This document provides guidance on selecting the proper size of conduit or trunking based on the number and size of cables being installed. It includes tables with cable and conduit/trunking factors that are used to calculate the total factor for the cables and select a conduit/trunking with an equal or greater factor. The example shows how to use the tables to determine that a 20mm conduit is required for a 3m run with 6 cables rated at 4mm2 each, as their total cable factor of 348 is less than the 20mm conduit factor of 286. Proper spacing of cables is important to prevent damage and excessive temperature increases during operation.
This document provides guidance on selecting the proper size of conduit or trunking based on the number and size of cables being installed. It includes tables with cable and conduit/trunking factors that are used to calculate the total factor for the cables and select a conduit/trunking with an equal or greater factor. The example shows how to use the tables to determine that a 20mm conduit is required for a 3m run with 6 cables rated at 4mm2 each, as their total cable factor of 348 is less than the 20mm conduit factor of 286. Proper spacing of cables is important to prevent damage and excessive temperature increases during operation.
This document provides guidance on selecting the proper size of conduit or trunking based on the number and size of cables being installed. It includes tables with cable and conduit/trunking factors that are used to calculate the total factor for the cables and select a conduit/trunking with an equal or greater factor. The example shows how to use the tables to determine that a 20mm conduit is required for a 3m run with 6 cables rated at 4mm2 each, as their total cable factor of 348 is less than the 20mm conduit factor of 286. Proper spacing of cables is important to prevent damage and excessive temperature increases during operation.
Not only must it be possible to draw cables into completed
conduit and trunking systems, but neither the cables nor their enclosures must be damaged in the process. If too many cables are packed into the space available, there will be a greater increase in temperature during operation than if they were given more space. It is important to appreciate that grouping factors still apply to cables enclosed in conduit or trunking. To determine the conduit size needed, multiply the quantities of each size of cable by the appropriate factor, compare the total with the conduit figures shown. For situations not covered by these tables, the requirement is that a space factor of 45% for conduit and 45% for trunking must not be exceeded. This means that not more than 45% of the space within the conduit or trunking must be occupied by cables, and involves calculating the cross- sectional area of each cable, including its insulation, for which the outside diameter must be known. To use the ({Tables 4.14 to 4.17}) the cable factors for all the conductors must be added. The conduit or trunking selected must have a factor (otherwise called 'term') at least as large as this number. Table 4.14 - Cable factors (terms) for conduit and trunking Factor for Factor for Type of Conductor Factor for trunking trunking pvc conductor c.s.a. (mm) conduit thermosettin insulation g insulation Solid 1.0 16 3.6 3.8 Solid 1.5 22 8.0 8.6 Stranded 1.5 22 8.6 9.1 Solid 2.5 30 11.9 11.9 Stranded 2.5 30 12.6 13.9 Stranded 4.0 43 16.6 18.1 Stranded 6.0 58 21.2 22.9 Stranded 10.0 105 35.3 36.3 Stranded 16.0 145 47.8 50.3 Stranded 25.0 217 73.9 75.4 Table 4.15 - Cable factors (terms) for straight runs up to 3m. Type of conductor Conductor c.s.a. (mm) Cable factor Solid 1.0 22 Solid 1.5 27 Solid 2.5 39 Stranded 1.5 31 Stranded 2.5 43 Stranded 4.0 58 Stranded 6.0 88 Stranded 10.0 146 Table 4.16 - Conduit factors (terms) Length of run between boxes (m) 1 2 3 4 5 6 8 10 Conduit, - straight 16mm 290 290 290 171 171 167 158 150 20mm 460 460 460 286 278 270 256 244 25mm 800 800 800 514 500 487 463 442 32mm 1400 1400 1400 900 878 857 818 783 Conduit, one - bend 16mm 188 177 167 158 150 143 130 120 20mm 303 286 270 256 244 233 213 196 25mm 543 514 487 463 442 422 388 258 32mm 947 900 857 818 783 750 692 643 Conduit, two - bends 16mm 177 158 143 130 120 111 97 86 20mm 286 256 233 213 196 182 159 141 25mm 514 463 422 388 358 333 292 260 32mm 900 818 750 692 643 600 529 474 For 38mm conduit use the 32mm factor x 1.4. For 50mm conduit use the 32mm factor x 2.6. For 63mm conduit use the 32mm factor x 4.2. Table 4.17 - Trunking factors (terms) Dimensions of trunking (mm x mm) Factor 37.5 x 50 767 50 x 50 1037 25 x 75 738 37.5 x 75 1146 50 x 75 1555 75 x 75 2371 25 x 100 993 37.5 x 100 1542 50 x 100 2091 75 x 100 3189 100 x 100 4252 Example 1: The following single-core p.v.c. insulated cables are to be run in a conduit 6 m long with a double set: 8x1mm2, 4x2.5mm2 and 2x6mm. Choose a suitable size.
Consulting {Table 4.14} gives the following cable factors:
16 for 1 mm, 30 for 2.5 mm and 58 for 6 mm
Total cable factor is then (8 x 16) + (4 x 30) + (2 x 58)
= 128 + 120 + 116 = 364 EXAMPLE 1. What size of conduit is required for 6 No. 4mm cables in a three metre run with no bends? 6 x 58 = 348 So the nearest size of conduit with a factor greater than 348 is 20m