Sei sulla pagina 1di 202

Technical Seminar

Hydraulics & Chiller Sequencing

Gaëtan Michielsen

21 October 2008
In Chilled Water System
Design ...

“Everything should be made


as simple as possible, but
no simpler.”

Albert Einstein

‹#› Hydraulics & Chiller Sequencing


Today's Agenda
Hydraulics & Chiller Sequencing
1) Hydraulic Fundamentals
– Basic formulas
– Mixing
– Pipe Sizing
– Balancing
– Pumps: Parallel / Serial

2) Different Hydraulic Arrangements


– Non Decoupled Constant flow
– Non Decoupled Variable flow
– Decoupled Constant Flow
– Decoupled Variable Flow
– Decoupling line sizing
– Chillers in Series
– Variable Primary Flow
– Water Content / Buffer tanks / Expansion tanks
– Ice Storage
– Cooling Towers

3) Chiller Plant Management


– Chiller Sequencing
– Load / Unload
– Rotations
– Failure recovery
– Tower Optimisation

4) Wrap-up

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals

 Water has nearly infinite compressive strength.


 Water has almost no tensile strength.
 Water always flows from a point of higher pressure to
a point of lower pressure.
 All water flowing into a “T” must flow out of it.
 Water does not flow simultaneously in two opposite
directions in the same pipe.
 Water does not flow through closed valves.
 Water cannot read the arrows painted on pipes.

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Basic Concepts

• To achieve the desired conditioning:


load and the source has to be equal

• Better the balance


Better the quality

• True either at
full and partial load

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals

• Basic formulas
• Mixing
• Pipe Sizing
• Balancing
• Pumps: Parallel / Serial

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Basic Formulas
• Capacity
kW capacity = 4.186 * l/s * K
1000 kW = 4.186 * 47.8 l/s * 5 K

• Reduction of capacity
– reduction of temperature DT .  constant volume application

– reduction of flow  variable volume application

– change of both  as in a terminal device

500 kW = 4.186 * 47.8 l/s * 2.5 K


500 kW = 4.186 * 23.9 l/s * 5 K
500 kW = 4.186 * 17.1 l/s * 7 K

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Basic Formulas
• Pump
kW pump = l/s * kPa .
eff pump * eff motor * 1000

12.5 kW = 47.8 l/s * 200 kPa .


85% eff pump * 90% eff motor * 1000

• Pump laws
l/s pump proportional to rpm
kPapump proportional to rpm²
kW pump proportional to rpm³

• Reduction of speed 100% to 50%  “ 0.5”


– reduction of flow 47.8 l/s * 0.5  23.9 l/s
– reduction2 of kPa 200 kPa * 0.5²  50 kPa
– reduction3 of kW 12.5 kW * 0.5³  1.6 kW
‹#› Hydraulics & Chiller Sequencing
1) Hydraulic Fundamentals
Basic Formulas
• Pump
kW pump = l/s * kPa .
eff pump * eff motor * 1000
12.5 kW = 47.8 l/s * 200 kPa .
85% eff pump * 90% eff motor * 1000
• Pump laws
l/s pump a rpm
kPa pump a rpm2
kW pump a rpm3
• Reduction of speed 100%  50%
– reduction of flow 47.8 l/s 23.9 l/s 50%
– reduction2 of kPa 200 kPa 50 kPa 25%
– reduction3 of kW 12.5 kW 1.6 kW 13%

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Basic Formulas
Mixing
Flow1 10 l/s
Temp1 6°C
Flow2 5 l/s
Temp2 12°C

Flow3 15 l/s = 10 l/s + 5 l/s


Temp3 8°C = 10 l/s * 6°C + 5 l/s * 12°C
10 l/s + 5 l/s

Flow3 = Flow1 + Flow2


Temp3 = Flow1 * Temp1 + Flow2 * Temp2
Flow1 + Flow2

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Part Load in Terminals
100% Load 100% Flow 36% Flow 50% Load
7°C 7°C

27°C 13°C 23°C 15.5°C

12°C 14°C

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Water Flow in Terminals
2-way valve 36% 100% 36% 3-way valve
7°C 7°C

14°C 100%64% 7°C 14°C


9.5°C
‹#›Whatever
Hydraulicsthe control
& Chiller  terminal
Sequencing sees the same -reduced- water flow
1) Hydraulic Fundamentals
Terminal Control Options
• 2-way modulating valve
– Variable water flow (pump energy savings)
– (almost) Constant system return-water temperature
– Reduced installation cost
– Requires a System Bypass

• 3-way modulating valve


– Constant water flow
– Variable system return-water temperature
– Pump Energy Same at All Loads
– Flow Balance Critical
– Higher installation cost

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals

Example:

For a constant flow system


with 3-way valves

LOAD, % LOAD, kw RETURN T° SUPPLY T° ΔT


100 1000 12 7 5
80 800 11 7 4
60 600 10 7 3
40 400 9 7 2
20 200 8 7 1
0 0 7 7 0

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals

• Basic formulas
• Mixing
• Pipe Sizing
• Balancing
• Pumps: Parallel / Serial

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pipe Systems Design
 Two major concerns:
• Size the pipe (e.g. from charts & tables)
• Determine the flow-pressure relationship
 By analyzing the system, e.g. finding out pump pressure
 By using manual or computer-based methods

 Calculations for pipelines or pipe networks


• Can be very complicated for branches & loops
• Basic parameters: pipe diameter, length, friction factor, roughness,
velocity, pressure drop

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pipe Sizing
 While the moving water overcomes the resistance there is
pressure drop

 L   rV 
2
Dp  f *   *  
D  2 
Dp = energy loss through friction
f = friction factor
L = pipe length
D = pipe diameter
V = fluid velocity
r = fluid density

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pipe Sizing
• The pressure drop is quadratic function of the speed
• Longer the length, larger the pressure drop
• Narrower the diameter, larger the pressure drop
• Larger the density, larger the pressure drop
• Smoother the pipe surface, smaller the pressure drop

 Pressure drop and noise is a function of the flow speed


 Speed ranges set by economics & acoustics

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pipe Sizing
Speed
 Volume [m³] = surface [m²] * length [m]

 Speed [m/s] = distance [m] / time unit [s]

 Flow [m3/s] = volume [m3] / time [s]

 Flow [m³/s] = surface [m²] * speed [m/s]

Speed [m/s] = flow [m³/s] / surface [m²]

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pipe Sizing

Speed Limits Pressure Drop Limits

 Usual figures:  Usual figures:

• Larger pipes, • Larger pipes,


long distance over 50 mm diameter,
2.5 ~ 3 m/s long distance
• Branches
0.3 ~ 1.5 m/s 400 ~ 500 Pa / m
• Variable flow systems
up to 5 m/s

