Switchgear
Objectives of
Protection
Minimize Maintain
Protect the
damage to system
public
equipment stability
Selectivity
Selectivity Reliability
Reliability Speed
Speed
Max service continuity Ability to function properly Minimize fault time to
with min system throughout its life prevent equipment
Simplicity
Sensitivity Economy
Simplicity& Economy
disconnection Reliability% = damage and maintain
Ability to detect the
(No. of Correct Trips/Max No. performance
desired with
system interconnection
smallest possible fault simplest
Trips + No. of incorrect Trips) xdesign
100 and at
condition min cost
Security
Security Dependability
Dependability
Ability to not trip when Ability to trip when it is
it is not expected to trip expected to trip
Security % = Dependability% =
(No. of Correct Trips/ (No. of Correct Trips/
Total No. of Trips) x 100 No. desired Trips) x 100
EPM581- Protection& Switchgear Prof. Hossam Talaat
Example on Reliability Calculations
5 The performance of an overcurrent relay was monitored
over a period of one year. It was found that the relay
operated 14 times, out of which 12 were correct trips. If the
relay failed to issue trip decision on 3 occasions, compute
dependability, security and reliability of the relay.
Solution
Trip Coil
CB
Battery
Relay
Contact Trip Circuit
CT
Relay Coil
Fall 2018
Title: Protection and Switchgear in EPS
Code: EPR 581 Credits: 3
Lectures: 3 hours/week Tutorials: 2
hours/week