Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Fig. 4: CT connection
1
CURRENT TRANSFORMER (CT)
A CT operates with its secondary under
nearly short circuit conditions.
The secondary circuit is connected to
ground in may cases.
Role of CT is important in protection and
measurement. Accuracy in current
conversion is very much important
2
CURRENT TRANSFORMER (CT)
When CT saturates, large current errors
may result.
Digital relays, on the other hand, permit a
relatively severe degree of saturation as the
integrated saturation detector avoids
incorrect operation.
During normal operation, the flux density in
CT is small compared to its saturation
induction.
3
CURRENT TRANSFORMER (CT)
The induction increases proportional to
primary current and correspondingly the
voltage across secondary burden.
CT is generally dimensioned such that a
certain AC fault current can be transformed
without saturation. DC component of fault
current also affects operation of CT.
The simplified equivalent circuit of CT is
shown in Fig. 5.
4
CURRENT TRANSFORMER (CT)
6
CURRENT TRANSFORMER (CT)
Standard Specifications of CT:
Primary rated current
Transformation ratio
Rated knee point voltage (Fig. 6)
Magnetizing current at the rated knee point
voltage
Resistance of the secondary winding
7
CURRENT TRANSFORMER (CT)
The knee point voltage is defined by the
point on the magnetizing curve at which a
10% increase in the voltage corresponds to
50% increase in magnetizing current.
8
Fig. 6: CT magnetization characteristics
TRANSIENT RESPONSE OF CT
The induction of the CT is proportional to the
integral of the secondary voltage across the
magnetizing inductance. Thus, it is
proportional to the area below the
secondary fault current.
The DC component of the fault current
therefore results in single-sided severe
transient magnetization of CT which is
several times larger than AC component.
9
TRANSIENT RESPONSE OF CT
DC transient flux depends on time constant of
fault loop impedance (TN), as shown in Fig. 7.
10
Fig. 7:CT induction in DC-offset short circuit current
TRANSIENT RESPONSE OF CT
The increase of induction determines the
required over-dimension of CT to enable the
transformation of a fully off-set fault current.
DEMAGNETISATION:
Interruption of fault current by circuit breaker is
done at the instant of current zero crossing.
At this point, induction is at a maximum.
Following fast fault clearance, CT may still be
heavily magnetized due to DC component at
the instant of breaker opening. 11
TRANSIENT RESPONSE OF CT
Demagnetization takes place via a transient
current in the secondary circuit of CT.
12
Fig. 8: Magnetizing and demagnetizing of CT
TRANSIENT RESPONSE OF CT
The induction is not reduced to zero as a
result of this, but only down to remnant
induction BR.
This state is reached approximately after 3
CT (secondary) time constants.
Unsuccessful Auto-Reclosure:
The most common case for rapid re-closure
onto a fault is the unsuccessful auto-
reclosure.
13
TRANSIENT RESPONSE OF CT
In Fig. 9, the course of induction for entire
fault cycle (C-O-C-O) is shown.
17
Fig. 11: Magnetization in unsuccessful auto-reclose
TRANSIENT RESPONSE OF CT
CTs with Air Gap:
Air gaps in CT core dramatically reduces
remnant flux. At the same time, the
demagnetizing time is reduced to 1s or less.
In case of larger air gaps (linearized cores),
the DC component is dampened so severely
that a much smaller flux increase is achieved
and the core de-magnetizes very fast.
This following a shortetst auto-reclose, the
flux would have decayed to zero (Fig. 12).
18
TRANSIENT RESPONSE OF CT
25
CT SATURATION
Reduction of DC Current Component:
With closed iron CT, the secondary time
constant amounts to several seconds. The
DC component of the fault current is
transformed correctly.
CTs with linearized core have very short
secondary time constants; thus the DC
component is damped quickly and even
sometimes swings to a negative value.
26
CT SATURATION
When connecting differential protection to
CTs of different types, the through flowing
current would therefore result in a differential
current consisting of the difference between
the DC component transient current of two
CT types. With a sensitive setting (generator
or transformer differential protection), this
may result in in undesired tripping if a
corresponding blocking filter is not provided
in the protection.
27
CT SATURATION
This however is not a problem with Fourier
filtering used in digital protection.
In computer relaying, the CT error can be
computed and corrected inside the
computer relay if the CT characteristics and
the burden impedance are given as inputs
to the computer relay. This clearly can not
be done in conventional relays.
28
VOLTAGE TRANSFORMER
Voltage transformer is much simpler than the
current transformer since the voltage and
hence the flux density in the core is nearly
constant, whereas the flux density in the core
of a current transformer varies with the
current. A typical connection of voltage
transformer is shown in Fig. 15.
The primary winding is connected between
lines so that full line voltage is impressed on
it. In contrast, in CT, primary is connected in
one line and carries full line current.
29
VOLTAGE TRANSFORMER
32
VOLTAGE TRANSFORMER
By making capacitive and inductive
reactances equal, the secondary phase
voltage becomes in phase with primary
voltage.
In general, the steady state error of capacitive
voltage transformer (CVT) is negligible.
The transient response of CVT is of some
concern in relay design.
33
VOLTAGE TRANSFORMER
As the primary voltage changes suddenly
from its pre-fault value to its (smaller) post-
fault value, the output voltage undergoes a
subsidence transient before settling to its
final steady state value.
The subsidence transient magnitude
depends upon CVT equivalent circuit
parameters, burden impedance and power
factor, and upon angle of incidence of the
primary fault.
34
VOLTAGE TRANSFORMER
36
37