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals

• Basic formulas
• Mixing
• Pipe Sizing
• Balancing
• Pumps: Parallel / Serial

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Balancing
Typical complaints with balancing problems
 Some rooms never reach the desired temperatures,
particularly after load changes
 Room temperatures keep swinging, particularly at low and
medium loads, even though the terminals have sophisticated
controllers
 Although the rated power of the production units may be
sufficient, design power can’t be transmitted
 Un-favored circuits must wait for full flow until the
temperature sensors closes the favored circuits
 Many terminals only receive the desired temperature at
midday, some not until late afternoon, some
Particularly during start-up
after weekend or night set back

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Balancing

Some consequences of bad balancing


• Incorrect flows prevent controllers from doing their job
• The flow goes on the "easy way"
• Controllers can control efficiently only close to the
design flows conditions

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Balancing
Energy cost
Heating Cooling
Energy Waste by Unbalance
• When the system is not properly
balanced, tenant satisfaction is
achieved by over heating/cooling

• The energy cost rises radically


with every degree of over
tempering

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Balancing
What Can Influence Balancing?
Even the best-designed and best-built plants can suffer from
hidden operational problems:
– Clogged filters or valves,
– Terminal units replaced,
– Damaged pipe,
– Shut-off valve half open.

Measure differential pressure, flow and temperature and you will


find the cause!

Service and maintenance has an important role!

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals

• Basic formulas
• Mixing
• Pipe Sizing
• Balancing
• Pumps: Selection / Parallel / Serial

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pumps
Indoor coils
Are the “Heart of the system”
• Deliver media
• Lift against pressure
• Convert mechanical work
to energy (static and dynamic)
• Can overcome the system total pressure P1
• Meets the minimum net positive suction head System
requirements (no surge at the inlet) pump
• Maintains the dynamic pressure head at P0
components
• Multiple pumps are used for redundancy
• Can be constant or variable flow
Note: The major portion of the generated heat Chiller / Boiler
by the pump is absorbed by the system water!

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pump Selection
System
curve
• Where is our operating
point?
• System resistance curve
• Flow rate P1
• Pressure drop

Pressure
Operating
point
P2

F2 F1
Water flow

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pump Selection  Operating Point
Total Total (3) (4) steep
Pressure (1) Pressure (1)
[kPa] [kPa]
system (2)

(2)
system
flat

Flow [l/s] Flow [l/s]


Provides high pressure at constant flow Less sensible for Flow variation
Small change in system pressure (1) - (2) is stable operation: Higher pressure
changes the flow significantly means lower flow
(3) - (4) is unstable operation: Higher pressure
means more flow (impossible to control)

‹#› Note
Hydraulics the relationship
& Chiller Sequencing between pressure and flow change
1) Hydraulic Fundamentals
Pump Selection
• Determine the load
• Determine the temperature drop
• Determine the total flow
• Find the pressure on the most resistant circuit path
• Determine the pump type
Based on the just determined data:
• Select a pump family by the manufacturer's curves
• Select the pump by the individual pump performance curve
chart

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pump Parallel Operation

H
• total pressure will not
change
• forwarded amount of liquid is
summarized
HA

HB

QA QB 2QA 2QB Flow

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pump Parallel Operation
• The Operating Point H
travels the system
resistance curve System curve
• So in this example
Q2 = 1,4 x Q1

Q1 Q2 Q
The head pressures has to be balanced to avoid
‹#›the pumps
Hydraulics toSequencing
& Chiller work "against" each other !!!!!!!!!!!
1) Hydraulic Fundamentals
Pump Serial Operation
H
• forwarded amount of liquid is 2HB
not changed
• total pressure will be
summarized 2HA
HB
HA

QB QA Flow

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pump Serial Operation
H System curve
• The Operating Point travels
the system resistance curve
• So in this example
H2
H2 = 1,7 x H 1

H1

Q1 Q2 Flow

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pump Sequencing
Head Pressure System Curve (Circuit resistance)
More resistance Less resistance

If Pump has constant speed : When system


100% curve changes the functioning point follows
90% the PUMP curve
80%
If Pump has variable speed : When system
70%
curve changes the functioning point follows
the SYSTEM curve

Flow

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pump Sequencing
Head Pressure System Curve (Circuit resistance)

H2 The curves shows the combination


100% between two pumps:
90% Pump 1 Constant flow
80% Pump 2 Variable flow
H1 70%
60% Flow

‹#› Hydraulics & Chiller Sequencing


1) Hydraulic Fundamentals
Pump Sequencing
Flow

Variable speed
over 30% of range
100%
If you have two pumps in parallel, and only
one variable, you will not be able to control the
The control of the flow cannot be
flow correctly and therefore you won’t make the
optimal. The variable pump needs
energy @100%
Pump1 savings your are supposed to doto with at least 70% before the
reach
50%
a variable flow solution. flow increases.

You need a frequency drive on both pumps!

Pump2 @70%
Time

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulic
Arrangements

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
(bağımsız sabit akış)

Pump

3-way
valves

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
(bağımsız sabit akış)
Chiller: Start/Stop/Set point

Supply temp
(Besleme Sıcaklığı)
Constant Pump

Return temp
(Dönüş Sıcaklığı)

3-way
valves Change chiller set point
to control the load
(Yükü kontrol etmek için,chiller
ayar noktasını değiştirin)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1
CW RETURN CW SUPPLY
T° T°

CHILLER #2

LOAD
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 FLOW
CW RETURN SWITCH CW SUPPLY
TS1 (Akış Anahtarı)
T° T°

FLOW
TS2 SWITCH

CHILLER #2

LOAD
Minimum accessories needed
for a hydraulic system.
(hidrolik sistem için gerekli minimum aksesuarlar)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 7°c 7°c
CW RETURN TS1 CW SUPPLY
T° T°
100%
ON
12°c
7°c
TS2

100%
ON
FULL LOAD (100%)
Load fluctuation CHILLER #2
(Yük Dalgalanması)

LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 7°c 7°c
CW RETURN TS1 CW SUPPLY
T° T°
80%
ON
11°c
7°c
TS2

80%
ON
Load fluctuation LOAD 80%
CHILLER #2

LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80 11 80 7 80 7 7

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 7°c 7°c
CW RETURN TS1 CW SUPPLY
T° T°
60%
ON
10°c
7°c
TS2

60%
ON
Load fluctuation LOAD 60%
CHILLER #2

LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80 11 80 7 80 7 7
60 10 60 7 60 7 7

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 7°c 7°c
CW RETURN TS1 CW SUPPLY
T° T°
50%
ON
9,5°c
7°c
TS2

50%
CHILLER #2
ON
Load fluctuation LOAD 50%

LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80 11 80 7 80 7 7
60 10 60 7 60 7 7
50 9,5 50 7 50 7 7

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 7°c 7°c
CW RETURN TS1 CW SUPPLY
T° T°
40%
ON
9°c
7°c
TS2

40%
ON
LOAD 40%
Load fluctuation CHILLER #2

LOAD
LOAD, % RETURN T° CH1, % T° S1 CH2, % T° S2 SUPPLY T°
100 12 100 7 100 7 7
80 11 80 7 80 7 7
60 10 60 7 60 7 7
50 9,5 50 7 50 7 7
40 9 40 7 40 7 7

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 7°c 7°c
CW RETURN TS1 CW SUPPLY
T° T°
40%
ON
9°c
7°c
TS2

40%
ON
LOAD 40%
CHILLER #2

LOAD
Less than 50% load ….
(Yük 50% ‘den daha az….)

