easYgen-3200

Operational Modes

marked

CERTIFICATE of
Design Assessment
by ABS
American Bureau of Shipping & Affiliated Companies

Proprietary Information
DynamicsLCDTM
The 320x240 pixel graphic interactive LC display provides soft keys
whose functionality changes depending on application (see FlexAppTM)
and operation.

Delta / Wye Alarm screen


Voltage
Configure
Automatic parameter

Manual Additional
measured values
STOP
Acknowledge
centralized alarm
Change operation
modes

Engine start / stop Breaker control

2
Proprietary Information
DynamicsLCDTM
The display topography:

Last alarm

Current operation
i.e. Cranking, loading,
start pause, etc.

Single line diagram


and operation mode

3
Proprietary Information
DynamicsLCDTM
Symbol meanings in the single line diagram

Voltage detected

Rotation field clockwise

Rotation field counter clockwise

Import/Export Mains power

Delayed engine monitoring expired

Engine speed detected


4
Proprietary Information
Status Menu
Navigation through the screens measured values

Advance to Next Screen

Select subdirectory

Screen Name

5
Proprietary Information
Status Menu

Setpoints

6
Proprietary Information
Status Menu

Synchroscope

7
Proprietary Information
Status Menu

Event History

8
Proprietary Information
Status Menu

Counters and Service

9
Proprietary Information
Status Menu

Measured Values

10
Proprietary Information
Status Menu

Version and Time

11
Proprietary Information
Status Menu

Online
diagram
visible

12
Proprietary Information
Parameter Menu
Navigation through the parameter screens
Press Parameter soft key

Select subdirectory

Screen Name

13
Proprietary Information
Parameter Menu
Navigation through the parameter screens
System overview Parameter

Screen name

Pathway to
this screen

14
Proprietary Information
Parameter Menu
Change a Parameter

Move black cursor


line up and down

Press Enter soft key to select


parameter to be changed

15
Proprietary Information
Parameter Menu
Changing a Parameter

Move cursor if value


is numeric

Other parameters are


cleared from display

Old value

New value

Select value + / - soft keys


16
Proprietary Information
Operation Modes
Changing the operation mode may
be performed via:
a shutdown alarm class
the HMI soft keys
the LogicsManager

Automatic mode

Manual mode

Stop mode
17
Proprietary Information
Operation Modes
A shutdown alarm will change the operating mode to STOP

18
Proprietary Information
Operation Modes

Changing the operation mode via HMI soft keys

Automatic

Manual

STOP

19
Proprietary Information
Start / Stop in Manual
Generator circuit breaker: Mains circuit breaker
Start/Stop via push buttons Manual operation of MCB only
Conditions for AUTO are ignored LM: Enable MCB is true (default
Start prevented if active C - F class alarm DI6)
No automatic start if mains failure detected Open / close MCB
Open / close GCB

20
Proprietary Information
Start / Stop in Manual

Stop command issued

Start/run command issued

Unit is trying to close the breaker

Unit is trying to open the breaker


21
Proprietary Information
Start / Stop in Auto
Generator:
Start conditions Stop conditions
LM: Start in auto is true LM: Start conditions are false
may be used with load dependent start/stop function Alarm class C-F detected
LM: Start w/o load is true LM: Stop in auto
LM: Critical mode is true
Loss of mains {GCB/MCB} (Emergency mode) LM: Inhibit emergency mode
Mains voltage/frequency out of operating range
Mains rotation field wrong
Fail to close MCB (if parameter is enabled)

Mains:
Close MCB: Open MCB:
Mains are within accepted limits Dependent upon breaker logic
DI7 is de-energized (MCB is open) For mains decoupling
LM: Enable MCB is true (default DI6)
Conditions for synchronization or
dead bus closing are met
22
Proprietary Information
Start / Stop logic
Diesel engine
- Pre-glow function
- Fuel or Stop solenoid activation
- Crank/start circuit control

Gas engine
- Ignition
- Gas valve
- Crank/start circuit control

External logic
- Fuel solenoid as a start request to external controllers
- External control must take care of start sequence no start failure

23
Proprietary Information
FlexAppTM

There are four application modes available:

Parameter name: in product spec:

[GCB/MCB] [GCB/MCB open/close {2oc}]


[GCB] [GCB open/close {1oc}]
[GCB open] [GCB open {1o}]
[none] [0-CB-Mode {0}]

24
Proprietary Information
FlexAppTM - The 4 Application Modes - [GCB/MCB]
Two breaker mode
Mains/utility breaker (MCB) and generator breaker (GCB)
Generator protection for shutdown and GCB open command
Single or multiple genset operation
GCB & MCB open close command
Automatic mains failure (AMF) / emergency mode

Fixed Input Fixed Output


DI 8 reply GCB (B contacts) DO 6/7 GCB close / open
DI 7 reply MCB (B contacts) DO 8/9 MCB close / open
25
Proprietary Information
FlexAppTM - The 4 Application Modes - [GCB]
One breaker mode
Generator breaker (GCB) control
Generator protection for shutdown and GCB open command
Single or multiple genset operation
GCB open/close command Grey= breaker status only:
MCB control is external

Fixed Input Fixed Output


DI 8 reply GCB (B contacts) DO 6/7 GCB close / open
DI 7 reply mains parallel
26
Proprietary Information
FlexAppTM
It is possible to not
display mains data
Application mode [GCB]

Application mode [GCB/MCB]

27
Proprietary Information
FlexAppTM - The 4 Application Modes - [GCB open]
Breaker open mode
Generator breaker open only
Generator protection for shutdown and GCB open command
Single or multiple genset operation
GCB open command (shunt trip)

Fixed Input Fixed Output


DI 8 reply GCB (B contact) DO 7 GCB open
28
Proprietary Information
DI 7 reply MCB (mains parallel)
FlexAppTM - The 4 Application Modes - [none]
Base mode
No breaker control
Single or multiple genset operation
Generator and engine protection
All breaker control is external

Fixed Input
DI 8 reply GCB (B contact)
DI 7 reply MCB (mains parallel)
29
Proprietary Information
FAQ
Frequently Asked Questions

How can I reset the maintenance counter?

How can I define the loss of mains condition


in order to activate the emergency mode?

30
Proprietary Information
FAQ
How can I reset the maintenance counter?
The maintenance hours counter decreases as the operation hours counter increases.
The maintenance days counter decreases as the Internal calendar clock increases.
When a count down timer reaches 0 an alarm is issued. The reset procedure is as follows:
Step 1:

31 Enter password (see config. manual)


Proprietary Information
FAQ
How can I reset the maintenance counter?

Step 2:

Symbol appears only if the


required password is active

Press Next page Counters and


service buttons to get to counters screen.
32
Proprietary Information Next, press the Tool symbol button.
FAQ
How can I reset the maintenance counter?

Step 4:

Select counter to reset. Press enter, select YES, press enter.


Now the alarm may be acknowledged in
the alarm list.
33
Proprietary Information
FAQ
How can I define the loss of mains condition, in order to activate the
emergency mode?
The operating range defines the loss of mains conditions.
The thresholds from the mains monitoring are used for protection
purpose, not for the loss of mains detection!
Adjust the Operating range
voltage / frequency of the mains

34
Proprietary Information