AGENDA
● In this course you will learn the following
●Note about ION Setup .dcf files and ION Designer .fwn files
● You will need access to an ION meter or have the 8600 Offline Files available
on your laptop
● If you have a physical meter, you will need a serial or Ethernet cable to
connect to the meter
● Please download the ‘ION Setup User Guide’ and ‘ION Reference’ documents
● Test that it’s working through Windows security by running Offline meter display
● You are able to connect a 100BaseFX Multimode Fibre Ethernet cable with SC
connectors directly into the newer ION 7650s, and communicate all the
supported Ethernet protocols (ION, Modbus TCP, DNP3) to and from the meter.
● When you connect to the fibre Ethernet port, you aren’t able to connect to the
copper Ethernet port beside the fibre port on the ION 7650’s communication
card – only one (1) Ethernet port can be used on the meter at a time.
Security
● Security Mode – Standard with meter password, Advanced with user names and passwords
● Manitoba Hydro has Advanced Security on Revenue Locked meters
● Hardware Lock – Disabled for standard meters, Enabled for Revenue Sealed/Locked meters
Communications
● Serial Settings – COM1 to COM4, listed on the meter (careful not to change settings on the serial port you are
accessing)
● Network Settings
●IP address
●Gateway
●Enable SNMP
●MAC Address (for IT)
●Modbus Gateway (for downstream serial Modbus devices)
●DNS Primary/Secondary
●SMTP (Emails)
●NTP (Time Synchronization)
Demand
● Rolling Block Demand = Sliding Window Demand
● Manitoba Hydro standard is 3 sub-Intervals of 5 mins
● Industry standard is 1 sub-interval of 15 mins
Energy Pulsing
● Tabs of Pulsed values and End of Interval (EOI)
●Kt = pulse weight (how much of a value is needed before a pulse is generated
●Pulse Width = minimal time in seconds between pulses (in case PLC’s or IO Controllers read pulses at a
limited rate)
●Port = which digital output or LED will pulse
●Output mode = Pulse or KYZ
Expansion IO
● Additional Digital inputs and outputs – same settings as above
● Analog In
●Zero Scale, Full Scale, Port
● Analog Out
●Input (must be static value = KW, KVA, PF), Zero Scale, Full Scale, Port
● Converting from 0-20mA to 4-20mA on ION meters – refer to ‘Analog Outputs Program Guide’ for steps
● Load Profile
●Channels: This is the 1st data recorder which captures Revenue Data (in most cases) or Load Profile data
(KWh, KVARh)
●Interval / Depth: For configuring intervals between records (standard is 15mins), and the amount of records
stored in the meter before the earliest records get erased (FiFo)
●Event Log: How many events are stored in the meter, ensure EvPriority is above 0 to ensure the meter is
recording sag/swell information
Revenue
● PT / CT Correction: Enables or Disables Transformer Correction within the meter: Voltage inputs or Current
inputs – can be used to increase the accuracy of the entire meter system (meter + CT/PT accuracy)
●After running a CT / PT points test using a NIST traceable standard you can determine the precision and
accuracy of the CT/PT, once you have these values you can enter them into the meter so it compensates
● Transformer Loss
●Method Selection: enables or disables loss compensation, and determines which method of calculation for
compensation you want to use
●Test Sheet and %Loss Constants: refer to the ‘Transformer / Line Loss Calculations’ technical note
●Time of Use: to be used for revenue billing when the Utility decides to implement TOU billing structures
● Transients (if supported on meter): Transients can be detected by the ION 7650 or ION 8650A meter, the settings
of when and how the meter captures transient
Displays
● All the displays for the ION meters can be configured to show any type of value with variable granularity (within
limits) – with the exception of Revenue Sealed meters (ION 8650)
Verification
● Verification: Useful in the field when installing or rewiring a meter – ensures CT/PT inputs are connected
correctly (no negative / reversed values, no missing phases, etc..)
● Phasor Viewer under Wiring: Useful in the field when installing or rewiring a meter – ensures phases are
connected correctly (ABC)
Verification (cont)
● Using the Phasor Viewer or the Phasor_Tool.xml
● You can Invert the Polarity on non-sealed meters using the meter front panel or ION Setup in Advanced Mode
● In the ‘Power Meter Modules’ folder, in ‘Power Meter’ ION Module, select the Setup Registers tab
4. Click on ‘Edit’, ‘Properties’, select the Tools tab and change ‘Show Basic ION Setup’
to ‘Show Advanced ION Setup’
5. Alternatively you can hold shift down and click on the meter – much easier
6. Refer to ‘ION Reference’ for detailed information for each ION Module
Diagnostic Views
● Diagnostic View is a method for checking whether your Ethernet or Serial connection from the meter is reliable
● It can also show a measure of how loaded the meter’s onboard CPU is: up to 98% is safe, if it’s loaded more the
meter life might not be as long (standard is 10 years in the field)
Data View (Real Time and Historical view into the meter readings)
● All we’ve seen is the setup / configuration view of ION Setup, sometimes in the field you need to see
real time values or to go back into the meter’s onboard memory and look at the historical information
or waveform captures
*Meter Configuration Report Most of the settings / critical information of meter *.txt
Configuration Comparison Compares the *.txt report versus the current settings *.txt
highlights differences in red
Template Comparison Report Compares the stored *.dcf file versus the current *.txt
settings in the meter
MV-90 Report Revenue report used by Revenue Meter shop to MV-90xi1.5 file *.DAT
collect revenue data
*Data Collection Exports Log Data file into Excel format *.xml
2. Click on ‘Template’ settings, under the ‘Save to PC’ tab, click ‘Save’
3. Ensure you save the file with organization and proper naming convention
● AsFound_version_Date_SN_Location.dcf
● AsSent_version_Date_SN_Location.dcf
Note about ION Setup .dcf files and ION Designer .fwn files
● They are not compatible ION Designer can not load a *.dcf file and ION Setup can
not always load a complete *.fwn file.
● ION Designer can copy and move sections of Modules whereas ION Setup can only
copy the entire file.
Schneider Electric - Division - Name – Date 20
General Navigation around ION Setup
Configuration Comparison
Template Comparison
● Limitations to Measurement Canada Sealed meters (*ION 7700, ION 8600 and ION 8650)
● ION Device Template provides a list of ‘locked modules’ on Revenue Sealed meters
● Some changes can only be done with ION Setup or ION Designer and can not be done through
the meter front panel
Changing CT / PT ratios
4. Click Edit for FAC1 Owner, FAC1 Tag1, FAC1 Tag2 (Factory 1 settings Owner info, Meter Tag1
3. Click on Send, and select from a previously saved *.dcf file to load on the meter
● Firmware may be a mismatch but meter type must be the same (i.e. an ION 7700 framework will not
successfully load on to an ION 7650)
3. Click on Upgrade to choose the *.upg file with the latest firmware you wish to install on the
meter
● This will reset all recorded data on the device – you can export the existing data before performing an
update