What about turning a chiller off ?


(Chillerlerin birini kapatsak mı ?)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CW RETURN
CHILLER #1 ? ?
CW SUPPLY
TS1
T° T°
40%
OFF
ON
9°c
7°c
TS2

40%
ON
LOAD 40%
CHILLER #2

LOAD
What happens to chilled water supply
temperature ?
(Soğutulmuş besleme suyu sıcaklığına ne olur ?)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 9°c 8°c
CW RETURN TS1 CW SUPPLY
T° T°

OFF
ON
9°c
7°c
TS2

ON
LOAD 40%
CHILLER #2

LOAD
Supply temperature higher means ….
(Besleme sıcaklığının yüksek olması demek ….)
Inability to satisfy load (Yükü
karşılayamamaktır)
(designed for 7°c)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow
CHILLER #1 9°c 7°c
CW RETURN TS1 CW SUPPLY
T° T°

OFF
ON
9°c
5°c
TS2

80%
ON
LOAD 40%
CHILLER #2

LOAD
How can we keep our designed
Supply temperature at 7°c ?
(Dizayn besleme sıcaklığımızı 7 °C de nasıl tutarız ?)
Change chiller #2 setpoint down to 5°c
(2 No’lu Chillerin ayar noktasını 5°c’ye düşürmek)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Constant Flow

• Lower water supply temperature means …


• (Düşük besleme suyu sıcaklığı demek…)

– Lower evaporation pressure (Daha düşük buharlaşma basıncı demek.)


– Higher compressor work (Daha çok kompresör iş yükü demek.)
9°c condenser C

pressure
5°c F E D
CW RETURN TS2
T° expansion
device compressor
ON
A B
CHILLER #2

enthalpy

‹#› Hydraulics & Chiller RISK


Sequencing
OF FREEZING EVAPORATOR !
2) Different Hydraulics
Non Decoupled Constant Flow
Chillers, set points and constant pump can be
controlled by the chiller plant control management
system.
Characteristics:
- 3-way valves  constant water flow
- Typical design for small industrial process
- Works great if cooling load is maximum all the time
- Supply temperature controlled using chiller set-points
- Reduced energy consumption
- Possible rotating of chillers (same working hours)
Risks:
- Variable chilled water supply temperature
- If load request not 100%, pump still runs 100%

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ayrılmaz Sabit Akış
Chillerler, ayar noktaları ve sabit pompa, chiller
fabrika kontrol yönetim sistemi ile kontrol edilebilir..
Özellikleri:
- 3 yollu vanalar  sabit su akışı
- Küçük endüstriyel proses için tipik tasarım
- Soğutma yükü her zaman maksimumsa işler mükemmel
- Chiller ayar noktalarını kullanarak besleme sıcaklığı kontrol edilir
- Düşürülmüş enerji tüketimi
- Chillerlerin dönüşümlü olabilmesi (aynı çalışma saatleri)
Risks:
-Değişken soğutulmuş su besleme sıcaklığı.
-Yük ihtiyacı % 100 değilse bile, pompa hala % 100 çalışır.

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)
(bağımsız değişken akış) (Sıralı)

3-way
valves

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)
Chiller: Start/Stop/Set point

Constant
Flow
Pumps
Supply
Temp

Return Temp

3-way
valves

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)
CHILLER #1
TS1 CW SUPPLY

TS2

CHILLER #2
CW RETURN

LOAD
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)
CHILLER #1
TS1 CW SUPPLY

M

OFF OFF
ON

TS2
M

ON ON
CHILLER #2
CW RETURN

LOAD
What happens at partial load if we
switch OFF one chiller with his pump?
(Bir soğutucuyu pompasıyla birlikte kapattığımızda
kısmi yüke ne olur?)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)
3 Way Valve Circuit
12th Floor
Distant from the production, (Üretime uzak)
LOAD high pressure drop (Yüksek basınç düşmesi)

Close to production, (Üretime yakın)


low pressure drop (Düşük basınç düşmesi)
Ground Floor

PRODUCTION
LOAD

System is balanced for nominal flow
(Sistem nominal akış için dengelenmiştir)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)
3 Way Valve Circuit
12th Floor
LOAD 40 l/s

By-pass : 10 l/s

50 l/s

50 l/s 30 l/s
Ground Floor

PRODUCTION
LOAD 100 l/s

By-pass : 20 l/s

System is balanced
Nominal flow = 100 l/s 100 l/s

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)
3 Way Valve Circuit
12th Floor
? l/s
LOAD STARVING H System curve

By-pass : ?

? l/s Q1 Q2 Q

50 l/s 10 l/s
Ground Floor

PRODUCTION
LOAD

½ CAPACITY
60 l/s

By-pass : 40 l/s

Let’s suppose we have a flow of 60 l/s. 60 l/s


(60 l/s debimiz olduğunu varsayalım)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Non Decoupled Variable Flow (Sequenced)

The chiller and its dedicated pump are switched on and off according
to the estimated cooling load and the outside weather conditions
In this system we get sequenced flow as per the number of chillers
running at the same time

Characteristics:
- 3-way valves
- Pump per chiller
- Typical design for small Building process
- Control based on the variation of the flow
(1 pump/chiller set or both)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Constant Secondary Flow
(Ayrıştırılmış Sabit İkincil Akış)

Larger Loads
Larger Installations
For larger installations,
pressure drop in the distribution circuits is higher as
• More piping length, curves, balancing valves, accessories
• More terminal units
• Larger terminal units (more water to handle, larger flow)

Pump are bigger resulting in too large flow to be


handle by one pump.

