Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Gaëtan Michielsen
21 October 2008
In Chilled Water System
Design ...
Albert Einstein
4) Wrap-up
• True either at
full and partial load
• Basic formulas
• Mixing
• Pipe Sizing
• Balancing
• Pumps: Parallel / Serial
• Reduction of capacity
– reduction of temperature DT . constant volume application
• Pump laws
l/s pump proportional to rpm
kPapump proportional to rpm²
kW pump proportional to rpm³
12°C 14°C
Example:
• Basic formulas
• Mixing
• Pipe Sizing
• Balancing
• Pumps: Parallel / Serial
L rV
2
Dp f * *
D 2
Dp = energy loss through friction
f = friction factor
L = pipe length
D = pipe diameter
V = fluid velocity
r = fluid density
• Basic formulas
• Mixing
• Pipe Sizing
• Balancing
• Pumps: Parallel / Serial
• Basic formulas
• Mixing
• Pipe Sizing
• Balancing
• Pumps: Selection / Parallel / Serial
Pressure
Operating
point
P2
F2 F1
Water flow
(2)
system
flat
‹#› Note
Hydraulics the relationship
& Chiller Sequencing between pressure and flow change
1) Hydraulic Fundamentals
Pump Selection
• Determine the load
• Determine the temperature drop
• Determine the total flow
• Find the pressure on the most resistant circuit path
• Determine the pump type
Based on the just determined data:
• Select a pump family by the manufacturer's curves
• Select the pump by the individual pump performance curve
chart
H
• total pressure will not
change
• forwarded amount of liquid is
summarized
HA
HB
Q1 Q2 Q
The head pressures has to be balanced to avoid
‹#›the pumps
Hydraulics toSequencing
& Chiller work "against" each other !!!!!!!!!!!
1) Hydraulic Fundamentals
Pump Serial Operation
H
• forwarded amount of liquid is 2HB
not changed
• total pressure will be
summarized 2HA
HB
HA
QB QA Flow
H1
Q1 Q2 Flow
Flow
Variable speed
over 30% of range
100%
If you have two pumps in parallel, and only
one variable, you will not be able to control the
The control of the flow cannot be
flow correctly and therefore you won’t make the
optimal. The variable pump needs
energy @100%
Pump1 savings your are supposed to doto with at least 70% before the
reach
50%
a variable flow solution. flow increases.
Pump2 @70%
Time
Pump
3-way
valves
Supply temp
(Besleme Sıcaklığı)
Constant Pump
Return temp
(Dönüş Sıcaklığı)
3-way
valves Change chiller set point
to control the load
(Yükü kontrol etmek için,chiller
ayar noktasını değiştirin)
CHILLER #2
LOAD
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 FLOW
CW RETURN SWITCH CW SUPPLY
TS1 (Akış Anahtarı)
T° T°
FLOW
TS2 SWITCH
CHILLER #2
LOAD
Minimum accessories needed
for a hydraulic system.
(hidrolik sistem için gerekli minimum aksesuarlar)
100%
ON
FULL LOAD (100%)
Load fluctuation CHILLER #2
(Yük Dalgalanması)
LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80%
ON
Load fluctuation LOAD 80%
CHILLER #2
LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80 11 80 7 80 7 7
60%
ON
Load fluctuation LOAD 60%
CHILLER #2
LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80 11 80 7 80 7 7
60 10 60 7 60 7 7
50%
CHILLER #2
ON
Load fluctuation LOAD 50%
LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80 11 80 7 80 7 7
60 10 60 7 60 7 7
50 9,5 50 7 50 7 7
40%
ON
LOAD 40%
Load fluctuation CHILLER #2
LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80 11 80 7 80 7 7
60 10 60 7 60 7 7
50 9,5 50 7 50 7 7
40 9 40 7 40 7 7
40%
ON
LOAD 40%
CHILLER #2
LOAD
Less than 50% load ….
(Yük 50% ‘den daha az….)
40%
ON
LOAD 40%
CHILLER #2
LOAD
What happens to chilled water supply
temperature ?
(Soğutulmuş besleme suyu sıcaklığına ne olur ?)
