Methods of Installation of Cables
Installation Method Installation Method Appropriate
Reference for
determining
Number Description
Current-carrying
Capacity
Open and Clipped Direct
In Conduit
Sheathed single
core cables in
free air (any
supporting metal
work under the
12 cables occupying Reference to Table
less than 10% of
the plan area) :
2 or 3 cables
vertically one
above the other,
distance between
cables equal to
the overall
diameter (De);
distance from the
wall not less than
0.5 (De)
Methods of Installation of Cables
Installation Method Installation Method Appropriate
Reference for
determining
Number Description
Current-carrying
Capacity
In Free Air
Sheathed
Multicores cables
in free air
distance between
wall and cable
13 surface not less Reference to Table
than 0.3 De (any
supporting
metalwork
occupying less
than 10% of the
plan area)
Cu and Al Equivalent Size Comparison
Cu. Equivalent
Nom. Cross Nom. Cross
Conductor Voltage Drop Voltage Drop Current Rating
Sectional Area Sectional
Current Cu. Conductor Al. Conductor of Al.
for Cu. Area for Al.
Rating Conductor
Equivalent
Nom. Cross Nom. Cross
Cu. Conductor Voltage Drop Voltage Drop Current Rating
Sectional Area Sectional
Current Rating Cu. Conductor Al. Conductor of Al.
for Cu. Area for Al.
Conductor
Equivalent
Nom. Cross Nom. Cross
Cu. Conductor Voltage Drop Voltage Drop Current Rating
Sectional Area Sectional
Current Rating Cu. Conductor Al. Conductor of Al.
for Cu. Area for Al.
Conductor
The continuos current carrying capacities are based on the following condition :
a) Ambient temperature 30 deg.C
b) Maximum continuos loading temperature of conductor 90 deg.C
c) Clipped direct 3 or 4 cable, 3 phase a.c
Current-carrying Capacity for Single Core
Copper Conductor, Non-armoured or without
Sheath to BS6004 & BS6346
Current Carrying Capacity
Method of Installation
mm2 (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
1.25 13 12 16 14 19 17 - - - - -
2.5 19.5 18 24 21 27 25 - - - - -
4 26 24 32 28 37 33 - - - - -
6 34 31 41 36 47 43 - - - - -
10 46 42 57 50 65 59 - - - - -
16 61 56 76 68 87 79 - - - - -
50 119 108 151 134 182 167 191 172 219 197 167
70 151 136 192 171 234 214 246 223 281 254 216
Current-carrying Capacity for Single Core
Copper Conductor, Non-armoured or without
Sheath to BS6004 & BS6346
Current Carrying Capacity
Method of Installation
In Free Air
Enclosed in
Enclosed in On a Perforated
Conduit in
Conduit on Cable Tray Vertical
Conductor Thermally Clipped Direct
Wall or Horizontal or Horizontal Flat Trefoil
Cross Insulated Spaced
Trunking etc. Vertical Spaced
Sectional Wall etc.