SOLUTION : Split production and distribution pumps

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Constant Secondary Flow
Constant
production Pump
Pumps Constant flow
(Sabit üretim pompası) (Sabit akış pompası)

Supply
Temp
Return Temp

3 ways valves

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Constant Secondary Flow
Constant
production
pumps

Pump
Supply Temp Constant flow

Return Temp

3 ways valves

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Constant Secondary Flow
50 l/s at 6°C
100% Load
50 l/s at 6°C
100 l/s at 12°C
100 l/s at 6°C

No flow
100 l/s at 6°C

100 l/s at 12°C

50 l/s at 12°C
three-way valve
50 l/s at 12°C

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Constant Secondary Flow
OFF No flow
50% Load
50 l/s at 11,5°C 50 l/s at 6°C
OFF
50 l/s at 6°C

50 l/s at 11,5°C
100 l/s at 8,5°C

100 l/s at 11,5°C

50 l/s at 11,5°C
three-way valve
50 l/s at 11,5°C

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Constant Secondary Flow
Primary-Secondary with a by-pass
Dedicated pump per chiller
By-pass flow is the difference of water flow between the 2 circuits
when not all chillers/primary pumps are running
In this case a Constant speed secondary pump is used
This is a frequently used system, but it is not the most stable in supply
temperature and certainly not the most energy efficient!
Warning: Trane does not recommend this design !
Characteristics:
- Supply temp. control only by changing the chiller set points
- The reactivity of the control is very slow because the set points have to
be changed very slowly to avoid start/stop cycling
- Max. supply temp. accuracy +/- 1.5 °C
- Waste of energy because the secondary flow pump will run 100% all
the time whatever the demand.
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow

production
pumps

pump

production
loop

distribution
loop

two-way valves
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Decoupled Variable Secondary Flow
The chiller set points are constant, system control is achieved through
the variable speed pump
Constant
production
pumps Variable
pump

Supply
Temp
production
Return Temp
loop

distribution two-way valves


loop

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow
CHILLER #1

50 l/s

PRODUCTION FLOW
CHILLER #2 EQUALS
DISTRIBUTION FLOW
50 l/s (ÜRETİM AKIŞI=DAĞITIM AKIŞI)

PRODUCTION PRODUCTION 50 l/s 50 l/s


LOAD LOAD
DISTRIBUTION BY-PASS = +/-0 l/s DISTRIBUTION
Nearly No Flow

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow
CHILLER #1
PRODUCTION FLOW
50 l/s DIFFERENT FROM
DISTRIBUTION FLOW
(Üretim akışı, dağıtım akışından farklı.)
ON
CHILLER #2
DECOUPLED SYSTEM,
50 l/s
NO PUMP IN SERIE
(Bağımsız sistem, Seri bağlantıda olan pompa yok)
ON
PRODUCTION PRODUCTION
50 l/s 25 l/s
LOAD LOAD
DISTRIBUTION BY-PASS = 25 l/s DISTRIBUTION

Variable
speed drive
ΔP

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow
Varying Distribution Flow (Değişen Dağıtım Akışı)
Variable-speed control Riding the system curve
(Değişken hız kontrolü)

LOAD

head pressure
ΔP
Variable
speed drive

pressure
difference 0 percent flow 100

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow
CHILLER #1

50 l/s Load decreases (Yük azalır)


Distribution flow decreases (Dağıtım akışı azalır)
ON
By-pass flow increases (Baypas akışı artar)
CHILLER #2
By-pass flow not used by the
50 l/s distribution circuit = excess flow
(Baypas akışı,dağıtım devresi tarafından
kullanılmaz = aşırı akış)
ON
PRODUCTION PRODUCTION
20 l/s 25 l/s
LOAD LOAD
DISTRIBUTION
BY-PASS = 55 l/s DISTRIBUTION

Excess Flow
Variable
speed drive
(Değişken hız ΔP
sürücüsü)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow
CHILLER #1

50 l/s
Excess by-pass flow > 110%
of one chiller flow
ON ,(Aşırı baypas akışı bir chillerin akışından 110% fazladır

CHILLER #2 One chiller can be turned off


(Bir Chiller kapatılabilir)
50 l/s

ON
PRODUCTION PRODUCTION
15 l/s 20 l/s
LOAD LOAD
DISTRIBUTION BY-PASS = 65 l/s DISTRIBUTION

Excess Flow
Variable
speed drive
ΔP

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow
CHILLER #1

0 l/s
Production flow is 50 l/s against
35 l/s needed
OFF
ON (Üretim akışı 35 l/s ihtiyaç olmasına karşın 50 l/s)

CHILLER #2
By-pass flow is 15 l/s in excess
direction
50 l/s (Aşırı yönde bypass akışı 15 l / sn'dir.)

ON
PRODUCTION PRODUCTION
15 l/s 20 l/s
LOAD LOAD
DISTRIBUTION BY-PASS = 15 l/s DISTRIBUTION

Excess Flow
Variable
speed drive ΔP

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow
CHILLER #1

0 l/s Load increases (Yük artar)


Distribution flow increases (Dağıtım akışı artar)
OFF
ON
By-pass flow changes direction
CHILLER #2 and increases (Baypas akışı yön değiştirir ve artar)
50 l/s By-pass flow not produced = deficit
flow (baypas akışı yok = açık akış)
ON
PRODUCTION PRODUCTION
30 l/s 35 l/s
LOAD LOAD
DISTRIBUTION BY-PASS = 15 l/s DISTRIBUTION

Deficit Flow
Variable
speed drive
ΔP

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Decoupled Variable Secondary Flow
Here we have variable speed secondary pumps (instead of constant speed)
and we have 2-way valves on the equipment (instead of 3-way valves)
Measuring the direction of water flow and the amount in by-pass gives a
correct indication of when to add or subtract a chiller
Characteristics:
- 2-way valves
- Good design for all type of cooling processes
- Control based on the variation of the flow
- Best solution for temperature accuracy
- Best solution for energy saving
- Variable speed pump controlled from differential pressure in secondary
circuit
- Chillers and pumps sequenced by Bypass flow or Water temperatures
Risks:
- Too low flow in distribution equipment
- Poor heat exchange functionality
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
By-Pass
Sensing Deficit Flow
PRODUCTION

PRODUCTION CHWR CHWS PRODUCTION

DISTRIBUTION DISTRIBUTION

Deficit Flow
CW SUPPLY

DISTRIBUTION
Load is increasing
Distribution Flow is increasing
We have a deficit flow in the by-pass
The temperature sensor to see effect of Deficit Flow will be placed

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
By-Pass
Sensing Excess Flow
CW RETURN
T° PRODUCTION

PRODUCTION CHWR CHWS PRODUCTION

DISTRIBUTION DISTRIBUTION

Excess Flow

DISTRIBUTION
Load is decreasing
Distribution Flow is decreasing
We have an Excess flow in the by-pass
The temperature sensor to see effect of Excess Flow will be placed

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
By-Pass
PRODUCTION

• When deficit flow appears


– Seen by Temperature sensor
 ADD A CHILLER Deficit Flow
DISTRIBUTION

• Excess flow > 110% to 115% of the flow


of the chiller to be turned off PRODUCTION
– Seen by Temperature Δt
Sensors
OR
Excess Flow
– Seen by Flow sensor device
 SUBTRACT A CHILLER DISTRIBUTION

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
By-Pass Sizing

• Bypass sized for 110 to 115 percent of the largest


chiller’s designed flow rate AND for minimum
security flow of all chillers (in case distribution flow
breakdown)
• Minimum length of 5 to 10 pipe diameters is
recommended to prevent random mixing of the
supply
• Minimal pressure drop in bypass pipe
– No obstruction (valves or other)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Chillers in Series

