Introduccin
Importancia de los Conceptos Basicos
-Afortunado
-Mentores
*Su Denominador Comn- Gran Dominio De Los Conceptos Basicos
-Explicamelo Como Si Yo Fuera Un Ninho De 15 Anhos
-Perspectiva De Mis Preasentaciones: Corresponsal Tecnico
*Apoyado por un grupo de profesionales y nuestro propio esfuerzo y protocol de Investigacion
*Such luxuries disappeared during the Dark Ages, and large-scale air-
conditioning efforts didn't resurface in the West until the 1800s, when well-
funded American engineers began to tackle the problem. In the intervening
centuries, fans were the coolant of choice.
HISTORIA GENERAL DEL AIRE
ACONDICIONADO
(50 CFM)
(262 CFM)
http://www.cfm.va.gov/til/dguide/dgsurg.pdf
Que es y Como Lo Hace?
La Magia de Self Sensing Pumps
Self-Sensing pumps. Un poco de historia
Importancia del tema historico para mi.
Todo comenzo con valvulas de tres vias:Caudal constante
Denominador comun en los cambios historicos
La valvula de dos vias: Caudal Variable
Ahorro En Consumo Electrico- Riding The Curve
Mas Ahorro Todavia- VFD
Pero Necesitamos Caudal Constante Minimo en el
EnfriadorPor Que? Como se logra?
Congelamiento en el Evaporador
Tuberia Con Valvula De Desvio (By-Pass Valve)
Algunas Valvulas De Tres Vias
Circuito Primario Secundario- Solucion de Oro
Hablando de Valvulas de Dos Vias
Recordemos el Cv y su importancia
Cv = Q x Raiz de 1/Delta P
Son los GPM que fluiran a traves de una valvula u
orificio cuando su caida en presion = 1 psi!!!
Hablando de Historia:
Valvulas de Bola vs de Globo
Metodo Tradicional
Sensor de Presion
2/3 Partes Del Largo Hidronico
Curvas de Bombas
Pruebas de Laboratorio
Curvas de Bombas
140
120
50
KS Modelo 4009
Con impeller de 8.00
Pruebas a1760 RPM
Pump System
Capacity Efficiency BHP Head
Head (Ft)
(GPM) (%) (HP) (Ft)
0.00 59.55 -0.16 2.86 0
100.00 59.74 44.25 3.40 6.91
200.00 58.00 65.04 4.50 24.91
300.00 52.76 73.03 5.47 52.76
400.00 42.84 71.44 6.05 89.83
500.00 27.43 56.08 6.17 135.74
Bombas Self-Sensing
KS Modelo 4007
Con motor de 7.5HP y VFD
Con un impeller de 7.50 dimetro
Constant Flow
Variable Flow
Self-Sensing Pumps
100
Valvulas cerradas Valvulas abiertas
Flujo minimo Flujo Maximo
90
80
70
Head (Ft.)
60
50
40
30
20
10
0
0 50 100 150 200 250 300 350 400 450
Flow (GPM)
Self-Sensing Pumps
100
Valvulas cerradas Valvulas abiertas
Flujo minimo Flujo maximo
90
80
70
60
Head (Ft.)
50 60 Hz
40 50 Hz
30
40 Hz
30 Hz
20
20 Hz
10
0
0 50 100 150 200 250 300 350 400 450
Flow (GPM)
Self-Sensing Pumps
100
Valvulas cerradas, Valvulas abiertas,
90
Flujo minimo Flujo maximo
80
70
60
Head (Ft.)
50
Curva de Control 60 Hz
40
30
20
10
20 Hz
0
0 50 100 150 200 250 300 350 400 450
Flow (GPM)
Self-Sensing Pumps
Cuando la demanda aumenta, la bomba
se mueve a la derecha (abajo) en la curva
de la bomba.
80
70
Flujo Constante
60
Head (Ft.)
50
40
60 Hz
30
20
10
20 Hz
0
0 50 100 150 200 250 300 350 400 450
Flow (GPM)
Self-Sensing Pumps
100
Valvulas cerradas, Valvulas abiertas,
Flujo Minimo flujo maximo
90
80
Presion Constante
70
60
Head (Ft.)
