
0 0 0
20 6.25 0.3125
40 12.5 0.3125
60 25 0.417
80 50 0.625
100 100 1.0
Method B
Method B may be used when you do not want to step the
controller through such a wide range of values.
Step the controller in one direction such that you know all
deadband will be removed and wait.
Step the controller in the opposite direction by a small
amount (0.5%) and wait.
Step the controller again in the same direction by the same
amount (0.5%) and wait.
Repeat step 3 until the process variable shows a response
to the controller step.
The amount of deadband is the change in controller output
from step 1 to step 4.
Step the controller in one direction such that you know all
stiction/deadband will be removed and wait for the process
to stabilize.
Step the controller in the same direction by a small amount
(0.2%) and wait.
Step the controller again in the same direction by the same
amount (0.2%) and wait.
Repeat step 3 until the process variable shows a response
to the controller step.
The amount of stiction is the change in controller output
from step 1 to step 4.
Smart Transmitters
Check the configuration. Make sure the variable
being transmitted is the one you want.
Check the calibration, do the units and range match
the controller’s units and range configuration for the
process variable.
Check the filtering. Is an excessive dampening time
(time constant) specified.
Others?
Temperature Sensors
Check the calibration, does the thermocouple type or
RTD curve match the configuration of the controller.
Check the installation, is the thermowell or sensing
element sufficiently immersed in the medium. Is the
thermocouple or RTD properly fitted for the
thermowell. Is the temperature sensor in the right
place. Is there buildup on the thermowell.
Others?
Pressure Sensors
Check for plugged lines to the sensor.
Others?
Flow Sensors
Verify that the mounting conforms with the sensor
manufacturer's recommendations, straight runs of
piping, environment, etc.
Others?
What's changed?
Ask the operator what is different today.
Understand the Process.
Is the process is non-linear?
A change in process conditions may require different
tuning.
Set output limits to avoid windup or operation in
low gain regions of your final control element.
Others?