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Chillers in Series
• Advantages
– Constant chilled-water supply temperature
– Constant water flow within system and chillers
• Issues
– Addition of Pressure Drop
– High flow
• Fix:
– Selection of low pressure drop heat exchangers
– Best apply with high delta T system
• Limitation:
– (More) Complex control
– More complex piping (valves, pipes) for the maintenance or an
emergency- redondant chiller

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Chillers in Series

• Summary
– Can generate more capacity than parallel chillers
 At a better EER
– Allows to preferentially load a chiller
 Heat Recovery Unit
– Allows for large water temperature rise/drop
 Reduced water flow  Reduced pump input

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Variable Primary Flow

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Variable Primary Flow

Prefer manifold pumps:


‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Variable Primary Flow
VPF is a method for balancing production and
Variable-
UCP2
UCP2
distribution flows by making them equal
Speed
Drive
UCP2
UCP2

Flow

S UPP LY
Meter Production
DE MAND Air Handling Units
Bypass Line
Distribution

Control Valves

System variation of the primary/secondary flow


system is a ‘Highly Specialized’ design

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Variable Primary Flow
VPF Key Principles
• Just as in the primary-secondary system, VPF systems respond
to load changes by modulating flow

• In a VPF system, water flow varies throughout the entire system,


i.e. also through the evaporator of each operating chiller as
well as through the cooling coils

• VPF system elements:


- Two-way control valves on coils
- Check (or isolation) valves on chillers
- A bypass line with a control valve is mandatory
- Smallest VPF Chiller = 300 kW

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Variable Primary Flow
• Prerequisite:
– Chillers must handle variable evaporator flow
– System-level controls must limit the rate-of-flow change
– System must include a controlled bypass
• Advantages
– One set of (variable volume) pumps
 Savings in first cost, space, operation
– Bypass
 Sized on (largest chiller minimum flow)
 Could be located in the plant room or in the distribution loop
• Issues:
– Adequate time to design and commission controls
– Operator must understand the system

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Variable Primary Flow
VPF system – can only be used when…
• Load demand is variable
• Chillers with adaptive controls
– Operator understands plant operation

VPF system - benefits


• Reduced pumping costs
• Reduced piping costs
• Reduced electrical costs

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Out of Range Applications
• Flow out of Range

chiller 15 L/s at 7.0°C

15 L/s at 13.0°C

5 L/s at 7.0°C

5 L/s at 25.0°C
Industrial Process
(375 kW)
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Out of Range Applications
• Flow out of Range
chiller 15 L/s at 7.0°C

15 L/s at 13.0°C

5 L/s at 7.0°C

5 L/s at 25.0°C
Industrial Process
(375 kW)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Out of Range Applications
• Flow and Temperature out of Range
chiller 15 L/s at 7.0°C

15 L/s at 13.0°C

5 L/s at 20.0°C

5 L/s at 38.0°C
Industrial Process
(375 kW)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Out of Range Applications
• Flow and Temperature out of Range
chiller 15 L/s at 7.0°C

2.9 L/s at 7.0°C


15 L/s at 13.0°C

5 L/s at 20.0°C
2.9 L/s at 38.0°C

5 L/s at 38.0°C
Industrial Process
(375 kW)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Water Content
• To estimate the minimum water content
on a system, we can use the following
Rule of Thumb relationship between
Cooling capacity & Evaporator water flow:

Flow (6°/12°) [l/s] = cooling kW / 25

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Water Content

• Loop time is the time required for chilled water to make one round trip in
the distribution system.

• Depending on the type of chiller control the required loop time can vary
between 1..3..5 minutes.

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Water Content

• Practically the 3 minutes is a good guess, i.e.:


Minimum Water Content [l] = Flowrate [l/s] * 180 s

• We have seen that:


Flow (6°/12°) [l/s] = cooling kW / 25

• Therefore:
Min. Water [l] = Cooling capacity [kW] * 7,2 [l/kW]
 For example: a chiller has 250kW cooling capacity,at 6°/12°C
the flow is roughly 10 l/s = 600 l/min = 0.6 m3/min
 with 3 minutes loop time the ideal water content minimum is around 1.8 m3

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Buffer Tanks THE PURPOSE OF
Chiller THE STORAGE
TANK IS TO STORE
A CERTAIN
AMOUNT OF
WATER TO
Pump SATISFY THE
Load DEMAND DURING
THE STOP TIME
Buffer
Tank OF THE CHILLER.

The buffer tank has to be on the return to allow


warmer water capacity to the chiller in case of small
loads. It also allows the CONTROLLER time to adapt
to the load.

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Buffer Tanks

• Is an extension of the system volume,


to enlarge the water content
• It should have a mixing function
• Can be used as hydraulic by-pass
• Thermally well insulated

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Buffer Tanks
WHAT DOES AFFECT TANK SIZE?
• Minimum Load
• Number of cooling steps
• Anti-recycle timers
• Control Dead-Band
• Installation Water content
• Allowed temp. fluctuation

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Buffer Tanks
• Available Energy Qty in Tank:
– Q = M x C x DT
• Required Time to reach a given DT:
– t = (M x C x DT)/Load
• So:
– DT = (Load x t) / (M x C)
or
– M = (Load x t) / (DT x C)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Buffer Tanks
EXAMPLE
• Chilled Water Temp.: 12/7°C Entering Leaving
• 2 compressors
• Cooling Cap. at Full load: 85 kW
• Minimum building Load 20 kW
• Anti-Recycle Timer: 10 min
• Control Dead Band: 4°C
• Total Volume of water Loop: 400 l (Pipes + Tank)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Buffer Tanks
EXAMPLE
• Water Temp. in the tank when chiller stops:
– (Chilled Water setpoint) - (Dead band/2) + (DT at 50% Load)
– 7°C - 2 + 2.5 = 7.5°C
• Average Anti-recycle timer:
– ART(for 1 compressor) / (Nbr of compressors)
– 10 / 2 = 5 min = 300 s
• Water temp. rise in tank 5 min Later:
– DT= (300 x 20)/(400 x 4.18) = 3.6°C
– 7.5°C + 3.6°C = 11.1°C  This is to much
Normally + 2°C is excepted as maximum.
So we calculate M with these 2°C raise.
M = 20 x 300 / 2 x 4,18  717,7 l Must be total Content

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Buffer Tanks
What would be the reason to add a tank in
the installation ?
Is it correctly placed for this purpose ?
What are the parameters that influence
sizing of the tank ?

