Sei sulla pagina 1di 40

Protection, metering, and monitoring functions for generators.

Presented by:

m syukur siregar
Overview
Theory
Wiring
Security

2
3
4
What a Generator looks like
6
Overview

7
 Existing generator and transformer protection (more than 5
years or non-digital) may:
◦ Cause protection security issues
 Tripping on through-faults, external faults, swings, load encroachment
and energizing
◦ May lack comprehensive monitoring and communications
capabilities
 Not provide valuable forensic info that can lead to rapid restoration
◦ Not be up to ANSI/IEEE Standards!
 Insurance, Asset Reliability and Personal Liability Issues
 C37-102: Guide for the Protection of Synchronous Generators
 C37.91: Guide for Transformer Protection

8
Generator Management Relay
Product Overview
• Ideal Protection for Induction and
Synchronous Generators at 25, 50
and 60Hz
• Complete Generator Protection
including:
 Generator Stator Differential
 2 or 3 Zone Distance Backup
 100% Stator Ground
• High speed sampling, 12 samples per
cycle
• Drawout Case Installation
• Powerful Fault Recording: Waveform,
Sequence of Events
• Ethernet and Serial Communications
• Metering of all important parameters

9
Theory

10
11
System
Ground
Stator
Ground
Exciter
The
"Wild"
G Power
System

Stator
Phase
System
Phase

 Internal and External Short Circuits


12
◦ Abnormal Operating Conditions
 Loss of Synchronism
 Abnormal Frequency
 Overexcitation
 Field Loss
 Inadvertent Energizing
 Breaker Failure
 Loss of Prime Mover Power
 Blown VT Fuses
 Open Circuits

13
Overexcitation
Over Open
Power Loss of Field
Loss of Field Circuits
Overexcitation
Overexcitation

Exciter
The
"Wild"
G Power
System
Abnormal
Inadvertent Frequency
Abnormal Energizing,
Frequency Pole Flashover
Loss of
Reverse Breaker Synchronism
Power Failure

 Abnormal Operating Conditions


14
◦ Conducted in early ’90s, showed many areas of protection
lacking

◦ Unwillingness to upgrade:
 Lack of expertise
 To recognize deficiency
 To perform the work
 “Generators don’t trip” (wrong)
 Operating procedures will save the day

PSRC = Power System Relay Committee

15
 Latest developments reflected in:
◦ Std. 242: Buff Book
◦ C37.102: IEEE Guide for Generator Protection
◦ C37.101: IEEE Guide for AC Generator Ground
Protection
◦ C37.106: IEEE Guide for Abnormal Frequency
Protection for Power Generating Plants

These are created/maintained by the IEEE PSRC & IAS


They are updated every 5 years
16
32 Reverse Power
40 Loss of Excitation
51V voltage restraint
51G Ground overcurrent
87 Differential

 Small – up to 1 MW to 600V, 500 kVA if >600V


17
32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
51V voltage restraint
51G Ground overcurrent
87 Differential

 Medium – up to 12.5 MW
18
32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
49 Thermal Overload
51V voltage restraint
51G Ground overcurrent
64 Ground Relay
87 Differential

 Large – up to 50 MW
19
 Unit
Connected,
 High Z
Grounded

32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
49 Thermal Overload
51V voltage restraint
51G Ground overcurrent
64 Ground Relay
87 Differential

20
21
Protection Functions
Protection Functions Include:
• Generator Stator Differential
• Backup Distance Protection
• 100% Stator Ground
• Generator Unbalance
• Loss of Excitation
• Accidental Energization
• Breaker Fail
• Phase Overcurrent – Voltage Restraint
• Neutral Inst. / Timed Overcurrent
• Neg. Sequence Overcurrent
• Under / Over Voltage
• Under / Over Frequency
• Generator Thermal Model
• RTD Temperature
• Overexcitation – Volts/Hertz

22
23
24
25
26
 Reverse Power (32)
 Should be sensitive to 0.05 pu to properly detect motoring in large steam
turbines
 Existing E/M and Static relays not sensitive enough
 May cause shutdown difficulties
 Negative Sequence (46)
 Should be sensitive to low values to detect open poles/conductors on system
after GSU
 Existing E/M and Static relays not sensitive enough
 Long time low level events may cause excessive rotor heating, thermal tripping
and damage rotor
 100% Stator Ground (59N / 59D)
 Protects all of the stator winding
 Existing schemes typically only see 90%
 Stop low level fault near neutral from degrading into a high level fault and causing large
amounts of damage
 Very secure

27
 Inadvertent Energizing (50/27)

◦ High speed tripping of unit after breaker accidentally closed


on dead machine, also pole flashover prior to syncing
 Most existing schemes do not incorporate
◦ Many schemes fail due to complexity (reliance on breaker
auxiliary switches, yard distance relays, etc.
◦ If breaker is not tripped rapidly, mechanical and electric
damage can occur to machine in fractions of a second!
◦ Pole flashovers must be cleared by high speed breaker
failure, as the breaker is open!

28
29
30
Protection Functions
Generator Stator Differential
• Stator Phase Differential
• Dual Slope Percent Restraint Operating
Characteristic
• Directional Supervision under saturation
conditions

Distance Backup Protection Dual Slope Phase Differential


• 2 or 3 Zone Mho Distance Protection
• Backup for primary line protection
• Configurable Reach and Angle Distance
Characteristic

100% Stator Ground Protection


• 95% Fundamental OverVoltage
• 15% Third Harmonic UnderVoltage
Two Zone Distance Backup

31
Protection Functions
Voltage Protection
• Phase Overvoltage
• Phase Undervoltage
• Neutral Overvoltage (fundamental)
• Neutral Undervoltage (3rd Harmonic)
• Voltage Phase Reversal
Voltage Restraint Overcurrent
Current Protection
• Phase, Ground and Negative Sequence
Overcurrent Tripping
• IEC, ANSI , IAC and Customizable
Overcurrent Curves
• Voltage Restraint increasing sensitivity under
low voltage conditions

Frequency Protection
• Overfrequency
• Underfrequency Undervoltage Trip Curves

32
Protection Functions
Thermal Protection
• Generator Thermal Model
• RTD Alarming and Tripping
• RTD Biased Thermal Model

Inadvertent Energization
• Prevents Accidentally Closing a Stopped
Generator onto a Live Line
• Armed when Generator is Offline and Voltage is
Thermal Model – Voltage
below a pre-set level Dependant Overload Curves

Loss of Excitation (show Training CD)


• Uses Impedance Circle for loss of excitation
detection
• 2 Zones for fault detection and control

Volt/Hertz (Overexcitation)
• Detects changes in the Volts/Hertz ratio of the
generator or associated transformer Loss of Excitation

33
Wiring

34
35
36
37
38
39
Enhanced Security
Prevents Unauthorized Access and Provide Traceability

Security Audit Trail • Date/time


security report
was generated
• Date and time of hardware,
firmware or setting changes to • Description of
the GE Multilin
your relays Relay
• Summary of the
• Logging of the MAC address of last time the
computers and users making configuration
settings changes was changed

• Track method of how settings • History of last 10


changes were made (i.e. keypad, occurrences the
configuration
serial port, ethernet) was changed

Security strategy – conforms to industry and regulated guidelines

40

Potrebbero piacerti anche