Wye connected windings:
Have a common connection point
Have two voltages available “L-L & L-N”
Has only one current
Line current
Delta connected windings:
Have no common connection point
Have only one voltage available “L-L”
Delta can be closed “connected” in more than one way
Has two currents
Line current
Phase or winding current
Definitions
• Delta: Phase voltage is line voltage but phase
current is not line current.
– Line current ÷ √3= phase current
– Line voltage = Phase voltage
• Wye: Phase voltage is not line voltage but
phase current is line current.
– Line voltage ÷ √3= phase voltage
– Line current = phase current
HS Line 230 kV
LS Line 23 kV
Transformer 3 Ø 230/13280/23000 Gnd. Wye
25 MVA
230 kV
A B C
H1 H2 H3
W1
W2 W3
W4 W5
W6
X1 X2 X3
23 kV
a b c
HS Line 115 kV
LS Line 12 kV
Transformer:
3 3 Ø 115/12000/6928 Gnd. Wye 40MVA
A B C
H1 H2 H3
W
W
5
Transformer N 6
Ratio 16.6/1 X1 X2 X3
1925
a b c
LS Line 23 kV
Transformer
? MVA
A B C
H1 H2 H3
W2 W3
W5
W6
N
X1 X2 X3
1255
a b c
Typical GSU Transformer
Connection System
A
B C
H1 H2 H3
W6
W5 W4
W3 W2
W1
X1 X2 X3
a b c
Generator
Transformer Solutions
• Information: 230/23kV 25 MVA transformer
230 kV
• What is the voltage A-B, B-C, C-A ?
23 kV
• What is the voltage a-b, b-c, c-a?
• What is the voltage across W1, W2, W3? 230 kV (Same as the line for Δ winding)
• What is the voltage across W4, W5, W6? 13,280 kV ( L-N voltage)
• On the delta side of the transformer The line current ÷ √3 = Winding Current ;
62.76 ÷ √3 = 36.23
A B C
H1 H2 H3
W1 W2 W3
W4 W5 W6
N
Note: X1 X2 X3
W4 current/ W1 current = 627.56/36.3 = 17.3
627.56 amps X 13,280 volts = 8.3 MVA a b c
36.3 amps X 230,000 volts = 8.3 MVA
8.3 MVA X 3 (windings) =25 MVA
How Are They
Connected?
H H H H
primary H H
primary primary
secondary
secondary secondary
H H H H H H
A B C
H1 H2 H3
W1
W2 W3
W4 W5
W6
X1 X2 X3
a b c
Both transformers are Δ-Υ but A B C
notice the Δ windings are not H1 H2 H3
closed the same
W W W
1 2 3
W W
W
4 5
N 6
X1 X2 X3
A B C a b c
H1 H2 H3
W W W
1 2 3
W W
W
4 5
N 6
X1 X2 X3
a b c
Single Phase Transformer information:
HV 115 kV
LV 7200 V
Capacity 16,670 KVA
primary
Primary amps
16,670,000 ÷ 115,000 = 145 amps
Secondary amps
16,670,000 ÷ 7,200 = 2315 amps secondary