LOAD

LOAD
M

TANK

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Buffer Tanks
• Adding a tank protect chiller from short-cycling
– If the water volume (content) of the installation is not sufficient
– If Load is likely to vary quickly
• Tank should be placed after loads to absorb loads variations
(temporize loads variations). Tank is named “buffer tank”
• Parameters for sizing (volume) are
– Anti-short cycling time
– Minimum capacity of the chiller (before turning off)
– Water volume of installation
– Authorized variation of Temperature (chilled water set point
deadband)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Expansion Tanks
Water Expansion
• As temperature changes water expands or shrinks
• Expansion Tank has to be selected according to the water content and
temperature range of the system

Temperature [°C] 30 40 50 60 70 80 90
Expansion [%] 0.4 0.75 1.17 1.67 2.24 2.86 3.55

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Expansion Tanks
Accommodates the volume change caused by temperature
change

• Open-tank
tank open to atmosphere
•A diaphragm tank
flexible membrane

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Expansion Tanks

Diaphragm tank
Connector
– flexible membrane
Polypropylene liner
Reservoir
Butyl diaphragm
Nitrogen cushion

Nitrogen charge valve

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Expansion Tanks
Thermal function:
• The water which occupies 1 m3 @ 10°C
occupies 1,044 m3 @ 80°C
• Need space for 44 litres of water

Hydraulic function:
• System pressure reference point

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage Tank

Example are Calmac tanks


‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
Ice Storage

pump chiller

cooling heat-transfer
coil fluid

ice storage
tanks

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
ice VFD
ice storage
pu tanks
mp
cooling
coil with bypass
two-way pipe
control valve

load
pump

VFD
water-cooled chiller
chiller pump

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
ice VFD
ice storage
pump tanks

cooling
coil

off-peak
chiller
off-peak load ice chiller
pump pump chiller pump

VFD VFD

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
Intermediate Heat Exchanger ice storage
tanks

heat
exchanger
cooling
coil
ice
load valve
pump
chiller
pumps
VFD

existing ice-making ice


chillers chiller pump

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
100

75
cooling load, % of design

50
Building Cooling Load Profile
25

0
midnight 6 a.m. noon 6 p.m. midnight

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
100

75
cooling load, % of design

off peak on peak off peak

50

On-Peak and Off-Peak Periods


25

0
midnight 6 a.m. noon 6 p.m. midnight

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
100

75
cooling load, % of design

On-Peak Cooling with Ice

50
make melt
ice ice
25

0
midnight 6 a.m. noon 6 p.m. midnight

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
100

75
On-Peak Cooling with Chiller and Ice
cooling load, % of design

melt
ice
50
make
ice
25
chiller
0
midnight 6 a.m. noon 6 p.m. midnight

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
100
cooling load, % of design

75
melt melt
ice ice
50

make make
25 ice ice
chiller chiller
0
midnight 6 a.m. noon 6 p.m. midnight midnight 6 a.m. noon 6 p.m. midnight

Peak shaving Load shifting


The melt of Ice is used to The melt of the Ice is used
reduced the electrical peak to reduce the electrical
consumption when the consumption on peaks
demand of electricity when the electricity
in the building is high. is very expensive

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
Downsizing the Chiller
100
chiller melt
capacity ice
cooling load, % of design

75
chiller
capacity
50

chiller
make chiller
25 ice

0
midnight 6 a.m. noon 6 p.m. midnight midnight 6 a.m. noon 6 p.m. midnight

Full-sized chiller Downsized chiller

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
Potential Benefits
• Lower utility costs
– Lower on-peak electrical consumption (kWh)
– Lower on-peak electrical demand (kW)
• Smaller equipment size
– Smaller chiller
– Smaller electrical service (A)
• Reduced installed cost
– May qualify for utility rebates or other incentives

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
Cooling-only chiller Ice-making chiller
– Increases or – Operates at
decreases capacity maximum capacity
in response to while in
changing cooling ice-making mode
load – Operates until
– Controlled to entering-fluid
maintain leaving- temperature drops
fluid temperature at below lower limit
setpoint

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Ice Storage
Combining tactical and strategic control
Overlapping Operating Modes
operating mode start time end time
chiller only 6 a.m. noon
ice only noon 8 p.m.
chiller and ice noon 8 p.m.
chiller only 8 p.m. midnight
freeze and cool 8 p.m. midnight
freeze midnight 6 a.m.
off when building or ice-making loads
are not present
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics
• Non Decoupled Constant Flow
• Non Decoupled Variable Flow (Sequenced)
• Decoupled Constant Secondary Flow
• Decoupled Variable Secondary Flow
• Decoupling line sizing
• Chillers in Series
• Variable Primary Flow
• Out of range applications
• Water Content / Buffer tanks / Expansion tanks
• Ice storage
• Cooling towers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers
• Generally, water cooled chillers use cool
(e.g. 15 to 30°C) water to condense refrigerant.

• This cool water may come from


– Cooling tower
– Lake or river
– Ground water
– Geothermal loop
– Dry Cooler

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers

Condenser water
system
cooling tower

condenser

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers
Chiller – Tower Interaction
• Tower determines return condenser water
temperature
• Chiller determines required heat rejection rate of
tower
• Condenser water warms in proportion to heat
rejection and condenser water flow rate
• Condenser pressure rises with condenser
temperature
• Compressor work increases as
condenser pressure rises

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers

• Heat transfer device, often tower-like, in which


atmospheric air cools warm water, generally by direct
contact (evaporation).

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers
propeller fan

sprays
louvers

outdoor fill
air

sump
to from
condenser cold water hot water condenser

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers
Cooling Tower Types
Open-Circuit Closed Circuit

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers
Definitions
• Wet Bulb
• Range
– Difference between tower entering and leaving water
temperatures
• Approach
– Difference between ambient
wet bulb temp and tower
leaving water temp
• Flow rate

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers
Performance Factors
• Interferences
• Position/Orientation
 Restrictions
 Air recirculation
 Obstacles
 Piping positioning
• Recirculation
 Space
 Winds
 Air velocity
 Plume (fogging)

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics

Dry Cooler
• A dry cooler is a forced convection air-cooled fluid
cooler.
• Air is forced over a finned coil which contains the
working fluid such as water or water & glycol mix.

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics

Dry Cooler Principle

from condenser to condenser


 In a dry cooler, there is no direct contact between
atmospheric air & condenser water!
‹#› Hydraulics & Chiller Sequencing
2) Different Hydraulics

Dry Cooler
PROs CONs
• Cost similar to evaporative cooling • Higher leaving water temperature
tower
• High electrical consumption due to the
• No water consumption numerous fans
• No sanitary risk of Legionnaires’ • High noise level because of higher
disease airflow rate
• No need of chemical water treatment • Necessity to add glycol to water to
avoid freezing of installation
• No plume
• Important ground surface
• Easy maintenance, even if finned coils
must be regularly cleaned to keep
efficiency

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Cooling Towers
Capacity Control
• Lowest possible leaving water temp
= ambient wet bulb + approach

• Maintain tower leaving water setpoint


by modulating airflow, using:
– Fan control
 Cycling (On/Off)
 Two-speed fans
 Variable speed drives
 More economical to modulate multiple fans
than have one at full speed
– Modulating dampers

‹#› Hydraulics & Chiller Sequencing


2) Different Hydraulics
Dry Coolers
Some examples of free-cooling with dry-coolers in combination with
water-cooled chiller and air-cooled chiller.

