Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1
FIRE SAFETY IN AUDITORIUM AND MULTIPLEX
2
WHAT IS AUDITORIUM?
• LOSS OF LIFE
2 Luxembourg 0.10(Max.)
• LOSS OF GOODWILL
3 Nigeria 21.13(Min.)
• ENVIRONMENT POLLUTION Ref. www. worldlifeexpectancy.com
5
FIRE
2) Life Safety — Covering life safety provisions in the event of fire and
similar emergencies, also
addressing construction and occupancy features that are necessary to
minimize danger to life from
fire, smoke, fumes or panic.
7
OBJECTS OF FIRE FIGHTING AND FIRE SAFETY
8
LIFE SAFETY
Raising Alarm
Smoke Management
9
PROBLEMS IN AUDITORIUM AND MULTIPLEX
10
FIRE RISK MANAGEMENT
1. Incipient
2. Growth
3. Fully Developed
4. Decay
Ref. www.journeytofirefighter.com
12
1. Incipient
15
4. Decay
16
Four ways to put out a fire
2. Exclude oxygen
17
ACCIDENT PREVENTION
• Safety Audits
• Routine Safety Inspection
• Safe Working Practices
• Performance Assessment
• Interaction
• Education and Training
• Following Safety Standards.
18
ABSOLUTE SAFETY FROM FIRE IS NOT ATTAINABLE IN PRACTICE
• The objective of this part is to specify measures that will provide that degree of
safety from fire which can be reasonably achieved.
20
SMOKE MANAGEMENT
• SELECTION OF MATERIALS
• SMOKE VENTING
• SMOKE BARRIERS
• SMOKE EXTRACTION SYSTEM
• POSITIVE PRESSURE VENTING
21
Smoke Venting
Smoke venting facilities for safe use of exits in windowless buildings,assembly buildings
(including cinema halls) shall be automatic in action with manual controls in
addition.(clause 3.4.12.1)
Natural draft smoke venting shall utilize roof vents or vents in walls at or near the ceiling
level; such vents shall be normally open, or, if closed, shall be designed for automatic
opening in case of fire, by release of smoke sensitive devices.(clause 3.4.12.2)
The discharge apertures of all natural draft smoke vents shall be so arranged as to be
readily accessible for opening by fire service personnel.(clause 3.4.12.4)
23
FIRE PROTECTION (Components)
25
Automatic Sprinkler System
26
Emergency and Escape Lighting
Escape lighting shall be capable of:
28
Arrangement of Exits
• Exits shall be so located that the travel distance on the floor shall not exceed the
distance 30 m. (Table 22 ,clause 4.5.1)
• The travel distance to an exit from the dead end of a corridor shall not exceed half the
distance 30 m, except in assembly and institutional occupancies in which case it
shall not exceed 6 m.(Table 22 ,clause 4.5.2)
Every place of assembly of sub-division D-2, shall have at least two separate exits
as remote from each other as practicable and if of capacity over 600 at least three
exits shall be provided with each exit not less than of 2 000 mm width.
29
Standard Criteria for Doorway Exits
• Exit doorways shall open outwards, that is, away from the room, but shall not
obstruct the travel along any exit. No door, when opened, shall reduce the
required width of stairway or landing to less than 900 mm; overhead or sliding
doors.(clause 4.7.3)
30
Standard Criteria for Ramps
Ramps shall comply with all the applicable requirements for stairways
regarding enclosure, capacity and limiting dimensions except where specified
in 6.1 to 6.9 for special uses and occupancies.(clause 4.14.1)
The slope of a ramp shall not exceed 1 in 10.In certain cases steeper slopes
may be permitted but in no case greater than 1 in 8.(clause 4.14.2)
For all slopes exceeding 1 in 10 and wherever the use is such as to involve
danger of slipping, the ramp shall be surfaced with approved non-slipping
material.(clause 4.14.3)
31
Standard Criteria for Corridors and Pessageways
• Exit corridors and passageways shall be of width not less than the aggregate
required width of exit doorways leading from them in the direction of travel to the
exterior.(clause 4.8.1)
• All means of exit including staircases lifts lobbies and corridors shall be adequately
ventilated.(clause 4.8.3)
32
Note for Travel distance
33
TO CONCLUDE -- Why NBC shall be a dynamic Document ?
Fire Authorities
• Police Authorities
• Loss Prevention Authorities
• Insurance Authorities etc..
And each one of them look at the fire from different angles.
Every fire leaves a signature behind, leaves a trail, leaves a tell tale evidence of what
happened.
The authorities shall strive to update the respective documents from the experience
obtained from the fire behaviour in each occurrence.
Let me explain certain instances in the next slide ………….. 34
Uphaar Cinema fire Incident
35
Uphaar Cinema fire Incident
36
On that day in the morning repairing of
transformers was done. But due to unsatisfactorily
working and improper inspection connection
between wires of transformers could not occur
properly. After that at 6:55 pm due to sparkling
between wires at connection occurred and
incipient stage of fire took place.
38
Total 59 people lost their
life and 103 people had
got non-fetal injury.
Small mischiefs can
create this much big loss
of life.
Ref. www.thehindu.com
We can understand that how much fire safety is important in auditorium and in
other buildings.
39
THANK YOU
&
STAY SAFE FROM
FIRE
40