Sei sulla pagina 1di 19

POWER SYSTEM ANALYSIS

Transformers, Per Unit Calculations


Per Unit Calculations

 A key problem in analyzing power systems is the


large number of transformers.
– It would be very difficult to continually have to refer
impedances to the different sides of the transformers
 This problem is avoided by a normalization of all
variables.
 This normalization is known as per unit analysis.

actual quantity
quantity in per unit 
base value of quantity

1
Per Unit Conversion Procedure, 1f

1. Pick a 1f VA base for the entire system, SB


2. Pick a voltage base for each different voltage level,
VB. Voltage bases are related by transformer turns
ratios. Voltages are line to neutral.
3. Calculate the impedance base, ZB= (VB)2/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unit
Note, per unit conversion on affects magnitudes, not
the angles. Also, per unit quantities no longer have
units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)
2
Per Unit Solution Procedure

1. Convert to per unit (p.u.) (many problems are


already in per unit)
2. Solve
3. Convert back to actual as necessary

3
Per Unit Example
Solve for the current, load voltage and load power
in the circuit shown below using per unit analysis
with an SB of 100 MVA, and voltage bases of
8 kV, 80 kV and 16 kV.

Original Circuit
4
Per Unit Example, cont’d

8kV 2
Z BLeft   0.64
100 MVA
80kV 2
Z BMiddle   64
100 MVA
2
16kV
Z BRight   2.56
100 MVA

Same circuit, with


values expressed
in per unit.
5
Per Unit Example, cont’d

1.00
I   0.22  30.8 p.u. (not amps)
3.91  j 2.327
VL  1.00  0.22  30.8  
    p.u.
2
VL
SL  
VL I L*  0.189 p.u.
Z
SG  1.00  0.2230.8  30.8p.u.
6
Per Unit Example, cont’d

To convert back to actual values just multiply the


per unit values by their per unit base

VLActual
 0.859  30.8  16 kV  13.7  30.8 kV
S LActual  0.1890  100 MVA  18.90 MVA
SGActual  0.2230.8  100 MVA  22.030.8 MVA
100 MVA
I Middle
B   1250 Amps
80 kV
Middle  0.22  30.8  Amps  275  30.8
I Actual
7
Three Phase Per Unit

Procedure is very similar to 1f except we use a 3f


VA base, and use line to line voltage bases
1. Pick a 3f VA base for the entire system, S B3f
2. Pick a voltage base for each different voltage
level, VB. Voltages are line to line.
3. Calculate the impedance base
VB2, LL ( 3 VB , LN ) 2 VB2, LN
ZB   
S B3f 3S 1Bf S 1Bf
Exactly the same impedance bases as with single phase!
8
Three Phase Per Unit, cont'd

4. Calculate the current base, IB

S B3f 3 S 1Bf S 1Bf


I3Bf     I1Bf
3 VB , LL 3 3 VB , LN VB , LN

Exactly the same current bases as with single phase!

5. Convert actual values to per unit

9
Three Phase Per Unit Example

Solve for the current, load voltage and load power


in the previous circuit, assuming a 3f power base of
300 MVA, and line to line voltage bases of 13.8 kV,
138 kV and 27.6 kV (square root of 3 larger than the
1f example voltages). Also assume the generator is
Y-connected so its line to line voltage is 13.8 kV.
Convert to per unit
as before. Note the
system is exactly the
same!

10
3f Per Unit Example, cont'd

1.00
I   0.22  30.8 p.u. (not amps)
3.91  j 2.327
VL  1.00  0.22  30.8  
    p.u.
2
VL
SL   *
VL I L  0.189 p.u.
Z
SG  1.00  0.2230.8  30.8p.u.

Again, analysis is exactly the same!


11
3f Per Unit Example, cont'd

Differences appear when we convert back to actual values


VLActual
 0.859  30.8  27.6 kV  23.8  30.8 kV
S LActual  0.1890  300 MVA  56.70 MVA
SGActual  0.2230.8  300 MVA  66.030.8 MVA
300 MVA
I Middle
B   1250 Amps (same current!)
3 138 kV
Middle  0.22  30.8   Amps  275  30.8
I Actual

12
3f Per Unit Example 2

Assume a 3f load of 100+j50 MVA with VLL of 69 kV


is connected to a source through the below network:

What is the supply current and complex power?

Answer: I=467 amps, S = 103.3 + j76.0 MVA 13


Per Unit Change of MVA Base

 Parameters for equipment are often given using


power rating of equipment as the MVA base
 To analyze a system all per unit data must be on a
common power base
Z OriginalBase
pu  Z actual  Z NewBase
pu
2 2
Vbase Vbase
Hence ZOriginalBase
pu  OriginalBase
/ NewBase
 Z pu
NewBase
S Base S Base
NewBase
S Base
ZOriginalBase
pu  OriginalBase
 Z pu
NewBase
S Base
14
Per Unit Change of Base Example

A 54 MVA transformer has a leakage reactance or


3.69%. What is the reactance on a 100 MVA base?
100
X e  0.0369   0.0683 p.u.
54

15
Transformer Reactance

 Transformer reactance is often specified as a


percentage, say 10%. This is a per unit value
(divide by 100) on the power base of the
transformer.
 Example: A 350 MVA, 230/20 kV transformer has
leakage reactance of 10%. What is p.u. value on
100 MVA base? What is value in ohms (230 kV)?
100
X e  0.10   0.0286 p.u.
350
2
230
0.0286   15.1 
100 16
Distribution Transformer

LTC
Radiators
W/Fans
115 – 35 kV distribution transformer
Source: Tom Ernst, Minnesota Power 17
230/115 kV Transformer

230 kV surge 115 kV surge


arrestors arrestors

Oil Cooler
Oil
Radiators
pump
W/Fans
Source: Tom Ernst, Minnesota Power 18

Potrebbero piacerti anche