1 >P220 ARU–
MiCOM P12x Range
A range of overcurrent relays for:
2 >P220 ARU–
MiCOM P12x Range
A whole range for a global answer
3 >P220 ARU–
Functions ANSI MiCOM MiCOM MiCOM MiCOM
Code P120 P121 P122 P123
Single-phase overcurrent 50/51 or X
50N/51N
4 >P220 ARU–
Functions ANSI MiCOM MiCOM MiCOM MiCOM
Code P120 P121 P122 P123
CB control Local / Remote X
Circuit Breaker monitoring and X X
control
Blocking logic X X X X
Selective relay scheme logic X X
Multi-shot autoreclose 79 X
Clock phase and anti-clock Phase X X
rotation operation
Measurements (True RMS) X X X X
Peak and rolling values X X
Event records X X
Instantaneous records X X
Fault records X X
Disturbance records X X
RS 232 front communication for X X
MiCOM S1 Software
RS 485 rear communication (Modbus X X X X
RTU, IEC 60870-5-103, Courier,
DNP3.0)
5 >P220 ARU–
MiCOM P12x Range
Housing
78
97 11.6
24.6 52
All dimensions
in mm. Panel cut-out
168 158 Flush mounting
fixing details
4 holes O
/ 3.4 99 4 holes O
/ 4.4 (M4 screw)
103 25.1 226
MiCOM P121
IA = 214.50 A
Trip
Alarme C
Equip. fail
Auxiliary
supply 177 151.2 max.
AUX. 1
AUX. 2
AUX. 3
AUX. 4
AREVA
Flush mounting
6 >P220 ARU–
Rear face MiCOM
P120, P121, P122 & P123
Earth
Housing
+ 1 M4 screw
by connection
point
7 >P220 ARU–
User Interface MiCOM
P120, P121, P122 & P123
Trip Led
Alarm Led Retractable flaps
Equipment failure Led to withdraw
Auxiliary supply Led the active part
Programmable Leds
5 tactile buttons
keypad for setting
and consulting
Battery
(P122 & P123) RS 232
8 >P220 ARU–
DEFAULT DISPLAY
IL1 = 1245 A
Relay 4321
Status 1011
9 >P220 ARU–
DEFAULT DISPLAY
IL1 = 1245 A
[50/51] Phase OC Trip Commands Latch Functions Blocking Logic Output Relays Inputs 1/2
Idmt
IEC SI
Tms
0.025
I>> ?
Yes
I>>
2.0 In
I>>> ?
Yes
10 >P220 ARU–
MiCOM P12x Range
Communication
11 >P220 ARU–
MiCOM P12x Range
Communication
12 >P220 ARU–
MiCOM P12x Range
RS 232 Front Communication Port
13 >P220 ARU–
MiCOM P12x Range
MiCOM S1 Software
Data extraction
Settings
Measurements
Events records (75 events)
Faults records (Last 5 faults)
Disturbance records (5 records)
14 >P220 ARU–
MiCOM P121 Thresholds
Phase Overcurrent
15 >P220 ARU–
MiCOM P121 Thresholds
Earth Fault
16 >P220 ARU–
Thresholds
Ith
Time
I>
tI>
I>>
tI>>
I<
I>>> tI>>>
Current
17 >P220 ARU–
Thresholds
Ie>
Time
Ie>>
tIe>>
Ie>>> tIe>>>
Current
18 >P220 ARU–
EARTH AND PHASE CURRENT OVERCURRENT FUNCTIONS
19 >P220 ARU–
EARTH AND PHASE CURRENT OVERCURRENT FUNCTIONS
INVERSE TIME CURVES
The first and second stage overcurrent threshold can be selected
with a dependent time characteristic.
t = Tripping time
K = Coefficient
I = Value of measured current
IS = Value of the programmed threshold (Pick-up value)
α = Coefficient
L = ANSI/IEEE coefficient (zero for IEC curves)
T = Time multiplier between 0.025 and 1.5
20 >P220 ARU–
EARTH AND PHASE CURRENT OVERCURRENT FUNCTIONS
21 >P220 ARU–
Measurements (P122 & P123)
22 >P220 ARU–
Measurements (P122 & P123)
Peak and Average Values Meas. on a Time Window
The peak and average values by phase are calculated on a time RECORDS
window settable from 5mn to 60mn
TIME PEAK VALUE
The display is presented in the Measurement menu at the end
TIME WINDOW =
of the time window 5 mn
23 >P220 ARU–
Measurements (P122 & P123)
Rolling and Peak Value Demands
24 >P220 ARU–
Fault Records
(P122 & P123)
25 >P220 ARU–
Fault Records (P122 & P123)
Last 5 Faults
Time (13:07:15:53)
Date (09/08/01)
Fault magnitude
26 >P220 ARU–
Event Records
(P122 & P123)
27 >P220 ARU–
Event Records
(P122 & P123)
1 ms time stamped
28 >P220 ARU–
Event Records
(P122 & P123)
29 >P220 ARU–
Disturbance Records
(P122 & P123)
5 disturbance records
Sampling 1600 Hz (at 50 Hz)
30 >P220 ARU–
Wiring & Connections
31 >P220 ARU–
2 Setting Groups (P122 & P123)
2 Identical Protection Setting Groups