Sei sulla pagina 1di 11

ABB Switzerland Ltd - 1

2002 ABB. All rights reserved.

SMS/SCS Configuration
REB500

ABB
Content

Introduction/ Supported protocols


Example of Addressing
What can be visualised
2002 ABB. All rights reserved.
ABB Switzerland Ltd - 2

ABB
ABB Switzerland Ltd - 3
2002 ABB. All rights reserved.


LON
IEC 60870-5-103
Todays Supported IBB Protocols

ABB
Example of IEC addressing

Control
IEC 103 station address(on link layer) system

Entered via tool


IEC 60870-5-103

150 151 152 153 154 155


RET.... REB500 REL... REL.... REL.... REL....
CU

CAA MVB

1 2 59
BU 1 BU 2 BU BU 59
Common address of ASDU (CAA)
Bay 1 Bay 2 Bay Bay 59
Generated automatically in tool <6.10
2002 ABB. All rights reserved.

Selectable version 6.10 onwards


ABB Switzerland Ltd - 4

ABB
Example of LON addressing

Control
LON station address(Unit Address) system

Entered via tool


LON

50 51 52 53 54 55
RET.... REB500 REL... REL.... REL.... REL....
CU

MVB

BU 1 BU 2 BU BU 59

Bay 1 Bay 2 Bay Bay 59


2002 ABB. All rights reserved.
ABB Switzerland Ltd - 5

ABB
Example of IEC/LON addressing; HMI500 <6.10

Station address must be active for one protocol


2002 ABB. All rights reserved.
ABB Switzerland Ltd - 6

ABB
Example of IEC/LON addressing; HMI500 6.10
Station address must be active for one protocol
2002 ABB. All rights reserved.
ABB Switzerland Ltd - 7

Common address of ASDU (CAA) selectable ABB


ABB Switzerland Ltd - 8
2002 ABB. All rights reserved.

Example Exporting signals LON address-list

ABB
Example Exporting signals LON address-list
Module;Type of IBB;Station Addr.;REBWIN Version;REBCON Version;DB Version;DB Date;Export Date;Export Tool Version
REB500;LON; 1 ;5.00;5.00;V1.00 ;2001-10-23;02-01-25 ;AI 01-02-28 V5.00.01
Station Name;Bay Name;Device Name;4. Field;5. Field;Signal Name;Technical Signal Identifier;Event Text;Sign...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;11765_General Start ;11765...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;13740_Start BFP L1L2...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;16705_Start DR_1;16705_St...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;21110_TRIP;21110_TRIP; ...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;21805_In service;21805_In ser..
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;23105_BFP TRIP;23105_BF.
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;23110_BFP_REMOTE_TRI..
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;11765_General Start ;1.
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;13740_Start BFP L1L2;1.
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;16705_Start DR_1;16705_..
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;21110_TRIP;21110_TRI.
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;21805_In service;21805 .
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;23105_BFP TRIP;2310..
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;23110_BFP_REMOTE_..
CHA KWO LING ROAD 132KV;BBP1;11;;;EVENT;+R02+U14-F391.11 1 T500BU02_1;11765_General Sta...
...
2002 ABB. All rights reserved.
ABB Switzerland Ltd - 9

ABB
Example Contents IEC address-list DRR signals
Common ABB Bay Bay Name Stations Signal Signal
Address Name Number ID Text
ADSU ; ; ; ;
0; =ABB00; - ; Null; Null; Null
1; =ABB01; FUTURE CABLE; 1 ; 1 ; 21110_TRIP
1; =ABB01; FUTURE CABLE; 1 ; 2 ; 23105_BFP TRIP
1; =ABB01; FUTURE CABLE; 1 ; 3 ; 23110_BFP_REMOTE_TRI
1; =ABB01; FUTURE CABLE; 1 ; 4 ; 13740_Start BFP L1L2
1; =ABB01; FUTURE CABLE; 1 ; 5 ; 13745_Start BFP L1L2
1; =ABB01; FUTURE CABLE; 1 ; 6 ; 11765_General Start
10; =ABB10; FUTURE CABLE; 10 ; 1 ; 13740_Start BFP L1L2
10; =ABB10; FUTURE CABLE; 10 ; 2 ; 13745_Start BFP L1L2
10; =ABB10; FUTURE CABLE; 10 ; 3 ; 21110_TRIP
10; =ABB10; FUTURE CABLE; 10 ; 4 ; 23105_BFP TRIP
10; =ABB10; FUTURE CABLE; 10 ; 5 ; 23110_BFP_REMOTE_TRI
10; =ABB10; FUTURE CABLE; 10 ; 6 ; 11765_General Start
2; =ABB02; TRANSFORMER1; 2 ; 1 ; 13740_Start BFP L1L2
2; =ABB02; TRANSFORMER1; 2 ; 2 ; 13745_Start BFP L1L2
2; =ABB02; TRANSFORMER1; 2 ; 3 ; 21110_TRIP
2; =ABB02; TRANSFORMER1; 2 ; 4 ; 23105_BFP TRIP
2; =ABB02; TRANSFORMER1; 2 ; 5 ; 23110_BFP_REMOTE_TRIP
2002 ABB. All rights reserved.
ABB Switzerland Ltd - 10

ABB
What can be visualised LON/IEC
LON IBB protocol:
Time synchronisation
Binary events (signals,trips and diagnostics)
Trip Reset command
Differential current of each protection zone
Disturbance recording data transfer (BU03 only)
IEC 60870-5-103 protocol
Time synchronisation
Subset of binary events as specified in IEC
Trip Reset command
2002 ABB. All rights reserved.

Disturbance recording data transfer


ABB Switzerland Ltd - 11

Differential current of each protection zone (generic part)


All other binary events (generic part)

ABB