Area
2 3 or 4 3 or 4 2 cables,
2 cables,
cables 2 cables, cables, 2 cables, cables, single
3 or 4 2 cables, 3 or 4 single phase 3 cables,
, single three single three phase a.c
cables, single cables, a.c or d.c or trefoil
single phase a.c phase a.c phase a.c phase a.c or d.c or 3
three phase a.c three 3 cables three
phase or d.c flat flat & or d.c flat flat & cables
phase or d.c phase three phase phase a.c
a.c or touching touching touching touching three
a.c
d.c @ trefoil @ trefoil phase a.c
mm2 (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
95 182 164 232 207 284 261 300 273 341 311 264
120 210 188 269 239 330 303 349 318 396 362 308
150 240 216 300 262 381 349 404 369 456 419 356
185 273 245 341 296 436 400 463 424 521 480 409
240 320 286 400 346 515 472 549 504 615 569 485
300 367 328 458 394 594 545 635 584 709 659 561
400 - - 546 467 694 634 732 679 852 795 656
500 - - 626 533 792 723 835 778 982 920 749
630 - - 720 611 904 826 953 892 1138 1070 855
On a Perforated Cable
2 cables, single 2 cables, single 3 or 4 cables, three
Clipped Direct Tray Horizontal or
phase a.c phase d.c phase a.c
Vertical
Conductor
Cross
Sectional
Area 2 cables, 3 or 4 2 cables, 3 or 4
single phase cables, single phase cables, Vertical Horizont Vertical Horizon Vertical
Horizontal 3 cables
a.c or d.c three phase a.c or d.c three phase Flat al Flat tal Flat
Spaced Trefoil
flat & a.c, flat & flat & a.c, flat & Spaced Spaced Spaced Spaced Spaced
touching touching touching touching
mm2 (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
50 193 179 205 189 229 217 229 216 230 212 181
70 245 225 259 238 287 272 294 279 286 263 231
95 296 269 313 285 349 332 357 340 338 313 280
120 342 309 360 327 401 383 415 396 385 357 324
150 395 354 413 373 456 436 479 461 438 407 373
185 447 399 469 422 511 489 548 525 490 456 425
240 525 465 550 492 593 568 648 622 566 528 501
300 594 515 624 547 668 640 748 719 616 578 567
400 687 575 723 618 737 707 885 851 674 632 657
500 763 622 805 673 810 777 1035 997 721 676 731
630 843 669 891 728 893 856 1218 1174 771 723 809
800 919 710 976 777 943 905 1441 1390 824 772 866
1000 975 737 1041 808 1008 967 1685 1627 872 816 945
Current-carrying Capacity for Multicore
Copper Conductor, Armoured to BS6346
Current-Carrying Capacity
Method of Installation (in free air)
On a Perforated Cable Tray
Conductor Cross Clipped Direct
Horizontal or Vertical or in free air
Sectional Area 1 three-core cable 1 three-core cable
1 two-cores cable, 1 two-cores cable,
or four-core or four-core
single phase a.c or single phase a.c or
cable, three cable, three
d.c d.c
phase a.c phase a.c
mm2 (A) (A) (A) (A)
1.5 21 18 22 19
2.5 28 25 31 26
4 38 33 41 35
6 49 42 53 45
10 67 58 72 62
16 89 77 97 83
25 118 102 128 110
35 145 125 157 135
50 175 151 190 163
70 222 192 241 207
95 269 231 291 251
120 310 267 336 290
150 356 306 386 332
185 405 348 439 378
240 476 409 516 445
300 547 469 592 410
400 621 540 683 590
Current-carrying Capacity for Aluminum
Conductor
Continuous Current Rating (Unit Amperes)
In Air at 40oC On Ground at 25oC Short
Circuit
Nominal
Single Three or Current
Sectional Single Three or
2
Area (mm ) Conductor 3 Twin Conductor Twin Four Rating
Four
Conductor 3 cables Conductor Conduct for 1
cables S=2d Conductors sec.
S=2d ors
4 - 29 24 - 38 32 305A
6 - 36 31 - 47 41 405
10 - 49 41 - 63 53 760
16 - 66 55 - 82 69 1.22 kA
25 - 86 72 - 105 89 1.9
35 - 105 90 - 130 105 2.66
50 150 125 105 150 150 125 3.8
70 185 170 140 185 190 155 5.32
95 220 205 165 215 225 185 7.22
120 265 230 195 250 260 215 9.12
150 285 270 235 280 285 240 11.4
185 350 305 255 320 325 270 14.1
240 405 360 295 365 380 320 18.2
300 460 420 355 420 430 355 22.8
400 570 - - 495 - - 25.8
500 650 - - 550 - - 32.6
630 750 - - 640 - - 40.8
800 890 - - 725 - - 50.3
1000 1015 - - 815 - - 65.3
Single conductor : Single point
bonded
Short Circuit Ratings
Short Circuit Rating (A) Copper Conductor Aluminum Conductor
Depth of Laying
600/1000V Cables
(meter)
Up to 50 mm2 70 mm2 to 300 mm2 Above 300 mm2