Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
“ FR E E G OV E R N O R M O D E O PE R AT IO N ”
ORDERS
IEGC 1.6 IEGC 6.2 (e) & 6.2(f) IEGC 6.2 (g)
KERALA LETTER
ON FGM
WHY DOES FREQUENCY DROP ?
Sudden addition of load causes a drop in frequency.
An increased load is supplied through an increase in the load angle by which
the rotor lags the stator field.
It means a loss of Kinetic Energy of the rotating M/c and a
slower speed of rotation i.e. a lower frequency.
f = (P/2) X (N/60)
Where f = frequency of the system
P = no of poles of the M/c.
N = rpm of the M/c
PRIMARY CONTROLS
600
500
400
GENERATION IN MW --->
300
100MW for 0.5HZ
Frequency
200
100
40MW for 0.5HZ
Frequency
0
49 49.5 50 50.5 51 51.5
FREQ IN HZ --->
RESPONSE BY A 500 MW GENERATOR WITH DIFFRENT DROOP
500
500
500
450
400
400 375
350 4 % DROOP
300
300
MW ->
250
250
5 % DROOP
200
200
150
125
100
100
50
0 0
Example:-
200MW
22000MW Generation Lost
World wide
Self healing
mandatory
mechanism
practice
Makes
Collectively
restoration
Control
easy
Southern Region }
}
Eastern Region }
}
Northern Region } The date for the
} implementation of the
Western Region } Commercial mechanism
} mentioned in Section 7.1(d)
(ii) All thermal and reservoir based hydro } for the respective region.
generating units of installed capacity }
10 MW and above in North Eastern Region }
(iii) All other generating units - three months after the above dates for the respective
regions except in the case of Nuclear Power Stations which shall be exempted till the next
review of the IEGC.
Any exemption from the above may be granted only by CERC for which the
concerned constituent shall file a petition in advance.
UNQUOTE
CERC ORDER ON ‘IEGC’ DATED 22.02.2002
6.2(e) All generating units, which are synchronised with the grid, irrespective of
their ownership, type and size, shall have their governors in normal operation at all
times. If any generating unit of over fifty (50) MW size (10 MW for North Eastern
RLDC shall be immediately advised about the reason and duration of such
6.2(f) Facilities available with/in load limiters, Automatic Turbine Run up System
(ATRS), Turbine supervisory control, coordinated control system, etc. shall not be
used to suppress the normal governor action in any manner. No dead bands and/or
6.2(g) All Generating Units, operating at/up to 100% of their Maximum Continuous
Rating (MCR) shall normally be capable of (and shall not in any way be prevented from)
instantaneously picking up five per cent (5%) extra load for at least five (5) minutes or
within technical limits prescribed by the manufacturer when frequency falls due to a
system contingency. The generating units operating at above 100% of their MCR shall
be capable of (and shall not be prevented from) going at least up to 105% of their MCR
when frequency falls suddenly. Any generating unit of over fifty (50) MW size (10 MW for
NER) not complying with the above requirement, shall be kept in operation
(synchronised with the Regional grid) only after obtaining the permission of RLDC.
However, the constituent can make up the corresponding short fall in spinning reserve
by maintaining an extra spinning reserve on the other generating units of the constituent.
CERC ORDER ON ‘IEGC’ DATED 22.02.2002
6.2(h) The recommended rate for changing the governor setting, i.e. supplementary
control for increasing or decreasing the output (generation level) for all generating .units,
irrespective of their type and size, would be one (1.0) per cent per minute or as per
manufacturer's limits. However, if frequency falls below 49.5 Hz, all partly loaded
generating units shall pick up additional load at a faster rate, according to their capability.
FREE GOVERNOR MODE OF
OPERATION
CERC Order ON ‘IEGC’ dated 21.12.1999
Quote
6.2 (c) All generating units, which are synchronised with the
grid, irrespective of their ownership, type and size, shall have
their governors in normal operation at all times. If any
generating unit of over fifty (50) MW size (10 MW for North
Eastern Region) is required to be operated without its governor
in normal operation, the RLDC shall be immediately advised
about the reason and duration of such operation. All governors
shall have a droop of between 3% and 6%.
Unquote
SRLDC Requested all constituents including ISGS vide letter
dated 3rd Jan 03 to take a lead in this matter.
FREE GOVERNOR MODE OF
OPERATION
• The matter discussed in 368th OCC meeting
• All SR constituents/ISGS agreed to convey their readiness by 21.01.2003
• SRLDC again requested all constituents vide letter dt.21.01.03 to intimate unit/station wise status/ programme
• Matter discussed in 109th TCC/131st SREB meeting.
• ISGS/SR constituents agreed for FGM by 1st May 2003.
• Discussed in 369th, 370th, 371st & 372nd OCC meetings.
• KSEB & TNEB furnished unit wise/ station wise program/ constraint/ preparedness
• APTRANSCO conveyed readiness for FGM of all generators except thermal units of APGENCO
• Freq response characteristics calculation details covering 3 events furnished for examination & necessary
feedback by the constituents.
• Constituents Actual response Shortfall
(AVG) (AVG)
AP 2% 98 %
KAR 17 % 83 %
KER 29 % 71 %
TN 13 % 87 %