OFF
ON
9°c
7°c
TS2
ON
LOAD 40%
CHILLER #2
LOAD
Supply temperature higher means ….
(Besleme sıcaklığının yüksek olması demek ….)
Inability to satisfy load (Yükü
karşılayamamaktır)
(designed for 7°c)
OFF
ON
9°c
5°c
TS2
80%
ON
LOAD 40%
CHILLER #2
LOAD
How can we keep our designed
Supply temperature at 7°c ?
(Dizayn besleme sıcaklığımızı 7 °C de nasıl tutarız ?)
Change chiller #2 setpoint down to 5°c
(2 No’lu Chillerin ayar noktasını 5°c’ye düşürmek)
pressure
5°c F E D
CW RETURN TS2
T° expansion
device compressor
ON
A B
CHILLER #2
enthalpy
3-way
valves
Constant
Flow
Pumps
Supply
Temp
Return Temp
3-way
valves
TS2
CHILLER #2
CW RETURN
T°
LOAD
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)
CHILLER #1
TS1 CW SUPPLY
T°
M
OFF OFF
ON
TS2
M
ON ON
CHILLER #2
CW RETURN
T°
LOAD
What happens at partial load if we
switch OFF one chiller with his pump?
(Bir soğutucuyu pompasıyla birlikte kapattığımızda
kısmi yüke ne olur?)
PRODUCTION
LOAD
System is balanced for nominal flow
(Sistem nominal akış için dengelenmiştir)
By-pass : 10 l/s
50 l/s
50 l/s 30 l/s
Ground Floor
PRODUCTION
LOAD 100 l/s
By-pass : 20 l/s
System is balanced
Nominal flow = 100 l/s 100 l/s
By-pass : ?
? l/s Q1 Q2 Q
50 l/s 10 l/s
Ground Floor
PRODUCTION
LOAD
½ CAPACITY
60 l/s
By-pass : 40 l/s
The chiller and its dedicated pump are switched on and off according
to the estimated cooling load and the outside weather conditions
In this system we get sequenced flow as per the number of chillers
running at the same time
Characteristics:
- 3-way valves
- Pump per chiller
- Typical design for small Building process
- Control based on the variation of the flow
(1 pump/chiller set or both)
Larger Loads
Larger Installations
For larger installations,
pressure drop in the distribution circuits is higher as
• More piping length, curves, balancing valves, accessories
• More terminal units
• Larger terminal units (more water to handle, larger flow)
Supply
Temp
Return Temp
3 ways valves
Pump
Supply Temp Constant flow
Return Temp
3 ways valves
No flow
100 l/s at 6°C
50 l/s at 12°C
three-way valve
50 l/s at 12°C
50 l/s at 11,5°C
100 l/s at 8,5°C
50 l/s at 11,5°C
three-way valve
50 l/s at 11,5°C
production
pumps
pump
production
loop
distribution
loop
two-way valves
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Decoupled Variable Secondary Flow
The chiller set points are constant, system control is achieved through
the variable speed pump
Constant
production
pumps Variable
pump
Supply
Temp
production
Return Temp
loop
50 l/s
PRODUCTION FLOW
CHILLER #2 EQUALS
DISTRIBUTION FLOW
50 l/s (ÜRETİM AKIŞI=DAĞITIM AKIŞI)
Variable
speed drive
ΔP
LOAD
head pressure
ΔP
Variable
speed drive
pressure
difference 0 percent flow 100
Excess Flow
Variable
speed drive
(Değişken hız ΔP
sürücüsü)
50 l/s
Excess by-pass flow > 110%
of one chiller flow
ON ,(Aşırı baypas akışı bir chillerin akışından 110% fazladır
ON
PRODUCTION PRODUCTION
15 l/s 20 l/s
LOAD LOAD
DISTRIBUTION BY-PASS = 65 l/s DISTRIBUTION
Excess Flow
Variable
speed drive
ΔP
0 l/s
Production flow is 50 l/s against
35 l/s needed
OFF
ON (Üretim akışı 35 l/s ihtiyaç olmasına karşın 50 l/s)
CHILLER #2
By-pass flow is 15 l/s in excess
direction
50 l/s (Aşırı yönde bypass akışı 15 l / sn'dir.)