Example 1: Water-Cooled chillers, decoupled variable secondary


flow at the condenser side and decoupled

‹#› Hydraulics & Chiller Sequencing


Example 1: 100% Mechanical Cooling

n + 1 scenario:
• One chiller running
• One chiller stand by
• Free cooling off
• Four dry coolers running
• One dry cooler stand by
• Chiller has the best COP
• No extra pressure drops are created
 Save pump energy

All dry coolers could be running if


wanted, to optimize efficiency.

Optimal functioning in full load


and part load is guaranteed by the
Chiller Plant Control:
Sequencing of chillers, ...
‹#› Hydraulics & Chiller Sequencing
Example 1: Simultaneous Mechanical
Cooling and Free-Cooling

• Free Cooling circuit opens


• One chiller running
• One chiller stand by
• Five dry coolers are running
to maximize the free cooling capacity.

Optimal functioning is guaranteed by the


Chiller Plant Control:
Free Cooling and Chiller working together

‹#› Hydraulics & Chiller Sequencing ...


Example 1: 100% Free-Cooling

• Chillers off
• Free cooling on
• Five dry coolers are running.
When very low ambient temperatures,
the dry coolers also go into part load.

Optimal functioning is guaranteed by


the Chiller Plant Control

‹#› Hydraulics & Chiller Sequencing


Example 2: Free-Cooling System set-up
with Air Cooled Chillers

‹#› Only example – Temperatures are not right


Hydraulics & Chiller Sequencing
3) Chiller Plant Control

• Chiller Sequencing
• Load / Unload
• Rotations
• Failure Recovery
• Tower Optimisation

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control

Chiller Plant
Automation
System Cooling
Loads

Remember:
Without controls, it’s not a system.

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control

Chiller Plant Control is more than


turning chillers On and Off.

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control

• What are the requirements:


– Reliable chilled water flow
– Operating cost (energy
efficiency)
– Operator safety
– Environmental awareness
– Reduce maintenance cost

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Key Issues for Chiller Plant Control

• Load determination
– When to add or subtract a chiller?
• Capacity matching
– Number of running chillers required?
• Rotation
CHILLER
– Which SEQUENCING
chiller leads?
• ChillerWhich
setpointchiller to turn on or off?
control
– What is the setpoint strategy?
• Failure recovery
– What happens after a chiller failure?
• Operator interface
– How to communicate with the operator?

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control

Chiller Plant Control

Load Chiller
Determination Sequencing

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing

• Turning on an additional chiller


• Turning off a chiller
• Which chiller to turn on or off?

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Load Determination
• When to add or subtract a chiller ?
– Look at the building needs

 Match plant capacity to building(s) load.


– Said another way...
 Run as few chillers as possible at optimal efficiency

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
• Which chiller to turn on or off?
– Turn the right chiller on!

• Decision taken according to the following criteria:


– Load determination
– Capacity matching
– Rotation
– Chiller setpoint control
– Failure recovery

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Load Determination
• Applies to Constant or Variable Flow systems
• Add logic
– Based on Supply Temp & Chilled Water Setpoint
– Operator editable delay times and dead bands
• Subtract logic
– Based on:
 Supply/Return water temperatures & Chiller capacities
 or Bypass Flow (for large systems) & Chiller flows
– Operator editable delay times and dead bands
• Custom
– Adaptable to suit customer specific algorithm requirements

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Add Example

Add timer starts Chiller is added

6.5°

1.5° Add temp


Add timer dead band
reset 5°

Add delay
time (10 mn)
Chilled water supply temp System supply
set point
Parameters

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Temperature Based Logic
• Preferred method for:
– Non-decoupled systems (constant flow) and
– Decoupled systems (variable flow) up to 4 chillers
• Based on supply & return chilled water temp
• Simple to setup and to understand
• Add logic:
– Based on error from
chilled water system
supply setpoint
• Subtract logic:
– Based on system Delta T
‹#› Hydraulics & Chiller Sequencing
3) Chiller Plant Control
Chiller Sequencing
Subtract Example
(Temperature)
Chilled water delta temp

Chiller is
Subtract timer starts
subtracted
Design delta temp 3°

Subtract timer reset


Subtract temp dead
band 0°

Subtract delay
time (20 minutes)
Parameters

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Bypass Flow Based Logic
• Recommended for larger systems, i.e. decoupled systems
with more than 4 chillers
• Much more accurate than temperature based logic
• Add logic based on deficit flow
• Subtract logic based on excess flow
• Two sensing methods:
– Direct flow
– Indirect flow

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Bypass Flow – Direct Flow Sensing
• Flow measured with any type of flow meter
• Common problems when using flow meters:
– Accuracy + regular calibration required
– Cost Production
• Add a chiller
– Deficit flow
(based on error from chilled Load
water system supply setpoint )
• Subtract a chiller Production
– Excess flow > 110% of the flow
of the chiller to be turned off
E.g.: Chiller flow = 30 L/s, Load
Turn it off when excess flow = 33 L/s

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Subtract Example (Flow)
Subtract flow threshold Chiller is
Subtract timer starts Subtracted

70 l/s

60 l/s

Subtract timer reset

By-pass Pipe
flow ???????

Subtract delay
time (20 mn)
Parameters

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Capacity Matching
• What is the necessary number of running chillers
required?

• Purpose:
– Reduce operating cost by turning on and off the appropriate
chillers when needed
• Dependent on chiller types and sizes available
• Linked to the chillers rotation priority sequence!

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Capacity MatchingChillers On vs. Load
100% 2600
Chiller 1 (1000)
80% 2080 Chiller 2 (1600)
% Building Load

60% 1560

40% 1040

20% 520
kW
0%
Chiller Stages

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Capacity MatchingChillers On vs. Load
78% 5800
Chiller 5 (1600) Peak
Chiller 4 (1600) Base
65% 4800 Chiller 3 (1600) Normal 2
% Building Load

Chiller 2 (1600) Normal 1


57% 4200 Chiller 1 (1000) Swing

43% 3200
38% 2800

21% 1600
kW

0%
Chiller Stages (7400 kW Load)

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Chiller Sequencing
Swing example

UCP2 UCP2
UCP2

200 Ton Chiller 500 Ton Chiller (Normal500 Ton Chiller (Normal
(Swing) - 1) - 2)

0 200 500 700 1000 1200


Building Load (Tons)
The small chiller is used to match the flow capacity.

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control

• Chiller Sequencing
• Load / Unload / Soft Start
• Rotations
• Failure Recovery
• Tower Optimisation

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Load / Unload / Soft Start
• What is the chiller startup sequence?
– Start the chilled water pump
– Wait for a chilled water flow confirmation
– Chiller is enabled
– Wait for chiller status confirmation

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Load / Unload / Soft Start

• What is the purpose of unloading operating chillers before


starting an additional chiller?
– Remember: before you start a chiller you typically start a pump
or open a valve!
– This results in:
 A flow transient through the chillers
 Operational disturbance.