50
40 60 Hz
30
20
10
20 Hz
0
0 50 100 150 200 250 300 350 400 450
Flow (GPM)
Self-Sensing Pumps vs. Sensors
Los sensors son frecuentemente colocados en el
lugar incorrecto en el Sistema, colocar el sensor en
el lugar incorrecto resulta en deficiencias del
Sistema.
90
The SelfSensing pump has an advantage over
sensors because you no longer have to worry about 80
Head (Ft.)
50
Control Curve
You can quickly adjust the control head on a 40
SelfSensing pump in the field. Adjusting the control
30 Control Head
head is akin to moving the sensor to a new more
optimal location in the building. This optimization 20
If you are having trouble deciding whether to use a SelfSensing pump or a sensor, just ask:
How often does the construction team know in advance what the optimum location will be?
How often does the construction team place the sensor in the perfect location?
Self-Sensing Pumps vs. Sensors
Vigas Radiantes
Historia
Historia
Historia
Vigas Frias
Esta figura ilustra cmo el suministro de
agua del circuito primario entra en el LMB
en el puerto (PS). El agua de retorno del
circuito de terminal secundario entra en la
LMB en el terminal (Tr). A medida que la
unidad necesite calefaccin o enfriar, el
circulador de inyeccin (Ci) vara la
velocidad/flujo para mezclar las dos
temperaturas de agua para satisfacer las
necesidades de la zona.
Este suministro de agua mezclada se
enva a la terminal, por el puerto (TS) y el
agua de retorno primarios sale de la LMB
por el puerto (PR). Hay una gran variedad
de tamaos de bloques que pueden
manejar caudales de hasta 30 gpm, lo que
permite adaptarse a casi todas las
instalaciones.
Ventilacin por desplazamiento
VIDEO
VENTILACION POR MEZCLA
Ventilacin por desplazamiento
Beneficios
Mejor Calidad de Aire
Interior
Se puede reducir el
suministro de aire
exterior.
VENTILACION POR DESPLAZAMIENTO
Suministra el Aire a Bajas
Velocidades.
Temperatura del Aire 65F.
No Hay Mezcla.
Enfra solo de 0-6 de Altura.
Fuentes de Calor son la
Causa del movimiento de
Aire.
Beneficios
Silencioso
Debido a las bajas
velocidades.
Ideal para Escuelas,
anfiteatros y cuartos
de pacientes
Aplicaciones
Aeropuertos
Teatros
Escuelas
Casinos
Hospitales
Espacios
Industriales
Restaurantes
Oficinas
Supermercados
CALIDAD DEL AIRE INTERIOR
= cpe / cpbz
= efectividad en la eliminacin de
contaminantes de la zona ocupada
Mezcl
a
54/54F WB 75F DB
50%RH
T (20F)
Vh = nAH / 60 (pcm)
Ts = Tf fQt / (60CpV)
Donde:
Tf = Th Thf
*Check List
*Pero La Mas Importante
De Todas
Consultoria Tcnica de Las Fabricas
Quirfanos
Fuentes de Contaminacin y
Control de las Mismas
Dentro de un Quirfano
Fuentes Control
Aire exterior Filtros de alta
Infiltracin de aire eficiencia (HEPA)
El paciente mismo Presin positiva
y el personal Sistema de
medico distribucin de aire
laminar
Biggest Contamination Source
Flujo Laminar
Mas conocido
Unidireccional
Retornos a nivel del piso
Desafos en los Sistemas de Distribucin
de Aire
Espacio en el Techo
La mayora de los equipos estn montados en el Techo
(Cielorraso)
ASHRAE limita los CFM/ft2 de los difusores laminares
Desafos en los Sistemas de Distribucin
de Aire
Cargas Trmicas
Constantemente aumentando (Equipos Tecnolgicos)
Cambios rpidos de temperatura
(Cirugas Cardiovasculares)
Desafos en los Sistemas de Distribucin de Aire
Aragonite
Hard
Condenser
scale tube wall