TYPICAL CONTROL / SUPERVISION

CIRCUITS

By
Y. k. Pandharipande.
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TYPICAL CONTROL PANEL LAY OUT (FRONT VIEW)
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TYPICAL CIRCUIT ARRANGEMENT / MIMIC
TYPICAL CONTROL / SUPERVISION
CIRCUITS
LOCAL/REMOTE CONTROL & PROTECTION TRIP CKT
TYPICAL CONTROL / SUPERVISION
CIRCUITS
ANTI-PUMPING CIRCUIT FOR BREAKER

APR – Anti-pumping Relay, PR – Protection Relay Contact


CS – C.B. Remote Control Switch, C/C, T/C – CB Close /Trip Coil
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TYPICAL CONTROL / SUPERVISION
CIRCUITS
METERING CIRCUITS (TYPICAL)
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TRIP CIRCUIT SUPERVISION

 “A” Coil provides post close supervision while A & B Coil


provide pre-close supervision.
 “C” Element is provided with delay on drop off to prevent
false alarms on mommentary dip in DC Voltage.
TYPICAL CONTROL / SUPERVISION
CIRCUITS
VT FUSE SUPERVISION

P – Protection Burden, M – Metering Burden


R – Fuse Failure relay
 Detects only secondary fuse failure.
 High Speed operation. Used to monitor VT supply to
Distance relay to block tripping & sound alarm on VT Fuse
Failure.
TYPICAL CONTROL / SUPERVISION
CIRCUITS
VT SUPERVISION USING VOLTAGE BALANCE SCHEME

 Relay operates on unbalance voltage detection.


 Monitors Prim. & Secondary fuses using 2 out of 2 logic.