ON
PRODUCTION PRODUCTION
15 l/s 20 l/s
LOAD LOAD
DISTRIBUTION BY-PASS = 15 l/s DISTRIBUTION
Excess Flow
Variable
speed drive ΔP
Deficit Flow
Variable
speed drive
ΔP
DISTRIBUTION DISTRIBUTION
Deficit Flow
CW SUPPLY
T°
DISTRIBUTION
Load is increasing
Distribution Flow is increasing
We have a deficit flow in the by-pass
The temperature sensor to see effect of Deficit Flow will be placed
DISTRIBUTION DISTRIBUTION
Excess Flow
DISTRIBUTION
Load is decreasing
Distribution Flow is decreasing
We have an Excess flow in the by-pass
The temperature sensor to see effect of Excess Flow will be placed
• Summary
– Can generate more capacity than parallel chillers
At a better EER
– Allows to preferentially load a chiller
Heat Recovery Unit
– Allows for large water temperature rise/drop
Reduced water flow Reduced pump input
Flow
S UPP LY
Meter Production
DE MAND Air Handling Units
Bypass Line
Distribution
Control Valves
15 L/s at 13.0°C
5 L/s at 7.0°C
5 L/s at 25.0°C
Industrial Process
(375 kW)
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Out of Range Applications
• Flow out of Range
chiller 15 L/s at 7.0°C
15 L/s at 13.0°C
5 L/s at 7.0°C
5 L/s at 25.0°C
Industrial Process
(375 kW)
15 L/s at 13.0°C
5 L/s at 20.0°C
5 L/s at 38.0°C
Industrial Process
(375 kW)
5 L/s at 20.0°C
2.9 L/s at 38.0°C
5 L/s at 38.0°C
Industrial Process
(375 kW)
• Loop time is the time required for chilled water to make one round trip in
the distribution system.
• Depending on the type of chiller control the required loop time can vary
between 1..3..5 minutes.
• Therefore:
Min. Water [l] = Cooling capacity [kW] * 7,2 [l/kW]
For example: a chiller has 250kW cooling capacity,at 6°/12°C
the flow is roughly 10 l/s = 600 l/min = 0.6 m3/min
with 3 minutes loop time the ideal water content minimum is around 1.8 m3
LOAD
LOAD
M
TANK
Temperature [°C] 30 40 50 60 70 80 90
Expansion [%] 0.4 0.75 1.17 1.67 2.24 2.86 3.55
• Open-tank
tank open to atmosphere
•A diaphragm tank
flexible membrane
Diaphragm tank
Connector
– flexible membrane
Polypropylene liner
Reservoir
Butyl diaphragm
Nitrogen cushion
Hydraulic function:
• System pressure reference point
pump chiller
cooling heat-transfer
coil fluid
ice storage
tanks
load
pump
VFD
water-cooled chiller
chiller pump
cooling
coil
off-peak
chiller
off-peak load ice chiller
pump pump chiller pump
VFD VFD
heat
exchanger
cooling
coil
ice
load valve
pump
chiller
pumps
VFD
75
cooling load, % of design
50
Building Cooling Load Profile
25
0
midnight 6 a.m. noon 6 p.m. midnight
75
cooling load, % of design
50
0
midnight 6 a.m. noon 6 p.m. midnight
75
cooling load, % of design
50
make melt
ice ice
25
0
midnight 6 a.m. noon 6 p.m. midnight
75
On-Peak Cooling with Chiller and Ice
cooling load, % of design
melt
ice
50
make
ice
25
chiller
0
midnight 6 a.m. noon 6 p.m. midnight
75
melt melt
ice ice
50
make make
25 ice ice
chiller chiller
0
midnight 6 a.m. noon 6 p.m. midnight midnight 6 a.m. noon 6 p.m. midnight
75
chiller
capacity
50
chiller
make chiller
25 ice
0
midnight 6 a.m. noon 6 p.m. midnight midnight 6 a.m. noon 6 p.m. midnight
Condenser water
system
cooling tower
condenser
sprays
louvers
outdoor fill
air
sump
to from
condenser cold water hot water condenser
Dry Cooler
• A dry cooler is a forced convection air-cooled fluid
cooler.
