Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
college of engineering
electrical & electronic department
Design Of Electrical Power Systems Equipment's
lec 4
Design of Earthing System
Earthing :-
“Earthing means an electrical connection to the general mass of earth to
provide safe passage to fault current to enable to operate protective
devices and provide safety to personnel and Equipment's.”
Types of Earthing:-
1. System Earthing
This is primarily concerned with the protection of Electrical equipment
by stabilizing the voltage with respect to ground (Connection between
part of plant in an operating system like LV neutral of a Power
Transformer winding and earth).
2. Equipment Earthing (Safety grouding)
3. lightning/surge grounding
A good earthing system is required for:
· protection of buildings and installations against lightning
· safety of human and animal life by limiting touch and
step voltages to safe values.
· electromagnetic compatibility (EMC) i.e. limitation of
electromagnetic disturbances.
· correct operation of the electricity supply network and to
ensure good power quality.
There are four value for earthing resistance:
1. Earthing resistance for the lightning protection system shall not
exceed 5 OHM.
2. Earthing resistance for the power system earthing in power station
and power plants shall not exceed 5 OHM.
3. Earthing resistance for the electrical earthing (equipment earthing)
shall not exceed 4 OHM
4. Earthing resistance for the electronic devices instrumentations shall
not exceed 1 OHM.
Terms & Definitions
Step Potential is the difference in the voltage between two points which are
one meter apart along the earth when ground currents flowing.
Touch Potential is the difference in voltage between the object touched and
the ground point just below the person touching the object when ground
Clamp
Test link
Rod(Earthing electrode)
Rod coupler
Factors on which design of earth grid depends
Materials used for earth electrodes and conductors must be
chosen carefully taking into account physical, chemical and
economical constraints. Ground conductor must be adequate for
fault current (considering corrosion).
Conductor sizing depends on fault current and conductivity as
well as mechanical strength of material used.
Resistivity of soil and surface layer determines the STEP and
TOUCH potentials, which determine safe values of operation .
A good grounding system provides a low resistance in order to
A single line to ground fault is more common and causes more fault
zero. Then
Recommended values of earth resistance
Step and touch voltage criteria
shock energy from being absorbed before the fault is cleared and the
circuit should not exceed the limits defined as follows. For step voltage
the limit is