 In the worst case it can result in a chiller getting locked out


on low evaporator temp!

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Load / Unload / Soft Start

Unload at start

• Avoids electrical consumption peaks


when you start a new chiller
• Avoids flow discontinuities

In Variable Primary Flow Systems, this function is


necessary in order to prevent freezing the evaporator

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Load / Unload / Soft Start

• When do we need a soft start ?


– System soft loading is sometimes required during
system hot starts,
– Prevent more chillers than are actually required to
meet the load.

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Load / Unload / Soft Start
Soft Start Example
System chilled water
supply temperature
Chiller plant
enabled in the 16°
soft start mode

Chiller plant
transitions from 10° Soft start dead band
soft start mode to
normal mode
7.5°
System supply
1.5° Add temp dead band set point

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Load / Unload / Soft Start
Soft Load gives time to the first chiller to reach the setpoint temperature
when the complete plant starts with warm water temperature
System chilled water
supply temperature
Chiller plant
enabled in the 16°
soft start mode

Chiller plant
Soft Loading prevents a peak
transitions from in electric
10° Soft start dead band
consumption that would happen if
soft start mode
to normal mode
all chillers were started at the same time 7,5°
System supply
1,5° Add temp dead band set point

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Load / Unload / Soft Start
• Summary:
– Soft Start
 Prevents excess capacity on “warm” starts
 Pull down the system smoothly
 Don’t “machine gun” chillers on and off

– Unload before start


 Ride out flow transients during pump control
 Variable flow / multiple pump systems
 Low supply water temperatures (1 to 3°C)

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Ambient Lockout
Automatically disable the chiller plant when the outside air
temperature drops below the ambient lockout setpoint.

12°C

2°C
10°C

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control

• Chiller Sequencing
• Load / Unload / Soft Start
• Rotations
• Failure Recovery
• Tower Optimisation

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Rotations

• Which chiller leads?


– Look at the chillers priority order

• Factors influencing the rotation decision:


– Chiller plant design,
– Relative chiller age,
– Relative chiller efficiency,
– Customer preference.

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Rotations

• Action based on either (for normal sequencing only!):


– Selected rotation type
– Calendar
– Other system inputs
– Run time
– Manual operator action

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Rotations
• Normal rotation type:
equal-capacity chillers

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Rotations
• Example of a special rotation type:
small electric
chiller large electric
chiller
absorption
chiller

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control

• Chiller Sequencing
• Load / Unload / Soft Start
• Rotations
• Failure Recovery
• Tower Optimisation

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Failure Recovery
• Maintain flow of chilled water
• Keep it simple
– Lock out failed equipment
– Turn on the next chiller in the sequence
– Turn on Back-up Pump
• Notify the operator
• Allow the operator to intervene

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control

• Chiller Sequencing
• Load / Unload / Soft Start
• Rotations
• Failure Recovery
• Tower Optimisation

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Tower optimization
Condenser temperature
100
Chiller 27°C

Power (% of KW)
80 23°C
19°C
60

40

20

0
0 20 40 60 80 100
Load (%of kW)

Compressor Power Input increases by 2.5% to 3% approx


when Cond. Leaving Water Temperature increases by 1°C
– Compressor Power Input is function of
Condenser Leaving Water Temperature and Load

‹#› Coldest Water is better for the compressor


Hydraulics & Chiller Sequencing
3) Chiller Plant Control
Tower optimization
Cooling Tower Air
Flow Rate
– Cooling Tower Performances depend on
Warm Water
 Approach Temperature
 Range
Range
 Water Flow Rate
 Air Flow Rate
Cold Water
Temperature
Water
Approach Flow Rate

Ambient Wet Bulb


Coldest Water is obtained at reduced Approach
 at the maximum airflow

‹#› Hydraulics & Chiller Sequencing


Coldest Water is harder for the cooling tower
3) Chiller Plant Control
Tower optimization
- The condensing pressure is the refrigerant pressure in the
chiller compressor
- The more you decrease this pressure the less energy the chiller
will use
The target is to find the optimal
tower set point so that
energy used by the chillers AND
the towers is the lowest possible
-To reduce this pressure, the condenser water temperature
needs to be lowered

- To lower the condenser temperature, the tower setpoint needs


to be decreased, and therefore the tower will use more energy

‹#› Hydraulics & Chiller Sequencing


3) Chiller Plant Control
Tower optimization
Chiller kW +
Towers kW Optimizing
200 kW
1 100 kW
23°C WB
160 kW
550 kW
120 kW 19°C WB

80 kW 300 kW
15°C WB
40 kW

15°C 20°C 25°C 30°C 35°C


Leaving Condenser water set point

‹#› Hydraulics & Chiller Sequencing


4) Wrap-UP
Best Practices in System Design

Multiple chillers system are more common than


single chiller systems for the same reason that most
commercial airplanes have more than one engine.
Balance of reliability and cost.

Selection of the optimum coil size and type from


the wide variety available is important for proper
system performance (Terminal units)

‹#› Hydraulics & Chiller Sequencing


4) Wrap-UP
Best Practice – Temperature Sensor
• Temperature sensor requires good installation for accurate
temperature, sensor up to central axis of the tube
• Sensors need to be calibrated all together
• Sensors of same type for a common regulation
• Proper positioning to see deficit (supply) and excess flow
(return)

Don’t take Temperature Sensor value for granted.


Check the right positioning and calibration.

‹#› Hydraulics & Chiller Sequencing


4) Wrap-UP
Best Practice – Check Valve
• Check-valve should be correctly placed into the system
• Selection is important. Take into account additional pressure
drop for this device

Compare arrow on the check valve


with desired flow in the circuit

‹#› Hydraulics & Chiller Sequencing


4) Wrap-UP
Best Practice – Flow Switch
• Flow switch placed downstream each chiller
• Direct connection to chiller regulation (safety shutdown if insufficient
flow)
• Paddle of the flow switch need to be adjusted to piping diameter
• Adjust reactivity of flow switch

Check flow direction


same as
designed flow

Flow
Free movement of the paddle

‹#› Hydraulics & Chiller Sequencing


4) Wrap-UP
Best Practice – Pump Selection
• Some pumps have different speed settings
• It does not replace design calculations

pressure
efficiency

rpm

volume

‹#› Hydraulics & Chiller Sequencing


4) Wrap-UP
Best Practice – Pump Selection

Operating
System curve
point

Pressure
• What if the desired P1
operation point is
between two curves?
• Go below! Go to left! P2
– Lower first cost
– Lower operating cost
– Avoid over pumping

Q2 Q1 Water flow

‹#› Hydraulics & Chiller Sequencing


Thank you for your participation and interest.

The whole team is entirely at you disposal for further questions and remarks.

We hope that TRANE is a trusted partner for you, now and in the future.

‹#› Hydraulics & Chiller Sequencing


‹#› Hydraulics & Chiller Sequencing

Potrebbero piacerti anche