Electrostatic Precipitators (ESP)

8.2 KVDC 4.1 KVDC

RYDAIR
Electronic Air Cleaner
EAC at AHU, Complete Assembly
Innovations in Green Buildings

Advanced Air Filtration System


Electrostatic Air Filters
• Particles sizes down to 0.01 micron
• Minimal clogging
• Low pressure drop
• Low maintenance cost
9f.) Air Purification & Available Sterilize Systems

Ultra Voilet Germicidal Irradiation ( UVGI )


or
UVc
UVc emitters for Self cleaning AHU/FCU coils.

•Restore old coil capacity to like new


•Eliminates manual coil cleaning
•Eliminates slime formations
•Save energy - Max heat transfer always
•Kill bacteria and odor.
Innovations in Green Buildings
DYNAMIC EDUCATIONAL GREEN DISPLAY

Interactive graphics display to show how the building fares


- energy usage
- water consumption etc.
Serves to encourage and create awareness of going green and to
educate the public on the importance of Green Building.
Dynamic Balancing Control Valve

3-in-1 design
• Pressure Independent Control
• Automatic balancing
• Commissioning

Save installation space


Save installation time
Save commissioning time
Eliminate error
Dynamic Balancing Control valve
• Fan coil application/AHU

• 2 in 1 design.
• (Automatic balancing and
control valve)
• Provide on/off or 0-10V
modulating control.
• Save installation time.
• Eliminate commissioning time.
• Ensure design performance
Innovations in Green Buildings
REGENERATIVE LIFTS
The power generated by lifts traction machines are dissipated as heat.
Regenerative Converter transmits the power back to the electrical
distribution system.

Normal mode
• heavy load up
• light load down

Regenerative mode
• heavy load down
• light load up
Auto-Tube Cleaning System
• Use of rubberized ball or brush to clean heat condenser
water tubes

14
Innovations in Green Buildings
Auto Condenser Tube Cleaning System
 Cleaning of condenser tube automatically
- eliminate manual cleaning

 Removes foulants on tubes even before they have


the chance to harden on heat transfer surface .
 Maintaining lower fouling factors
- maintain energy efficiency & savings
System Operation
1. Injection cycle

wonderball_newtemplate_20071212 16
System Operation
2. Collection cycle

wonderball_newtemplate_20071212 17
Automatic On-line Condenser Tube Cleaning System

wonderball_newtemplate_20071212 18
Strainer
Benefits
• Optimal heat transfer in the cooling system
• Reduce electricity consumption
• Reduce costly equipment downtimes
• Lessen the usage of chemical
• Extend tube life by removing corrosive deposits
• Eliminate high cleaning cost (mechanical & chemical) in tubes

wonderball_newtemplate_20071212 20
•Air and Dirt in Chilled Water
System
Innovations in Green Building
• Air and Dirt
• Separator in
Chilled
• Water System
Innovations in Green Building
• Air and Dirt
• Separator in Chilled
• Water System
Where to install – Air & Dirt Separator
compressor

Air & Dirt


Separator

evaporator air-cooled
condenser

expansion
Chilled Water Loop device
Airside Loop (CHWP, Piping & Refrigeration Loop
(AHU & Air Duct) Cooling Coil) (Air-cooled Chiller)
Innovations in Green Buildings

Vacuum Degasser in Chilled Water Piping System


Water Cooled Chiller System
Vacuum
Degasser control
valve

80°F
(26.7°C) 54°F 50°F 110°F 97°F
(12.2°C) (10°C) (43.3°C) (36.1°C)
condenser

44°F 41°F 100°F 87°F cooling


55°F tower
(12.8°C) (6.7°C) (5.0°C) (37.8°C) (30.6°C)

pump
Chilled Water Loop Refrigeration Loop Condenser Water Loop
Airside Loop (CHWP, Piping &
(AHU & Air Duct) (Water-cooled Chiller) (CWP, Piping & Cooling Tower)
Cooling Coil)
Where to install VD & ADS Best
Control
Valve Compressor Control
Valve

Filters
54°F 50°F 110°F 97°F
80°F
(12.2°C) (10°C) (43.3°C) (36.1°C
(26.7°C) )

Evaporator Condenser
AHU

Cooling
44°F 41°F 100°F 87°F tower
55°F
(12.8°C) (6.7°C) (5.0°C) (37.8°C) (30.6°C)

Expansion
Pump Valve Pump
Option
Airside Loop Chilled Water Loop Refrigeration Loop Condenser Water Loop
(AHU & Air Duct) (CHWP, Piping & (Water-cooled Chiller) (CWP, Piping & Cooling Tower)
Cooling Coil)
Vacuum Degasser – Where to install
• Installed on the return side of the chilled water system
where the pressure is more stable at that location as it’s at the
suction side of the pumps. This gives a more stable and
better working for the degasser.
•The vacuum degasser will work in any part in the
system, it is just best to have it at a location where
there is a large volume of water flowing, so the return
in a chilled water system is a good place to install a
degasser with respect to reduced condensation.
Auto Refrigerant Leakage Detection and Recovery System
Carbon Dioxide (CO2)
Sensors/Controllers

Wall Mount / Room Models for Duct Mount


Models Application
Typical Installation – AHU Room
Return Air

CO2 sensor AHU Room

Supply Air
AHU

Fresh Air

Fresh air damper

Damper Actuator
EE5 ADVANCE EE PERFORMANCE - BEI 15 POINTS
EE5 ADVANCE EE PERFORMANCE - BEI 15 POINTS

WHY use 10°F and how much above can we go?

• 10°F=2.4 Usgpm/RT
• 12°F=2.0 Usgpm/RT SAVES
• 14°F=1.7 Usgpm/RT ENERGY
Btuh= 500 x Q (Usgpm) x ∆T (deg F)
kWR= 4.187 x Q (l/s) x ∆T (deg F)
EE5 ADVANCE EE PERFORMANCE - BEI 15 POINTS
EE5 ADVANCE EE PERFORMANCE - BEI 15 POINTS

Cooling tower performance is dependent on the ambient


wet bulb, cooling tower approach and cooling water
range.
Chiller energy consumption can be reduced by:
• Reducing tower approach temperature
• Reducing cooling water range