SURFACE EQUIPMENT
XPERT ESP
SURFACE COMPONENTS
- Transformer
- Switch Board
- Junction box
- Well Head or tubing head
SURFACE EQUIPMENT XPERT ESP
Transformer
• Provides required voltage for down hole motor
• Works by transforming the voltage through induction magnetic field
Transformer
The transformer sends the correct
voltage to the Switchboard for designed
surface voltage for the proper motor
operation.
Transformer
Normally when using single phase transformers
for three phase power, three individual
transformers are connected together, in various
configurations.
CORE
WINDING
SURFACE EQUIPMENT XPERT ESP
103
• TRANSFORMER
• Switch Board
- Control panel for electric motor
Reda Switchboard
• Ratings
Switchboard
• Ratings:
– Maximum Voltage
– Maximum Amp Load
– Maximum KVA
SURFACE EQUIPMENT XPERT ESP
Switchboard
Selecting a Switchboard
• Switch Boards
SWITCH BOARD
• 3 MAIN FUNCTIONS
- Motor starter unit
- Protective equipment for overload and under load problems
- Recording Instruments
Potential Transformers
The 120 volts is used to run all the control circuits in the Switchboard.
Motor controllers will monitor the control voltage; and using the P.T.
ratio calculate the line voltage in the switchboard.
SURFACE EQUIPMENT XPERT ESP
Potential Transformers
Current Transformers
Current Transformers
A conductor passes through the winding of the CT and
energizes the CT. Typically the CT ranges used in the
SPS controllers have a ratio of 200:5, 300:5, 150:5,
75:5 etc.
Primary side
Secondary side
SURFACE EQUIPMENT XPERT ESP
Current Transformers
As an example, if 180A is flowing through the conductor, and
the TR is 200:5, the amperage on the secondary side of the
CT will be:
180 or
Sec. Amps = = 4.5 A 180A
(200:5)
180
Sec. Amps = x 5 = 4.5 A
200
4.5 A
SURFACE EQUIPMENT XPERT ESP
Current Transformers
5 Amps
0
SURFACE EQUIPMENT XPERT ESP
Current Transformers
If one pass of the wire results is greater than 5A, the CT ratio must
be increased by going to a CT with a higher turns ratio.
Current Transformers
FUNCTION:
• Ventilation for gas that possibly
comes up to surface through the
JUNCTION BOX cable
• Connection terminals, easier to
reverse motor rotation and to take
initial readings.
SURFACE EQUIPMENT XPERT ESP
Wellhead
The Wellhead is the equipment
that is installed at the surface of
the well bore.
SURFACE
POWER PLUG
TUBING HANGER
PENETRATOR
O RING
WELL HEAD
CONNECTOR
ASSEMBLY
ATTACHABLE
CONNETOR
(ASSEMBLY) PRODUCTION TUBING
STRAPPED
CABLE BAND
PAU/ IWS-
XPERT
XpertESP
ESP/ IWS
2002
POWER CABLE
FROM JBOX
SURFACE EQUIPMENT
GLAND NUT
WELL HEAD
PACK OFF
ASSEMBLY
O RING