• Air is forced over a finned coil which contains the
working fluid such as water or water & glycol mix.
Dry Cooler
PROs CONs
• Cost similar to evaporative cooling • Higher leaving water temperature
tower
• High electrical consumption due to the
• No water consumption numerous fans
• No sanitary risk of Legionnaires’ • High noise level because of higher
disease airflow rate
• No need of chemical water treatment • Necessity to add glycol to water to
avoid freezing of installation
• No plume
• Important ground surface
• Easy maintenance, even if finned coils
must be regularly cleaned to keep
efficiency
n + 1 scenario:
• One chiller running
• One chiller stand by
• Free cooling off
• Four dry coolers running
• One dry cooler stand by
• Chiller has the best COP
• No extra pressure drops are created
Save pump energy
• Chillers off
• Free cooling on
• Five dry coolers are running.
When very low ambient temperatures,
the dry coolers also go into part load.
• Chiller Sequencing
• Load / Unload
• Rotations
• Failure Recovery
• Tower Optimisation
Chiller Plant
Automation
System Cooling
Loads
Remember:
Without controls, it’s not a system.
• Load determination
– When to add or subtract a chiller?
• Capacity matching
– Number of running chillers required?
• Rotation
CHILLER
– Which SEQUENCING
chiller leads?
• ChillerWhich
setpointchiller to turn on or off?
control
– What is the setpoint strategy?
• Failure recovery
– What happens after a chiller failure?
• Operator interface
– How to communicate with the operator?
Load Chiller
Determination Sequencing
6.5°
Add delay
time (10 mn)
Chilled water supply temp System supply
set point
Parameters
Chiller is
Subtract timer starts
subtracted
Design delta temp 3°
Subtract delay
time (20 minutes)
Parameters
70 l/s
60 l/s
By-pass Pipe
flow ???????
Subtract delay
time (20 mn)
Parameters
• Purpose:
– Reduce operating cost by turning on and off the appropriate
chillers when needed
• Dependent on chiller types and sizes available
• Linked to the chillers rotation priority sequence!
60% 1560
40% 1040
20% 520
kW
0%
Chiller Stages
43% 3200
38% 2800
21% 1600
kW
0%
Chiller Stages (7400 kW Load)
UCP2 UCP2
UCP2
200 Ton Chiller 500 Ton Chiller (Normal500 Ton Chiller (Normal
(Swing) - 1) - 2)
• Chiller Sequencing
• Load / Unload / Soft Start
• Rotations
• Failure Recovery
• Tower Optimisation
Unload at start
Chiller plant
transitions from 10° Soft start dead band
soft start mode to
normal mode
7.5°
System supply
1.5° Add temp dead band set point
6°
Chiller plant
Soft Loading prevents a peak
transitions from in electric
10° Soft start dead band
consumption that would happen if
soft start mode
to normal mode
all chillers were started at the same time 7,5°
System supply
1,5° Add temp dead band set point
6°
12°C
2°C
10°C
• Chiller Sequencing
• Load / Unload / Soft Start
• Rotations
• Failure Recovery
• Tower Optimisation
• Chiller Sequencing
• Load / Unload / Soft Start
• Rotations
• Failure Recovery
• Tower Optimisation
• Chiller Sequencing
• Load / Unload / Soft Start
• Rotations
• Failure Recovery
• Tower Optimisation
Power (% of KW)
80 23°C
19°C
60
40
20
0
0 20 40 60 80 100
Load (%of kW)
80 kW 300 kW
15°C WB
40 kW
Flow
Free movement of the paddle
pressure
efficiency
rpm
volume
Operating
System curve
point
Pressure
• What if the desired P1
operation point is
between two curves?
• Go below! Go to left! P2
– Lower first cost
– Lower operating cost
– Avoid over pumping
Q2 Q1 Water flow
The whole team is entirely at you disposal for further questions and remarks.
We hope that TRANE is a trusted partner for you, now and in the future.